LG ARUN096BT2 Installation Manual page 57

Arun series multi v system plus ii
Hide thumbs Also See for ARUN096BT2:
Table of Contents

Advertisement

3 Outdoor Units - 3Ø, 208/230V
When the power source is connected
In series between the units.
Power supply switch
(Switch fuse : ELCB)
3 Phase 3 Wires
Power supply
60Hz 208/230V
(Main Switch)
Power supply switch
(Switch)
Power supply
1 Phase 60Hz
208/230V
When the power source is supplied to
Each outdoor unit individually.
Power supply switch
(Switch fuse : ELCB)
3 Phase 3 Wires
Power supply
60Hz 208/230V
(Main Switch)
Power supply switch
(Switch)
Power supply
1 Phase 60Hz
208/230V
WARNING
• Indoor Unit ground Lines are required for preventing electrical shock accident during current
leakage,
Communication disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately
from the power supply.
• Install the main switch that can interrupt all the power sources in an integrated manner because
this system consists of the equipment utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase, momentary blackout or the power
goes on and off while the product is operating, attach a reversed phase protection circuit locally.
Running the product in reversed phase may break the compressor and other parts.
Between Indoor and Master Outdoor unit
SODU
IDU
INTERNET
DRY1 DRY2 GND
B
A
B
A
The GND terminal is a '–' terminal for the
central controller, not Ground Line
Master
Slave1
Slave2
SODU
12V
Master
B
A
Outdoor unit
SODU
B
A
SODU
B
A
Electrical Wiring
3 Phase 3 Wires Power line(R, S, T)
Communication line (3 line): Wired remote control
Single Phase of power supply line(L(1),L(2))
Communication line (2 shield line):
Between Outdoor Unit and Outdoor Unit
Communication line (2 shield line):
Between Indoor Unit and Outdoor Unit
Pull Box(Installer Option)
Pull Box(Installer Option)
IDU
INTERNET
DRY1 DRY2 GND
12V
B
A
IDU
INTERNET
DRY1 DRY2 GND
12V
B
A
IDU
INTERNET
DRY1 DRY2 GND
12V
B
A
Installation Manual 57
Master
Outdoor unit
Slave1
Outdoor unit
Slave2
Outdoor unit