Service And Maintenance - Crown Boiler BWC151 Installation Instructions Manual

Bwc series high efficiency gas-fired hot water direct vent condensing boilers
Table of Contents

Advertisement

WARRANTY DOES NOT COVER BOILER DAMAGE OR MALFUNCTION IF THE FOL-
LOWING STEPS ARE NOT PERFORMED AT THE INTERVALS SPECIFIED.
1) Continuously:
a.
Keep the area around the boiler free from combustible materials, gasoline and other
flammable vapors and liquids.
b.
Keep the area around the combustion air inlet terminal free from contaminates.
c.
Keep the boiler room ventilation openings open and unobstructed.
2) Monthly Inspections:
a.
Inspect the vent piping and outside air intake piping to verify they are open, unobstructed and free
from leakage or deterioration. Call the service technician to make repairs if needed.
b.
Inspect the condensate drain system to verify it is leak tight, open and unobstructed. Call the service
technician if the condensate drain system requires maintenance.
c.
Inspect the water and gas lines to verify they are free from leaks. Call the service technician to make
repairs if required.
WATER LEAKS CAN CAUSE SEVERE CORROSION DAMAGE TO THE BOILER OR
OTHER SYSTEM COMPONENTS. IMMEDIATELY REPAIR ANY LEAKS FOUND.
4) Annual Inspections and Service: In addition to the inspections listed above, the following should be per-
formed by a service technician once every year.
a.
Test the low water cutoff by pressing the "Test" button located at its end. The yellow light should
come on and "E12" should flash on the display. Push the reset button on the display to restore normal
operation. If the yellow light does not come on, determine why the low water cutoff is not working
properly.
b.
Follow the procedure for turning the boiler off found in the BWC Series Lighting and Operating
Instructions.
c.
Inspect the wiring to verify the conductors are in good condition and attached securely.
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.
WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION. VERIFY
PROPER OPERATION AFTER SERVICING.
XIII. Service and Maintenance
IMPORTANT
CAUTION
CAUTION
68

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bwc070Bwc090Bwc120

Table of Contents