LG ARUN096BT2 Installation Manual page 23

Arun series multi v system plus ii
Hide thumbs Also See for ARUN096BT2:
Table of Contents

Advertisement

Caution
1. Use the following materials for refrigerant piping.
• Material: Seamless phosphorous deoxidized copper pipe
• Wall thickness : Comply with the relevant local and national regulations for the designed pressure 3.8MPa. We
recommend the following table as the minimum wall thickness.
Outer diameter
6.35
[mm(inch)]
(1/4)
Minimum thickness
0.8
[mm(inch)]
(0.03)
2. Commercially available piping often contains dust and other materials. Always blow it clean with a dry inert gas.
3. Use care to prevent dust, water or other contaminants from entering the piping during installation.
4. Reduce the number of bending portions as much as possible, and make bending radius as big as possible.
5. Always use the branch piping set shown below, which are sold separately.
ARBLN01621
ARBLN07121
6. If the diameters of the branch piping of the designated refrigerant piping differs, use a pipe cutter to cut the
connecting section and then use an adapter for connecting different diameters to connect the piping.
7. Always observe the restrictions on the refrigerant piping (such as rated length, difference in height, and pip-
ing diameter).
Failure to do so can result in equipment failure or a decline in heating/cooling performance.
8. A second branch cannot be made after a header. (These are shown by
A
To Outdoor Unit
A
B
Sealed Piping
9. The Multi V will stop due to an abnormality like excessive or insufficient refrigerant. At such a time, always
properly charge the unit. When servicing, always check the notes concerning both the piping length and the
amount of additional refrigerant.
10. Never use refrigerant to perform an air purge. Always evacuate using a vacuum pump.
11. Always insulate the piping properly. Insufficient insulation will result in a decline in heating/cooling perfor-
mance, drip of condensate and other such problems.
12. When connecting the refrigerant piping, make sure the service valves of the Outdoor Unit is completely
closed (the factory setting) and do not operate it until the refrigerant piping for the Outdoor and Indoor Units
has been connected, a refrigerant leakage test has been performed and the evacuation process has been
completed.
13. Always use a non-oxidizing brazing material for brazing the parts and do not use flux. If not, oxidized film
can cause clogging or damage to the compressor unit and flux can harm the copper piping or refrigerant oil.
9.52
12.7
15.88
19.05
(3/8)
(1/2)
(5/8)
(3/4)
0.8
0.8
0.99
0.99
(0.03)
(0.03)
(3.25)
(0.04)
Y branch
ARBLN03321
ARBLN14521
Refrigerant piping installation
22.2
25.4
28.58
31.8
(7/8)
(1)
(1-1/8)
(1-1/4)
0.99
0.99
0.99
1.1
(0.04)
(0.04)
(0.04)
(0.04)
Header
4 branch
7 branch
ARBL054
ARBL057
ARBL104
ARBL107
.)
A
Installation Manual 23
34.9
38.1
41.3
(1-3/8)
(1-1/2)
(1-15/16)
1.21
1.35
1.43
(0.05)
(0.05)
(0.06)
10 branch
ARBL1010
ARBL2010
B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents