Input And Output Power Connections - Large Enclosure; Figure 6 Power Wiring To Tm115; Figure 7 Power Wiring To Tm230 - Liebert Liqui-tect MC68HC16Z1 User Manual

Liqui-tect monitoring system
Table of Contents

Advertisement

2.4.2

Input and Output Power Connections - Large Enclosure

CAUTION
!
The 115VAC/230VAC Transformer Module must be connected to a branch circuit with 15A
branch circuit protection.
This equipment is intended to be installed by a qualified and certified electrician who must
review and approve customer supplied wiring and circuit breakers, verify correct input and
grounded connections to ensure compliance with the technical standards and national and
local electrical codes.
The Transformer Module shall be used only as indicated by the manufacturer.
WARNING
!
Be sure that the power wiring is disconnected from the Liqui-tect panel before installing any
wiring to this unit.
Input Power Connections
To connect electrical power to the Transformer Module:
1. Install electrical wiring from utility power to the Transformer Module.
2. Use copper wires only; proper wiring to use for power is 14/2 AWG copper wire with ground.
3. For the TM230 only: strip wires 3/8" (9.6mm).
Note: For the TM115, wires are pre-stripped 0.4" (10.2mm) at the factory.
4. Connect the wiring as follows:
TM115
White wire
Black wire
Green wire
5. Secure the incoming electrical service wires to the TM115 input wires with wire nuts as shown in
Figure 6 or to the TM230 connectors as shown in Figure 7.
24 VAC Output Power Connections
To connect to the 24VAC outputs:
1. Install electrical wiring from device requiring 24VAC power to the Transformer Module.
2. Use copper wire only; proper wiring to use for power is 18, 20 or 22 AWG copper wire. Strip wire 1/4".
3. There are two 24 VAC output connectors (TB1 and TB2). Terminate wires to the connector as
shown in Figures 6 and 7. TB1 and TB2 are NOT polarity sensitive.
4. Secure the wires to the connector.
Figure 6
Power wiring to TM115
TM115
Wire nuts
connecting
electrical
wiring
Troubleshooting - Transformer Module
A common problem and possible solution are shown in the table below. For further information or if
you have other problems with the unit, consult your local dealer, Liebert representative or the Liebert
Worldwide Support Group.
Problem
24VAC power not available
from TB1 or TB2
TM230
Connection Type
Neutral (L2)
Neutral
Line (L1)
Power (Line)
Ground lead
Ground
Knockout for
external wiring
Ground
24VAC output
(TB1)
Possible Solution
Check fuse for respective
output (TB1 or TB2).
11
Figure 7
Power wiring to TM230
TM230
Neutral
(L2)
Replacement Fuse Part Numbers
• LITTLEFUSE 218002
• BUSSMANN GDC-2A
Installation
Knockout for
external wiring
Ground
Line (L1)
24VAC output
(TB1)