Refrigerant pipe diameter from branch to branch (B,C)
Downward Indoor Unit total capacity
[kW(Btu/h)]
<22.4(76,400)
< 33(112,600)
< 47(160,400)
< 71(242,300)
< 104(354,900)
104(354,900)
Total pipe length = A+B+C+a+b+c+d+e 1,000m(3,281 ft)
Longest pipe length
L
A+B+b
Longest pipe length after 1st branch
l
B+b
40m(131ft)
Difference in height(Outdoor Unit
H
H
100m(328ft)
Difference in height (Indoor Unit
h
h
15m(49ft)
Difference in height (Outdoor Unit
h1
h1
5m(16ft)
• * : Assume equivalent pipe length of Y branch to be 0.5m(1.6ft), that of header to be 1m(3.3ft), calculation purpose
• Indoor Unit should be installed at lower position than the header.
WARNING
It is recommended that difference of piping length for pipes connected to the Indoor Unit is
minimized. Performance difference between Indoor Units may occur.
Upward Outdoor Unit
total capacity [HP]
8
10
12~16
18~22
24
26~34
36~48
Liquid pipe
[mm(inch)]
Ø9.52(3/8)
Ø9.52(3/8)
Ø12.7(1/2)
Ø15.88(5/8)
Ø19.05(3/4)
Ø19.05(3/4)
* Equivalent pipe length
150m(492ft)
A+B+b
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
Ø9.52(3/8)
Ø19.05(3/4)
Ø9.52(3/8)
Ø22.2(7/8)
Ø12.7(1/2)
Ø28.58(1-1/8)
Ø15.88(5/8)
Ø28.58(1-1/8)
Ø15.88(5/8)
Ø34.9(1-3/8)
Ø19.05(3/4)
Ø34.9(1-3/8)
Ø19.05(3/4)
Ø41.3(1-5/8)
Refrigerant piping installation
Gas pipe
[mm(inch)]
Ø19.05(3/4)
Ø22.2(7/8)
Ø28.58(1-1/8)
Ø28.58(1-1/8 )
Ø34.9(1-3/8)
Ø41.3(1-5/8)
175m(574ft)
Indoor Unit)
Indoor Unit)
Outdoor Unit)
Upward Outdoor Unit
total capacity [HP]
20, 22, 24
26, 28, 30, 32
Upward Outdoor Unit
total capacity [HP]
8
10
12, 14, 16
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
Ø15.88(5/8) Ø28.58)(1-1/8)
Ø19.05(3/4)
Ø34.9(1-3/8)
Liquid pipe
Gas pipe
[mm(inch)]
[mm(inch)]
Ø9.52(3/8)
Ø19.05(3/4)
Ø9.52(3/8)
Ø22.2(7/8)
Ø12.7(1/2)
Ø28.58(1-1/8)
Installation Manual 31