4.2 Checking the Nominal Voltage

4.3 Setting the Motor Protection Switch

The nominal voltage given on the rating plate of the sewing drive and
the mains voltage must agree!
For conversion to a different mains voltage the appropriate voltage kit
must be mounted.
The voltage kit consists of:
V-belt pulley, V-belt, protection switch insert
Nominal voltage:
3 ~ 380 - 415 V + N, 50 Hz
3 ~ 220 - 240 V, 50 Hz
3 ~ 220 - 240 V, 60 Hz
"Delta"
By conversion to a different mains voltage the wiring must be changed.
The wiring is given in the components connection diagram.
The bridges in the motor terminal box are to be switched in "Star" or
"Delta" according to the mains voltage.
Dependent on the voltage kit one of the following motor protection
switch inserts is to be mounted:
220 - 240 V: 2.5 - 4 A
380 - 415 V: 4 - 6.3 A
The motor protection switch insert must be set appropriate to the
mains voltage:
220 - 230 V:
4.2 A
380 - 415 V:
2.5 A
Order no.:
0745 004464
0745 004504
0745 004544
"Star"
11