Baldor GLC30 Installation & Operating Manual page 65

Glc generator (gaseous liquid cooled)
Hide thumbs Also See for GLC30:
Table of Contents

Advertisement

Parameter
System Voltage (Line To Line)
System Frequency
System Phases
y
Temperature Scale
Pressure Scale
Start Delay
Crank Time
Rest Time
Starter Re–engage Delay
Number Of Cranks
Bypass Delay
Cool down Delay
Nominal RPM
Flywheel Teeth (Engine Speed
Sensing, Magnetic Pick Up
Crank Disconnect
Overspeed
Overspeed Transient
Run Output
Loss Of Speed Signal
Common Fail For
Horn For Not In Auto
Prog Output #1
Prog Output #2
Prog Output #3
Prog Output #4
Prog Output #5
Prog Output #6
Warm–up Delay
Neutral Delay
Return Delay
Reset Run Hours
Yes/No
MN2408
Figure 4-5 Main Menu Loop Parameters
Setting
XXXXX VAC
50Hz/60Hz
1 Phase/3 Phase
Neutral Connected
Voltage Sensing
Ratio XXX
Current Sensing
Ratio XXX
Deg C/Deg F
PSI/KPA
XXX Seconds
XX Seconds
XX Seconds
XX Seconds
XX Cranks
XX Seconds
XX Seconds
XXXX RPM
XXX Teeth
XX %
XX %
X.X Seconds
Fail Safe Yes/No
Shutdown Alarm/Shutdown
Not In Auto Yes/No
Range
120–15000VAC
Toggle Between 50/60 Hz
Toggle Between 1 & 3 Phase
Toggle Between Yes/No
Voltage Sensing Pt Ratio
Enter Number 1–208 (1=Direct)
Current Sensing Ct Ratio
Enter Number 1–999 (1=Direct)
Toggle Between Deg C/Deg F
Toggle Between Psi/Kpa
0–999 Seconds
0–99 Seconds
0–99 Seconds
0–99 Seconds 0=Disabled
0–99 Times 0=Continuous
0–99 Seconds
0–9999 Seconds
0–4000RPM
0–999 Teeth
0–100%
100–150%
0.0–9.9 Seconds
Toggle Between Yes/No
Toggle Between Alarm/Shutdown
Toggle Between Yes/No
Toggle Between Yes/No
Common Fail (Factory setting)
Common Fail (Factory setting)
Common Fail (Factory setting)
Common Fail (Factory setting)
Common Fail (Factory setting)
Common Fail (Factory setting)
0–99 Seconds
0–99 Seconds
0–999 Seconds
Access by Master Password Only
Toggle Between Yes/No
Operation 4-19