CARLO GAVAZZI POWERSOFT Instruction Manual page 14

Hide thumbs Also See for POWERSOFT:
Table of Contents

Advertisement

PowerSoft
output activation can be carried out manually or follow a setpoint
alarm. The digital output is to be set as "REM" (remote control) in the
instrument.
§
Enable gas: it enables the reading of the gas meter (only in the
instruments supplied with this function).
§
Enable water: it enables the reading of the water meter (only in
the instruments supplied with this function).
§
Enable 4 quadrants: it enables the displaying of the 4-quadrant
reactive energy meters (WM24 only).
When at least one of these parameters is modified, the modification/s is
accepted and stored after pressing the "Confirm" button.
1.3.3.2
T
The test area, located in the right side, allows the operator to test the
configuration from the communication and digital signals points of view.
"Auto test", if enabled, allows to automatically perform a communication
test every time the instrument is selected.
The communication status is shown by the "Communication" LED: it is
green in case of correct communication; red when the parameters are
wrong or the instrument is not connected; yellow if the selected type is not
correspondent to the actual instrument on the network.
If the instrument is correctly set and later is replaced by another model,
PowerSoft is not able to sense the replacement, it will try to establish again
the communication with the first instrument, and then it will show the
missing communication status (red LED) or the status of right
communication(green LED) but in this case all the acquired information is
potentially wrong. When replacing an instrument with another model, the
suggestion is to delete the old instrument and add a new one.
Concerning the digital inputs, it is possible to check the status by means of
2 LED's in the top right area: red if the status is ON and grey if the status is
OFF. The digital output can be switched using the proper buttons ("DO ->
ON" and "DO ->OFF").