Generator AC Connection System

A single-phase, three-wire AC connection system is used in
33
Neutral
the home generator. The stator assembly consists of a pair
22
of stationary windings with two leads brought out of each
winding. The junction of leads 22 and 33 forms the neutral
lead, as shown schematically and as a wiring diagram. A
complete schematic and wiring diagram can be found later
in this manual.
120V
NOTICE Neutral is not bonded to ground at generator.
A
The conduit
between the corner electrical inlet and the
control panel is a UL requirement. If removed, it must be
120V
replaced with similar conduit.
Circuit
Breaker
11
240V
44
A
0
22 33
44
11
Circuit
Breaker
Ground
Neutral
Line 2
Line 1
To Transfer Switch

Grounding the Generator

Ground the home generator per applicable codes, standards,
and regulations. The generator GND lug is located inside the
control panel box.