Fire-Lite LED-10 series Manual page 15

Led-10 series remote fire annunciators for use with the fire-lite ms-5210ud fire alarm control/communicator
Table of Contents

Advertisement

Surface Mount Backbox
Remove the plug-in terminal blocks from the LED-10 Series circuit board. Connect the
EIA-485 and power wiring into the terminal block positions illustrated in Figures 3-1 and
3-3. Plug the terminal blocks back into the TB1 and TB2 connectors on the back of the
annunciator circuit board.
Set DIP switches SW1 and SW2 for the desired options (refer to switch settings in
Figures 1-3, 1-4 and Table 1-1).
Mount the LED-10 Series to a three-gang electrical box using the four mounting holes
on the annunciator flange and the four screws provided for this purpose. Replace the
trim ring and secure with the two screws which were previously removed.
overtighten.
Three-gang electrical box
(Fire•Lite P/N SBB-3 or equivalent
with 2.75" minimum depth).
flange
LED-10 Series
Figure 2-4: Surface Mounting
Mounting Holes (4)
Document 50400
Rev B
10/27/97
Do not
LED-10 Series flange
EIA-485 and power wiring
P/N 50400:B
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Led-10lLed-10ls2

Table of Contents