Power Consumption; Electrical Load Requirements (Circuit Breaker Sizing); Power Quality - HP Integrity rx5670 Site Preparation Manual

Site preparation guide - hp integrity rx5670 (a6837b/a6838b)
Hide thumbs Also See for Integrity rx5670:
Table of Contents

Advertisement

General Site Preparation Guidelines
Electrical Factors
Smoke detectors
Fire and temperature alarms
Fire extinguishing system
Additional safety devices are:
Circuit breakers
An emergency power cutoff switch
Devices specific to the geographic location i.e., earthquake protection
Lighting Requirements for Equipment Servicing
Adequate lighting and utility outlets in a computer room reduce the possibility of accidents during equipment
servicing. Safer servicing is also more efficient and, therefore, less costly.
For example, adequate lighting reduces the chances of connector damage when cables are installed or
removed.
The minimum recommended illumination level is 70 foot-candles (756 lumens per square meter) when the
light level is measured at 30 inches (76.2 cm) above the floor.
Working Space for Server Access
The recommended working space for performing maintenance on the server is three feet. The work space
shall permit at least a 90 degree opening of equipment doors or hinged panels. When planning for the working
space area, consider whether access to the server will be at the front, the side, or the rear of the server.

Power Consumption

When determining power requirements, you must consider any peripheral equipment that will be installed
during initial installation or as a later update. Refer to the applicable documentation for such devices to
determine the power required to support these devices.

Electrical Load Requirements (Circuit Breaker Sizing)

NOTE
Local Authority Has Jurisdiction [LAHJ] and should make the final decision regarding
adherence to country-specific electrical codes and guidelines.
It is good practice to derate power distribution systems for one or more of the following reasons:
To avoid nuisance tripping from load shifts or power transients, circuit protection devices should never be
run above 80% of their root-mean-square (RMS) current ratings.
Safety agencies derate most power connectors to 80% of their RMS current ratings.

Power Quality

The hp Integrity rx5670 is designed to operate over a wide range of voltages and frequencies. The server is
tested and shown to comply with EMC Specification EN50082. However, damage can occur if these ranges are
exceeded. Severe electrical disturbances can exceed the design specifications of the equipment.