Page 1
OWNER'S MANUAL F A C T O R Y S E T MODELS: C2 Wiring See pages 16 thru 18 ✦ ✦ ✦ ✦ for other wiring configurations LOGIC CONTROL (VER. 2.0) INDUSTRIAL DUTY DOOR OPERATOR PATENT PENDING The Maintenance Alert System allows the installer to set an internal Maintenance Cycle Counter.
Secondary: #48 chain/sprocket Output: #50 chain Model J: Floor level disconnect for emergency manual door operation. OUTPUT SHAFT SPEED: ..36 R.P.M. Model H: Floor level chain hoist with electrical interlock DOOR SPEED: ......6 - 7” per sec. for emergency manual door operation. depending on door Model HJ: Includes both floor level disconnect BRAKE: (Optional) ....Solenoid actuated disc...
OPERATOR PREPARATION Both J and H series operators have dual output shafts and may be mounted on either the right (standard) or left side of door, and in either a vertical (standard) or horizontal mounting position. If you need to move the drive sprocket, loosen BOTH set screws, remove the sprocket and key, and place on the opposite side of the drive shaft.
OPERATOR MOUNTING Before your operator is installed, be sure the door has been properly aligned and is working smoothly. The operator may be wall mounted or mounted on a bracket or shelf. If necessary, refer to the operator preparations on page 3. Refer to the illustration and instructions below that suits your application. 1a.
7. Install Hand Chain (Models H and HJ only) 8. Mount Chain Keeper / Keyhole Bracket Place hand chain around hand chain wheel. Be Using suitable hardware mount the chain keeper sure to pass it through both openings in the chain approximately 4 feet above the floor, near the free guide.
LIMIT SWITCH ADJUSTMENT MAKE SURE THE LIMIT NUTS ARE POSITIONED BETWEEN THE LIMIT SWITCH ACTUATORS BEFORE PROCEEDING WITH ADJUSTMENTS. 1. To adjust limit nuts depress retaining plate to allow WARNING nut to spin freely. After adjustment, release plate and ensure it seats fully in slots of both nuts. 2.
POWER WIRING CONNECTIONS Remove the cover from the electrical enclosure. Inside this enclosure you will find the wiring diagram(s) for your unit. Refer to the diagram (glued on the inside of the cover) for all connections described below. If this diagram is missing, call the number on the back of this manual. DO NOT INSTALL ANY WIRING OR ATTEMPT TO RUN THIS OPERATOR WITHOUT CONSULTING THE WIRING DIAGRAM.
BRAKE ADJUSTMENT A solenoid brake is optional on all models, and is optional on 1/3 and 1/2 horsepower models. The brake is adjusted at the factory and should not need additional adjustment for the the life of the friction pad. Replace friction pads when necessary.
Page 10
LOGIC CONTROL (VER. 2.0) 1 PHASE WIRING DIAGRAM 1837-1 MOTOR 115V 1 PHASE MOTOR 230V 1 PHASE TO REVERSE MOTOR DIRECTION 115 VOLT: REVERSE BLUE AND YELLOW WIRES. 208-230 VOLT: REVERSE PURPLE AND GRAY WIRES.
Page 11
LOGIC CONTROL (VER. 2.0) 3 PHASE WIRING DIAGRAM 1837-3 MOTOR 230V 3 PHASE MOTOR 380/460V 3 PHASE TO REVERSE MOTOR DIRECTION REVERSE PURPLE AND GRAY WIRES...
Page 12
STANDARD POWER & CONTROL CONNECTION DIAGRAM Logic Control Board (VER. 2.0) - 115V, 208, 230V, 1Ph...
Page 13
STANDARD POWER & CONTROL CONNECTION DIAGRAM Logic Control Board (VER. 2.0) - 208, 230V, 380V, 460V, 3Ph...
PROGRAM SETTINGS Logic Control Pushbuttons Open, Close, Stop Open, Close and Stop buttons are mounted directly on the Logic Control board. This will provide easy programming ability and door control at the electrical box. Programmable Maximum Run Timer: Any time a “closing” or “opening” door takes 10 seconds longer than its programmed normal cycle time, the door will stop.
Page 16
WIRING TYPES All modes contain: Wiring for sensing devices to reverse. Wiring for failsafe reversing devices. Connection for electrical detection of clutch slippage. External interlocks and auxiliary devices. Open button override while door is traveling down. NOTE: Open, Close, and Stop buttons are located on the Logic Control board. This will provide programming ability and door control at the electrical box.
See Failsafe Safety Device Options below. Failsafe Safety Device Options To use the operator in any of the Failsafe wiring modes, or Timer to Close wiring modes, a LiftMaster failsafe safety device must be installed. FAIL SAFE Timer to Close with Failsafe Safety Device NOTE: The board will check attached Failsafe devices after setting the Timer to Close and activate them for the timer.
Page 18
DIAGNOSTIC MODE & RPM LEARN Diagnostic Mode Set dip switch to diagnostic mode. The following diagnostic codes are applicable: G Obstruction sensed = 2 flashes then pause DIAGNOSTIC G Board Okay = Rapid Flash Factory Memory Preset Activate this mode to initialize the board’s memory to the standard factory preset values.
MAINTENANCE SCHEDULE I I For use with Maintenance Alert System. I I Check at the intervals listed in the following chart. EVERY 3 MONTHS EVERY 6 MONTHS EVERY 12 MONTHS 5,000 CYCLES 10,000 CYCLES 20,000 CYCLES ITEM PROCEDURE Check for excessive slack. Drive Chain Check &...
Page 23
REPLACEMENT PARTS KITS – MODEL LOGIC CONTROL (VER. 2.0) Refer to the parts lists below for replacement kits available for your operator. If optional modifications and/or accessories are included with your operator, certain components may be added or remove from these lists. Individual components of each kit may not be available.
Page 25
REPLACEMENT PARTS KITS - MODEL LOGIC CONTROL (VER. 2.0) Refer to the parts lists below for replacement kits available for your operator. If optional modifications and/or accessories are included with your operator, certain components may be added or remove from these lists. Individual components of each kit may not be available.
Page 27
REPLACEMENT PARTS KITS – MODEL LOGIC CONTROL (VER. 2.0) Refer to the parts lists below for replacement kits available for your operator. If optional modifications and/or accessories are included with your operator, certain components may be added or remove from these lists. Individual components of each kit may not be available.
CONTROL CONNECTION DIAGRAM 41B6 IMPORTANT NOTES: The 3-Button Control Station provided must be connected for operation. LISTED DOOR OPERATOR If a STOP button is not used, a jumper must be placed between terminals 4 and 5. 3 BUTTON STATION OR 3 POSITION KEYSWITCH WITH SPRING RETURN TO CENTER AND STOP BUTTON STANDARD 2 OR MORE KEY LOCKOUT...
Page 29
SOLID STATE II THREE PHASE WIRING DIAGRAM 1842-3 WITH CONTACTOR DIP SWITCH SETTINGS OPTIONAL CONTROLS 3 BUTTON STATION MAINTENANCE MAINTENANCE ALER ALERT LED T LED TIMER STOP TIMER CLOSE CYCLE COUNTER OPERATING MODES FAIL SAFE FAIL SAFE SEE NOTE 2 FAIL SAFE FAIL...
Page 30
Logic Control (Ver. 2) 1897 575 VOLT THREE PHASE W/ CONTACTOR DIP SWITCH SETTINGS PROGRAM SETTINGS TIMER STOP TIMER CLOSE MAINTENANCE ALERT SYSTEM WIRING TYPES FSTS FAILSAFE WIRING TYPES FAIL Note: SAFE 1) TO REVERSE MOTOR DIRECTION: INTERCHANGE PURPLE AND GRAY WIRES LIMIT SWITCH ADJUSTMENT AT CONTACTOR.
Page 31
ADDENDUM 575 Volt Logic 2 Operator MODELS: T and SD NOTE: Refer to addendum for Wiring Diagram and Electrical Box Replacement Parts, for all other installation instructions refer to owners manual shipped with operator. 575 VOLT THREE PHASE W/ CONTACTOR...