3-3. How to Initialize the Data (FACTORY SETTING)

1. Select the mode of initialization data to which you want to initialize by [b85].
Japanese version data
EU version data
US version data
2. Set [b84] to "01" to initialize and store.
3. Keep pressing
(If front case is not closed by the screw, difficult to press 3keys.)
4. Additionally press
5. Keep pressing
6. Release all the keys after starts blinking.
FUNC.
1
2
STOP
RESET
[c95] ; INV kW code
01;0.2kW , 02;0.4kW , 03;0.75kW (0.5 kW) , 04;1.5kW , 05;2.2kW ,
06;3.7kW(4.0kW) , 07;5.5kW, 08;7.5kW
----->
Set "00" and store
----->
Set "01" and store
----->
Set "02" and store
keys at the same time.
2
FUNC.
1
STOP
key and release
RESET
keys until "d 00" will blink. (Approximately 2 seconds.)
2
FUNC.
1
ON (press)
ON
ON
ON
1s or more
STOP
key approximately after one second.
RESET
Initialization end
3-8
Release after "d 00"
started blinking