Plug-in terminal blocks
TB2
Refer to Note 6
Notes:
1) All connections are power-limited and supervised.
2) A maximum of 32 LED-10 Series Annunciators may be connected to this circuit.
3) 6,000 feet (1,800 m) maximum distance @ 18 AWG (0.75 mm
annunciators.
4) Use overall foil/braided-shield twisted pair cable suitable for EIA-485 applications (refer to Section
Four for shield termination information).
5) The EIA-485 circuit is rated at 5.5 VDC maximum and 60 mA maximum.
6) The LED-10 Series Annunciators must have the supplied R120 (120 ohm) resistor installed
across the EIA-485 terminals on the last or only device connected to the EIA-485 bus as shown.
The resistor is required for impedance matching.