LG ARUN096BT2 Installation Manual page 35

Arun series multi v system plus ii
Hide thumbs Also See for ARUN096BT2:
Table of Contents

Advertisement

3. In case pipe length between outdoors is 2m or more.
When the piping length between Branch of Outdoor units or between Branch and outdoor units.
Is 2 m(6.6ft) or more, prepare a oil trap 200 mm(0.7ft) or more as shown below) on the gas pipe line location.
Less than 2 m(6.6ft) from branch.
4. Example of wrong connection
Oil is accumulating in
outdoor units when
system stops
Oil is accumulating in lower level
outdoor units when system stops
Oil Trap
200mm(0.7ft)
or more
Less than 2m(6.6ft)
2m(6.6ft) or more
Oil Trap
Less than 2m(6.6ft)
2m(6.6ft) or more
Refrigerant piping installation
Installation Manual 35