6.2

Setup System - Overview

The Setup System screen displays six options that allow you to configure zones with cable, alarm
outputs, the re-alarm delay time, log points to create a map and system details, such as changing the
login password or the system date and time:
• Setup ZN1 Zone 1
• Setup ZN2 Zone 2
• Setup Alarm Outputs
• Setup Re-Alarm Delay
• Setup Mapmode
• Setup System Info
6.3

Setup System - Setup ZN1 Zone 1

The Liqui-tect panel has two independent zones—ZN1 and ZN2—that
may be configured individually. Each zone can monitor up to 5,000 ft.
(1524m) of cable.
If neither zone is configured as connected, the screen displays the
message:
WARNING! NO ZONES ARE INSTALLED
To configure the first zone:
Log In and Choose Setup System
• From the Main Menu, use the arrows
Control, then press Enter
• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows
Setup System, then press Enter .
Select Zone 1 to Configure
• From the Setup System Menu, shown at right, use the arrows
and press Enter .
• Use the steps following Table 8 to change the default settings for Zone 1.
Table 8 shows the features you may change for Zone 1, along with the default settings. By default,
Zone 1 is not connected.
To activate Zone 1, you must specify it as connected. Other features that may be altered include the
name of the zone, the measurement units, and the sensitivity for detection of water and of contamina-
tion. You may also initiate automatic calibration, during which the Liqui-tect panel determines the
length of cable and parameters.
Table 8
Default settings - Zone 1
Feature
CONNECTED
LABEL
UNITS
AUTO CALIBRATE
SENSITIVITY FOR
WATER DETECT
SENSITIVITY FOR
CONTAMINATED
(see 6.1 - Login for help)
Default
N (Not connected)
ZONE 1
FT (feet)
Automatically calculates cable length
150 UA
50 UA
25
to choose System and
to choose
Y (Connected)
Any name (up to eight characters)
M (meters)
Allows adjustment to calculated length of cable
Can define between 25µA and 300µA
Can define between 20µA and 300µA
System and Control Options
Setup System Menu
> SETUP ZN1 ZONE 1
SETUP ZN2 ZONE 2
SETUP ALARM OUTPUTS
=NEXT
=SELECT
SETUP REALARM DELAY
SETUP MAPMODE
SETUP SYSTEM INFO
Setup Zone 1 Menu
SETUP ZN1 ZONE 1
> CONNECTED:
N
LABEL: ZONE 1
=NEXT
=SELECT
UNITS: FT
AUTO CALIBRATE
WATER DETECT:150 UA
CONTAMINATED:050 UA
to choose Setup ZN1 Zone 1
Other Options