Network Control and Monitoring
Inverter Control Sequence 2 – In this second sequence, the DeviceNet host computer
will control the inverter (Run/Stop) and also provide values for output frequency / accel /
decel (overrides F_01, F_02, and F_03). This sequence assumes that you have success-
fully completed Control Sequence 1 on the previous page.
a. Confirm that the motor is stopped.
b. Turn ON the Network Reference bit (bit 6) in Word 0 as shown below. This
indicates to the inverter that the network will supply real-time profile values for
output frequency / accel / decel. (The Network Control bit should still be ON.)
DO NOT turn on the FW Run bit (bit 0) yet.
Inverter Polled I/O
Consumed (Input)
Word 0
c. Refer to the values for Word 1, Word 2, and Word 3 listed below. With the host
computer, set the values as indicated.
Word 1 (Output Frequency) = 2000 decimal (20.00Hz)
Word 2 (Acceleration time) = 100 decimal (10.0 seconds)
Word 3 (Deceleration time) = 100 decimal (10.0 seconds)
The host computer's polled I/O output data should match the values below.
Word 0
Word 1
Word 2
Word 3
NOTE: The scaling of the polled I/O data for output frequency /accel / decel values
corresponds to the network scale factors for parameters F_01, F_02, and F_03, respec-
tively. A listing of inverter parameters and scale factors is in the "Network Register
Map" on page 78.
d. Turn ON the FW Run bit (bit 1) in Word 0 as shown below. The motor will now
begin to run. The output frequency will be 20.00Hz. To verify the motor speed,
monitor D_01 on the inverter display, or use the host computer to observe the
actual output frequency reported in the polled I/O.
Word 0
High byte
MSB
LSB
0 0 0 0
0 0 0 0
Network Reference
Network Control
High byte
MSB
LSB
0 0 0 0
0 0 0 1
0 0 0 0
0 1 0 1
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
High byte
MSB
LSB
0 0 0 0
0 0 0 0
Network Reference
Network Control
Low byte
MSB
LSB
0 1 1 0
0 0 0 0
FW Run
Low byte
MSB
LSB
0 0 1 0
0 0 0 0
1 1 0 1
1 1 0 0
0 1 1 0
0 1 0 0
0 1 1 0
0 1 0 0
Low byte
MSB
LSB
0 1 1 0
0 0 0 1
FW Run
Hex
Decimal
0060h
96
Hex
Decimal
0060h
96
07D0h
2000
0064h
100
0064h
100
Hex
Decimal
0061h
97

Advertisement

Table of Contents
loading

Table of Contents