Hitachi SJ100DN DeviceNet Series Addendum Instruction Manual Addendum page 85

Sj100dn devicenet series
Hide thumbs Also See for SJ100DN DeviceNet Series Addendum:
Table of Contents

Advertisement

"B" Group Parameters
Func.
Name
Code
B212 Level of electronic thermal
setting, 2nd motor
B_13 Electronic thermal characteristic
B213 Electronic thermal characteristic,
2nd motor
B_21 Overload restriction operation
mode
B_22 Overload restriction setting
B_23 Deceleration rate at overload
restriction
B_31 Software lock mode selection
B_82 Start frequency adjustment
B_83 Carrier frequency setting
B_84 Initialization mode (parameters
or trip history)
DeviceNet Class ID = 103
Inst Attr Size
Range
2
112
2
5% to 120% rated
current, in A
1
113
1
0 Reduced torque
1 Constant torque
2 Reduced
torque2
2
113
1
0 Reduced torque
1 Constant torque
2 Reduced
torque2
1
121
1
0 Disabled
1 Enabled for
acceleration and
constant speed
2 Enabled for
constant speed
only
1
122
2
50% to 150%
rated current, in A
1
123
2
0.3 – 30.0
1
131
1
0 all parameters
except B_31 are
locked if [SFT] is
ON
1 all parameters
except B_31 and
output freq. F_01
when [SFT] is ON
2 all parameters
except B_31 are
locked
3 all parameters
except B_31 and
F_01 are locked
1
182
2
0.5 – 9.9 Hz
1
183
1
0.5 – 16.0kHz
1
184
1
0 Trip history
clear
1 Parameter
initialization
SJ100DN Inverter
Get/
Scaling
Set
10
G/S
G/S
G/S
G/S
100
G/S
10
G/S
G/S
100
G/S
10
G/S
G/S
85