Table 4 MIRO 32/0 DIP Switch and Jumper Settings
Module
MIRO 2/16
If a MIRO 32/0 is not required in a system, start addressing the 2/16 modules at
Note:
DIP switch 3. If a MIRO 32/0 is configured with an address other than 1 or 2, the
NetAXS™ panel will not communicate with it. Likewise, if a MIRO 2/16 is
configured with an address other than 3 through 6, the NetAXS™ panel will not
communicate with it.
The NetAXS™ board is not intended to provide either module power or module
output load power for downstream I/O. A separate 24VDC supply should be used to
provide power to all downstream modules and output loads. For some installations,
the noise immunity improves if the NetAXS™ common is connected to the 24 VDC
Return wiring for the downstream modules. This connection is not needed for most
installations.
24
www.honeywell.com
Setting
Jumper settings
DIP switches
Jumper settings
(continued)
Value
JP1 - CLOSED (if the module is
the last module on the
downstream bus), OPEN (if the
module is not the last module on
the downstream bus)
JP2 - any setting
JP3 - any setting
JP4 - NORMAL
(Positions 1 and 2)
Address (switches 1-6) - 3
through 6
Baud rate (switches 7 and 8) - 7
= OFF, 8 = ON
OP Mode (switches 9 and 10) - 9
= OFF, 10 = OFF
JP1 - CLOSED, positions 2 and
3 (if the module is the last
module on the downstream bus);
OPEN, positions 1 and 2 (if the
module is not the last module on
the downstream bus)
JP2 - NORMAL, positions 1
and 2