Environmental Specifications
This section provides the temperature/humidity requirements, noise emission, and air flow specifications for
the HP Server.
Temperature and Humidity Specifications
Ambient intake air temperature is often different from ambient room temperature; you should measure the
operating temperature and humidity directly in front of the cabinet cooling air intakes rather than just
checking ambient room conditions.
Table 1-6
Computer Environment
Operating
Parameter
Temperature
o
5
C to 35
to 5,000 feet)
Relative
15% to 80% at
humidity
o
35
noncondensing
NOTE
Operating ranges refer to the ambient air temperature and humidity measured at the cabinet
cooling air intake vents.
Acoustic Noise Specification
The acoustic noise specification for the HP Server is as follows:
•
< 60 db LpA (sound pressure level at bystander position)
The above level is appropriate for dedicated computer room environments, not office environments.
Care should be taken to understand the acoustic noise specifications relative to operator positions within the
computer room or when adding HP Servers to computer rooms with existing noise sources.
Air Flow
The recommended cabinet air intake temperature is between 68
Chapter 1
Recommended
Operating
Range
Range
o
o
C (up
20
C to 25
to 5,000 feet)
40% to 60% at
o
C
35
C
noncondensing
Maximum Rate of
Change
o
o
C (up
10
C/hr with tape
o
20
C/hr without tape
30% per hour
noncondensing
o
F and 77
System Specifications
Environmental Specifications
Non-Operating
Range
o
-40
C to +70
o
o
o
F (20
C and 25
C) at 960 CFM.
o
C
9