Hitachi SJ300-EL Series Instruction Manual Supplement page 42

Inverter for elevator applications three-phase input 200v class; three-phase input 400v class
Hide thumbs Also See for SJ300-EL Series:
Table of Contents

Advertisement

6. Observe the SJ300EL torque monitor by setting keypad display to monitor parameter
D012. Display is in percent of full load torque. Adjust the counterweight so that the torque
monitor reads less than 15% of rated torque.
7. Adjust H033 (I
) until the torque monitor reading (parameter D012) is less than 5% of
0
rated torque.
8. Make sure it is safe to run the car at contract (maximum design) speed.
9. Run the car at contract speed fully loaded and at minimum load, in both directions. Be
sure the torque and current never exceed 150% of the drive full load ratings. Confirm this
by monitoring parameters D002 for current in amperes, and D012 for torque in percent of
full load torque.
10. Check for any unstable or irregular elevator motion. Manually adjust the motor
parameters if necessary.
See page
47.
42
Appendix A - Auto-tuning Procedure