Download Print this page
Carrier Base 24ABC6 Wiring Diagram

Carrier Base 24ABC6 Wiring Diagram

Base 16 air conditioner with puron refrigerant
Hide thumbs Also See for Base 24ABC6:

Advertisement

24ABC6
Baset16 Air Conditioner
with Puronr Refrigerant
*CHS
BLK
or
BLK
RED
(NOTE #9)
RED or BLK
L1
208/230 1Ø
L2
POWER
SUPPLY
EQUIP
GND
(NOTE #14)
YEL/ BLU
*LPS
YEL/PNK
YEL/PNK
*LLS
BLK
YEL/ BLU
Y
R
G
INDOOR THERMOSTAT (NOTE #6)
CONDENSING UNIT CHARGING INSTRUCTIONS
For use with units using R-410A refrigerant
REQUIRED LIQUID LINE TEMPERATURE
Required Subcooling
Liquid Pressure
at Service
Temperature (ºF)
Valve (psig)
6
251
78
259
80
266
82
274
84
283
86
291
88
299
90
308
92
317
94
326
96
335
98
345
100
354
102
100
364
104
102 100
374
106
104 102 100 98
384
108
106 104 102 100 98
395
110
108 106 104 102 100
406
112
110 108 106 104 102
416
114
112 110 108 106 104
427
116
114 112 110 108 106
439
118
116 114 112 110 108
450
120
118 116 114 112 110
462
122
120 118 116 114 112
474
124
122 120 118 116 114
NOTES:
1. Symbols are electrical representation only.
2. Compressor and fan motor furnished with inherent thermal protection.
3. To be wired in accordance with National Electric N.E.C. and local codes.
4. N.E.C. class 2, 24 V circuit, min. 40 VA required, 60 VA on units installed with LLS.
5. Use copper conductors only. Use conductors suitable for at least 75ºC (167ºF).
6. Connection for typical cooling only thermostat. For other arrangements see installation instructions.
7. If indoor section has a transformer with a grounded secondary, connect the grounded
side to the BRN/YEL lead.
8. When start relay and start capacitor are installed, start thermistor is not used.
9. CH not used on all units.
10. If any of the original wire, as supplied must be replaced, use the same or equivalent wire.
11. Check all electrical connections inside control box for tightness.
12. Do not attempt to operate unit until service valves have been opened.
13. Do not rapid cycle compressor. Compressor must be off 3 minutes to allow pressures to equalize
between high and low side before starting.
14. Wire not present if HPS, LPS or CTD are used.

Wiring Diagram

CONNECTION DIAGRAM
*CH
BLK
BLK
BLU
BLU
COMP
CONT
BLU
CAP
S
YEL
BLK
H
C
11
21
R
YEL
C
23
23
YEL
YEL
F
OFM
BRN
YEL
BLK
*CTD
*DTS
*HPS
BLU/PNK
BLK
BLK
BLU/PNK
BRN/YEL
BLK
C
R
INDOOR BLOWER MOTOR
COOLING ONLY
CHARGING PROCEDURE
1. Only use sub cooling charging method
when OD ambient is greater than 70ºF
10 12 14 16
8
and less than 100ºF, indoor temp is
76
74
72
70
68
greater than 70ºF and less than 80ºF, and
78
76
74
72
70
line set is less than 80 ft.
80
78
76
74
72
2. Operate unit a minimum of 15 minutes before
82
80
78
76
74
checking the charge.
84
82
80
78
76
3. Measure liquid service valve pressure by
86
84
82
80
78
attaching an accurate gauge to the
88
86
84
82
80
service port.
90
88
86
84
82
4. Measure the liquid line temperature by
92
90
88
86
84
attaching an accurate thermistor type or
94
92
90
88
86
electronic thermometer to the liquid line
96
94
92
90
88
near the outdoor coil.
98
96
94
92
90
5. Refer to unit rating plate for required
98
96
94
92
subcooling temperature.
98
96
94
6. Find the point where the required subcooling
96
temperature intersects the measured liquid
service valve pressure.
7. To obtain the required subcooling temperature
at specific liquid line pressure, add refrigerant
if liquid line temperature is higher than indicated.
When adding refrigerant, charge in liquid form
using a flow restricting device into suction
service port. Recover refrigerant if temperature
is lower. Allow a tolerance of +/- 3ºF.
Fig. 1 – Wiring Diagram — Model sizes 1- -1/2 - - 5 tons, 208/230- -1
SCHEMATIC DIAGRAM (LADDER FORM)
L1
CONT
11
21
+t
*ST
BRN
EQUIP
1
2
GND
*CHS
*SC
5
(NOTE #8)
*SR
*CH
BRN/YEL
VIO
*LPS
T2
LOGIC
T1
T3
EXTERNAL
Y
POWER
SUPPLY
G
24 V
(NOTE #3)
R
INDOOR
THERMOSTAT
CONT
*CHS
COMP
*CTD
*HPS
1. Compressor damage may occur if system is over charged.
2. This unit is factory charged with R-410A in accordance with
the amount shown on the rating plate. The charge is
adequate for most systems using matched coils and tubing
not over 15 feet long. Check refrigerant charge for maximum
efficiency. See Product Data Literature for required Indoor
air Flow Rates and for use of line lengths over 15 feet.
3. Relieve pressure and recover all refrigerant before system
repair or final disposal. Use all service ports and open all
flow-control devices, including solenoid valves.
4. Never vent refrigerant to atmosphere. Use approved
recovery equipment.
COMP
R
C
S
5
2
*ST
*SC
+t
1
H
*SR
CONT
OFM
23
C
F
CAP
(NOTE #14)
CONT
*DTS
*HPS
T2
LOGIC
T1
T3
*LLS
* CTD
IFR
C
R
EXTERNAL POWER SUPPLY 24 V
LEGEND
FACTORY POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
FIELD POWER WIRING
COMPONENT CONNECTION
FIELD SPLICE
JUNCTION
CONTACTOR
CAPACITOR (DUAL RUN)
CAP
CRANKCASE HEATER
*CH
CRANKCASE HEATER SWITCH
COMPRESSOR
COMPRESSOR TIME DELAY
DISCHARGE TEMP SWITCH
*DTS
HIGH PRESSURE SWITCH
INDOOR FAN RELAY
IFR
LIQ LINE SOLENOID VALVE
*LLS
LOW PRESSURE SWITCH
*LPS
OUTDOOR FAN MOTOR
OFM
START CAPICATOR
*SC
START RELAY
*SR
START THERMISTOR
*ST
* MAY BE FACTORY INSTALLED
CAUTION
330440-101 REV. F
L2
23

Advertisement

loading

Summary of Contents for Carrier Base 24ABC6

  • Page 1: Wiring Diagram

    24ABC6 Baset16 Air Conditioner with Puronr Refrigerant Wiring Diagram CONNECTION DIAGRAM SCHEMATIC DIAGRAM (LADDER FORM) *CHS COMP (NOTE #9) CONT RED or BLK COMP CONT 208/230 1Ø EQUIP POWER *CHS SUPPLY CONT EQUIP (NOTE #8) BRN/YEL (NOTE #14) (NOTE #14)
  • Page 2 Catalog No: 24ABC6---1W Copyright 2010 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 01/10 Replaces: New Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.