Delivery Inspection; Generator Location - GE HOME GENERATOR SYSTEMS Installation And Start-Up Manual

15,000 and 20,000 watt home generator system
Hide thumbs Also See for HOME GENERATOR SYSTEMS:
Table of Contents

Advertisement

Available languages

Available languages

Delivery inspection

After removing the carton, carefully inspect the generator for
any damage that may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor's memo of loss or
damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier for claim
procedures. Missing or damaged parts are not warranted.
shipment contents
the home generator system is supplied with:
• Pre-attached mounting pad
• Fully-serviced oil/lubricating system
• Flexible fuel hook-up hose
• Installation and start-up manual
• Operator's manual
• Engine operator's manual
• Installation checklist
• Alternator cover
• Spare access door keys
• Spare 15 Amp ATO-type fuse
• Two-pin control panel connector
• Ten-pin control panel connector
• Touch up paint

Generator Location

Before installing the generator, consult with the homeowner
and convey the following guidelines, which may affect the
desired installation location.
WarninG Exhaust heat/gases could ignite combustibles
or structures resulting in death, serious injury and/or
property damage.
DO NOT install the generator closer than 5 feet (1.5m) from any
combustibles or structures with combustible walls having a fire
resistance rating of less than 1 hour.
8
not supplied:
• Starting battery (see page 19)
• Connecting wire and conduit
• Fuel supply valves/plumbing
• Crane, lifting straps, chains or cables
• Two 48" lengths of 1" pipe (NOT conduit)
• Hole punches for 16ga steel
• Torque screwdriver, 5 to 50 inch-pound range
• Voltage/frequency meter
• Various special tools and equipment
WarninG Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
Operate this product ONLY outdoors.
Install a battery operated carbon monoxide alarm near
the bedrooms.
Keep exhaust gas from entering a confined area through
windows, doors, ventilation intakes, or other openings.