Step 6 – Monitor Test – Verify Network Host Can Monitor Inverter
This step requires that you have completed the previous 5 steps, and that the powerup
test during the installation was successful (see "Running the Motor" on page 25). At this
point in the procedure, the inverter is using front panel keypad inputs for Run/Stop
commands. The DeviceNet host computer can monitor inverter operation without
actually controlling the inverter. So, you do not have to change any "P Group" parame-
ters from their defaults to do this network monitoring test.
Inverter Status LEDs – The two status LEDs on the
inverter's front panel are to the right of the Stop key.
• MS – Module Status
• NS – Network Status
The status LEDs may be green or red, and may or OFF,
ON, or flashing between OFF and ON. The table below
shows how to interpret the status LED indications. (At
this point, the correct status is MS=green, NS=OFF.)
LED
Color
MS
Green
Flashing Green
Red
Flashing Red
OFF
NS
Green
Flashing Green
Red
Flashing Red
OFF
Status
Normal power-ON status
Inverter in standby state
Fatal error (trip E11 or E12)
Trip condition (non-fatal)
Inverter power is OFF
Connected to network/online
Connected to network/idle
Critical network error
Communications time-out
Power OFF or DeviceNet offline
SJ100DN Inverter
POWER
HITACHI
5 0.0
RUN
Hz
PRG
A
STOP
MS
RUN
RESET
NS
2
STR
FUNC.
1
Corrective Action
Confirm electrical noise level
is acceptable
Replace inverter
Look up error code in manual
Chapter 6, press Stop/Reset
Check network for:
Disconnected cable
Termination resistor not
present / wrong value
Duplicate MAC IDs
Baud rate settings mis-match
Cable too long
Check network for:
Disconnected cable
Termination resistor not
present / wrong value
Baud rate settings mis-match
Cable too long
51