Ferroli F24 Installation, Servicing And User Instructions Manual page 11

Gas combination boiler for central heating and hot water production, wall mounted, copper heat exchanger, fan assisted, room sealed, electronic flame ignition and control installation, service and user instructions
Table of Contents

Advertisement

Ferroli F24
CLEARANCES:
* 600mm minimum clearance for servicing
access
Top clearance only applies to 100Ø concentric
flue system
Terminal Position
Minimum dimensions of fl ue terminal positions
Dimensions
(kW input expressed in net)
A a
Directly below an opening, air brick, (0-7 kW)
opening windows, etc.
(>14-32 kW)
(>32-70 kW)
B a
Above an opening, air brick, (0-7 kW)
opening windows, etc.
(>14-32 kW)
(>32-70 kW)
C a
Horizontally to an opening, air brick, (0-7 kW)
opening windows, etc.
(>14-32 kW)
(>32-70 kW)
Below gutters, soil pipes or drain pipes
D
Below eaves
E
Below balconies or car port roof
F
From a vertical drain pipe or soil pipe
G
From an internal or external corner
H
Above ground roof or balcony level
I
From a surface facing the terminal
J
(also see 6.1.2)
From a terminal facing the terminal
K
From an opening in the car port ( e.g. door,
L
window) into the dwelling
Vertically from a terminal on the same wall
M
Horizontally from a terminal on the same wall
N
From the wall on which the terminal is mounted
O
From a vertical structure on the roof
P
Above intersection with roof
Q
NOTE N/A = Not applicable
n addition, the terminal should not be nearer than 150 mm (fanned draucht) or 300 mm (natural draught) to an opening in the building fabric formed for the purpose of accommodating
a
I
a built-in element such as a window frame, (see Figure C2). Separation distances are linked to the rated heat inputs as shown.
b
This dimension may be reduced to 75 mm for appliances of up to 5 kW heat input.
Fig. 11
J
Balanced flues room
Terminal position
Natural
draught
300 mm
(>7-14 kW)
600 mm
1500 mm
2000 mm
300 mm
(>7-14 kW)
300 mm
300 mm
600 mm
300 mm
(>7-14 kW)
400 mm
600 mm
600 mm
300 mm
300 mm
600 mm
300 mm
600 mm
300 mm
600 mm
600 mm
1200 mm
1500 mm
300 mm
5 min.
460
P
D, E
B
C
G
A
Open flues
sealed
Fanned
Natural
Fanned
draught
draught
draught
300 mm
Not allowed
300 mm
300 mm
Not allowed
300 mm
300 mm
Not allowed
300 mm
75 mm
Not allowed
75 mm
200 mm
Not allowed
200 mm
200 mm
Not allowed
200 mm
150 mm b
Not allowed
150 mm
300 mm
Not allowed
200 mm
300 mm
Not allowed
300 mm
600 mm
N/A
600 mm
1200 mm
N/A
1200 mm
1200 mm
N/A
1200 mm
1500 mm
N/A
1500 mm
300 mm
N/A
300 mm
N/A
N/A
N/A
50 mm
N/A
N/A
See Table 2
and Fig. 6b
N/A
N/A
See Table 2
150 mm
and Fig. 4
5 min.
N
N
Fig. 12
N/A
272
50 mm
600* min.
11