TABLE 12.0c: RIELLO BURNER CONFIGURATION AND SETUP DATA
BOILER MODEL
BURNER MODEL
STANDARD
NOZZLE
PUMP PRESS (psi)
TURBULATOR
AIR
SHUTTER SETTING
DRAFT OVER FIRE
(in w.c.)
MAX. SMOKE
(bacharach scale)
FLUE CO
(%)*
2
MIN.
MAX
* Also see NOTICE below
Smoke and CO
levels may vary over time as the result of factors such as fuel chemistry, air
2
temperature, and combustion air contamination. To minimize soot production, and thereby help
assure continued efficient, reliable operation, observe the following precautions:
Never leave the boiler in operation at a smoke level exceeding #1, even if this means that
the boiler must be operated at a CO
Never leave the boiler in operation with a CO
if the smoke level at this CO
In cases where field conditions are known to vary significantly, a good practice is to
provide a CO
the burner is left in operation. The size of this cushion depends on local experience, but is
typically 0.5% - 1.0%. For example, using a 1.0% cushion, if the burner reaches a #1 smoke
at 13.5%, the burner would be left in operation with a CO
The following procedure should be performed on a weekly basis:
For boilers equipped with a float low water cut-off, blow down the low water cut-off following the low water cut-off
manufacturer's instructions. During this blow down, the low water cutoff should shut down the burner. If it does not, the low
water cut-off should be replaced immediately.
The following procedure should be performed on an annual basis:
1) Turn off electrical power and oil supply to the boiler.
2) Inspect the Hydrolevel CG450 low water cut-off - Remove and inspect the probe for scale and sediment buildup. Clean
any sediment or scale from the probe with a scouring pad or steel wool. Consult the Hydrolevel CG450 manual for any
additional maintenance information. Test the low water cut-off before placing the boiler back into service.
3) Allow the boiler to cool to room temperature and drain the boiler. Remove the 1-1/2" plug from the unused return tapping.
Use a flashlight to inspect the bottom row of pushnipples for accumulated scale or mud. If a significant amount is present, use
the following procedure to clean the inside of the heat exchanger:
KSB065
KSB075
40F5
DEL
0.60/60A 0.85/60W 1.00/60A
150
0
2.60
-0.02
#1
11.0
13.0
is zero and burner operation otherwise appears OK.
2
"cushion" between the CO
2
XIII Service and Maintenance
KSB100
KSB125
40F5
40F5
DEL
DEL.
150
150
2
3
2.85
3.8
-0.02
-0.02
#1
#1
11.0
11.0
13.0
13.0
NOTICE
level below the maximum shown Table 12.0.
2
outside the range shown in Table 12.0, even
2
corresponding to a #1 smoke and that at which
2
34
KSB150
KSB175
KSB200
40F5
40F10
DEL
HAGO
1.25/60B 1.35/45B
1.65/45B
150
150
3
1.5
4.5
3
-0.02
-0.02
#1
#1
11.0
11.0
13.0
12.5
at or below 12.5%.
2
40F10
DEL
150
2
3.8
-0.02
#1
11.0
12.5