Baldor GLC30 Installation & Operating Manual page 34

Glc generator (gaseous liquid cooled)
Hide thumbs Also See for GLC30:
Table of Contents

Advertisement

WARNING: An open bottom stationary engine generator set must be installed over noncombustible
materials and shall be located such that it prevents combustible materials from accumulating
under the generator set.
Several other factors should be carefully evaluated when selecting a location for installation:
Generator
A
GLC30
78.0
GLC35
78.0
GLC45
78.0
GLC50
118.0
GLC60
118.0
GLC80
118.0
GLC100
118.0
GLC125
118.0
3-2 Receiving & Installation
1.
For effective cooling and maintenance, the system should be mounted on a flat,
smooth, noncombustible level surface. A concrete pad is ideal and provides a secure
installation.
2.
Installation should prevent water levels from reaching the generator. Drainage must be
adequate to keep concrete pad free from standing water.
3.
Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. If
these items pose a problem, consider building a small fence or other break to protect
the unit from accumulation of debris.
4.
Installation should place the generator as close as possible to the fuel supply and
transfer switch.
5.
At least forty–eight (48) inches clearance must be provided on all sides for air flow.
6.
Access must be provided to allow the enclosure covers to be opened or removed for
service and maintenance.
7.
Maximum Ambient temperature is 122°F (50°C).
Figure 3-2 Generator Mounting
Table 3-3 Mounting Dimensions
A1
A2
6.0
33.0
6.0
33.0
6.0
33.0
6.0
38.0
6.0
38.0
6.0
38.0
6.0
38.0
6.0
38.0
B
B1
44.0
42.5
44.0
42.5
44.0
42.5
44.0
42.5
44.0
42.5
44.0
42.5
44.0
42.5
44.0
42.5
B2
E1
6.25
17.0
6.25
17.0
6.25
17.0
6.25
17.0
6.25
17.0
6.25
17.0
6.25
17.0
6.25
17.0
F1
32.0
32.0
32.0
32.0
32.0
32.0
32.0
32.0
MN2408