Download Print this page
Bryant 581J 04A Series Service And Maintenance Instructions
Bryant 581J 04A Series Service And Maintenance Instructions

Bryant 581J 04A Series Service And Maintenance Instructions

3 to 12.5 nominal tons single package rooftop gas heat/electric cooling with puron r-410a refrigerant sizes: 04-14

Advertisement

Quick Links

581J 3 to 12.5 Nominal Tons
Single Package Rooftop Gas Heat/Electric Cooling
with Puron r (R-410A) Refrigerant
Sizes: 04-14
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS
UNIT ARRANGEMENT AND ACCESS
RETURN AIR FILTERS
. . . . . . . . . . . . . . . . . . . . . . . . .
SUPPLY FAN (BLOWER) SECTION
2 SPEED FAN WITH VARIABLE FREQUENCY
DRIVE (VFD)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ADDITIONAL VARIABLE FREQUENCY DRIVE
(VFD) INSTALLATION AND TROUBLESHOOTING. 9
MOTOR
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
COOLING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
THERMOSTATIC EXPANSION VALVE (TXV)
PURONR (R- 410A) REFRIGERANT
COOLING CHARGING CHARTS
COMPRESSOR
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CONVENIENCE OUTLETS
SMOKE DETECTORS
. . . . . . . . . . . . . . . . . . . . . . . . .
SENSOR AND CONTROLLER TESTS
PROTECTIVE DEVICES
GAS HEATING SYSTEM
RTU- OPEN CONTROL SYSTEM
SENSORY/ACCESSORY INSTALLATION
ADDITIONAL RTU- OPEN INSTALLATION AND
TROUBLESHOOTING
. . . . . . . . . . . . . . . . . . . . . . . . .
ECONOMIZER UNITS
. . . . . . . . . . . . . . . . . . . . . . . .
PRE- START- UP/START- UP
START- UP, GENERAL
. . . . . . . . . . . . . . . . . . . . . . . .
START- UP, RTU- OPEN CONTROLS
FASTENER TORQUE VALUES
APPENDIX I. MODEL NUMBER SIGNIFICANCE
APPENDIX II. PHYSICAL DATA
APPENDIX III. FAN PERFORMANCE
APPENDIX IV WIRING DIAGRAMS
APPENDIX V. MOTORMASTER SENSOR
LOCATIONS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
UNIT START-UP CHECKLIST
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . .
. . . .
. . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . .
. . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . .
. . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
components. Only trained and qualified service personnel
should
install,
1
equipment. Untrained personnel can perform the basic
2
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
3
4
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
8
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguishers available for all brazing
9
operations.
13
Follow all safety codes. Wear safety glasses and work
15
gloves. Use quenching cloth for brazing operations. Have
16
fire extinguisher available. Read these instructions
18
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and National
22
Electrical Code (NEC) for special requirements.
25
Recognize safety information. This is the safety ALERT
26
symbol
. When you see this symbol on the unit and in
30
instructions or manuals, be aware of the potential for
33
physical injury hazards.
34
Understand the signal words DANGER, WARNING, and
49
CAUTION. These words are used with the safety- ALERT
49
symbol. DANGER indicates a hazardous situation which,
if not avoided, will result in death or severe personal
injury. WARNING indicates a hazardous situation which,
50
if not avoided, could result in death or personal injury.
52
CAUTION indicates a hazardous situation which, if not
60
avoided, could result in minor to moderate injury or
61
product and property damage. NOTICE is used to address
64
practices not related to physical injury. NOTE is used to
highlight suggestions which will result in enhanced
64
installation, reliability, or operation.
.
65
!
66
73
ELECTRICAL OPERATION HAZARD
92
Failure to follow this warning could result in personal
injury or death.
136
Before performing service or maintenance operations
139
on unit, LOCK- OUT/TAGOUT the main power
switch to unit. Electrical shock and rotating equipment
could cause severe injury.
repair,
or
service
air-conditioning
WARNING

Advertisement

loading
Need help?

Need help?

Do you have a question about the 581J 04A Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Bryant 581J 04A Series

  • Page 1 581J 3 to 12.5 Nominal Tons Single Package Rooftop Gas Heat/Electric Cooling with Puron r (R-410A) Refrigerant Sizes: 04-14 Service and Maintenance Instructions TABLE OF CONTENTS components. Only trained and qualified service personnel should install, repair, service air-conditioning SAFETY CONSIDERATIONS .
  • Page 2 WARNING WARNING FIRE, EXPLOSION HAZARD ELECTRICAL OPERATION HAZARD Failure to follow this Failure to follow this warning could result in personal warning could result in injury or death. death, serious personal Units with convenience outlet circuits can use injury and/or property multiple disconnects.
  • Page 3 S Wire terminal tightness FILTER ACCESS PANEL S Refrigerant charge level S Evaporator coil cleaning S Evaporator blower motor amperage Heating S Heat exchanger flue passageways cleanliness S Gas burner condition COMPRESSOR ACCESS PANEL (04-07 only) S Gas manifold pressure OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL S Heating temperature rise...
  • Page 4 2. Slide the bottom into the side channels. To remove the screen, loosen the screws in the top retainer and slip the retainer up until the filter can be removed. 3. Push the bottom flange down until it contacts the top Re- install by placing the frame in its track, rotating the of the lower panel (or economizer top).
  • Page 5 Selecting speed tap — The five communication terminals are each programmed to provide a different motor torque output. See Table 1. Factory default tap selection is Motor GRN/YEL Power Position 1 for lowest torque/speed operation. Connections Table 1 – Motor Tap Programing L G N (percent of full- load torque) Unit Size...
  • Page 6 Table 2 – Motor Test Volts BLOWER PULLEY Unit Voltage Motor Voltage Min- Max Volts V- BELT 208/230 190- 250 210- 250 MOTOR PULLEY 420- 500 5. Using a jumper wire from unit control terminals R to MOTOR G, engage motor operation. Check for 24v output at the defrost board terminal IFO.
  • Page 7 around the fixed flange side that increases or reduces the STRAIGHTEDGE pitch diameter of this driver pulley. (See Fig. 10.) BROWNING BELT TENSION CHECKER 1/2” FAN PULLEY (1.3 cm) MOVABLE FLANGE STRAIGHT EDGE MUST BE PARALLEL MOTOR AND WITH BELT FANSHAFTS MUST BE PARALLEL...
  • Page 8 the condition of the motor pulley for signs of wear. See “Variable Frequency Drive (VFD) Installation, Setup Glazing of the belt contact surfaces and erosion on these and Troubleshooting Supplement” for wiring schematics surfaces are signs of improper belt tension and/or belt and performance charts and configuration.
  • Page 9 ADDITIONAL VARIABLE FREQUENCY plate to the unit. Discard all lock washers. DRIVE (VFD) INSTALLATION AND 9. Remove motor and motor mounting bracket from unit. TROUBLESHOOTING 10. Remove four bolts, flat washers, lock washers and single external- tooth lock washer attaching motor to Additional installation, wiring...
  • Page 10 teeth on the lock washer are in contact with the motor’s painted base. Tighten motor mounting bolts to 120  12 in- lbs. Changing Fan Wheel Speed Changing fan wheel speed by changing pulleys: The horsepower rating of the belt is primarily dictated by the pitch diameter of the smaller pulley in the drive system (typically the motor pulley in these units).
  • Page 13 COOLING Routine Cleaning of Coil Surfaces Periodic cleaning with TotalineR environmentally sound WARNING coil cleaner is essential to extend the life of coils. This cleaner is available from Replacement Components Division as part number P902- 0301 for a one gallon UNIT OPERATION AND SAFETY HAZARD container, and part number P902- 0305 for a 5 gallon Failure to follow this warning could cause personal...
  • Page 14 CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in accelerated corrosion of unit parts. Harsh chemicals, household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind. These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin/tube interface where dissimilar materials are in C08206...
  • Page 15 3. Slide filters out of unit. 5. Remove bulb from vapor tube inside cabinet. 4. Clean coil using a commercial coil cleaner or dish- 6. Install the new TXV using a wrench and an additional washer detergent in a pressurized spray canister. Wash wrench on connections to prevent damage to tubing both sides of coil and flush with clean water.
  • Page 16 Refrigerant Charge Amount of refrigerant charge is listed on the unit’s Using Cooling Charging Charts nameplate. Refer Bryant GTAC2- 5 Charging, Recovery, Recycling and Reclamation training manual Take the outdoor ambient temperature and read the liquid and the following procedures.
  • Page 17 CORE SEAT (Part No. EC39EZ067) 1/2-20 UNF RH 0.596 WASHER DEPRESSOR PER ARI 720 O-RING +.01/-.035 1/2” HEX FROM FACE OF BODY 5/8” HEX 7/16-20 UNF RH This surface provides a metal to metal seal when torqued into the seat. Appropriate handing is required to not scratch or dent the surface.
  • Page 18 COOLING CHARGING CHARTS C14053 Fig. 21 - Cooling Charging Charts - 3 Ton C14054 Fig. 22 - Cooling Charging Chart - 4 Ton...
  • Page 19 COOLING CHARGING CHARTS (cont.) C14055 Fig. 23 - Cooling Charging Chart - 5 Ton CHARGING CHART - R410A REFRIGERANT COOLING MODE-ALL OUTDOOR FANS MUST BE RUNNING Add Charge if Above the Curve Remove Charge if Below the Curve Compressor Discharge Pressure, [psig] 48TM502680 rev.
  • Page 20 COOLING CHARGING CHARTS (cont.) CHARGING CHART - R410A REFRIGERANT COOLING MODE-ALL OUTDOOR FANS MUST BE RUNNING Add Charge if Above the Curve Remove Charge if Below the Curve Compressor Discharge Pressure, [psig] 48TM502681 rev. - C14059 Fig. 25 - Cooling Charging Chart - 7.5 Ton CHARGING CHART - R410A REFRIGERANT COOLING MODE-ALL OUTDOOR FANS MUST BE RUNNING Add Charge if Above the Curve...
  • Page 21 COOLING CHARGING CHARTS (cont.) C14057 Fig. 27 - Cooling Charging Chart - 10 Ton 12.5 TON HC CKT B CHARGING CHART 12.5 TON HC CKT A CHARGING CHART (COOLING MODE ONLY) (COOLING MODE ONLY) (R410A REFRIGERANT) (R410A REFRIGERANT) ADD CHARGE IF ABOVE THE CURVE ADD CHARGE IF ABOVE THE CURVE REMOVE CHARGE IF BELOW THE CURVE REMOVE CHARGE IF BELOW THE CURVE...
  • Page 22 COMPRESSOR CAUTION Lubrication INSTALLATION SITE DAMAGE The compressor is charged with the correct amount of oil Failure to follow this caution can result in damage to at the factory. equipment location site. CAUTION Puron (R- 410A) refrigerant contains polyolester (POE) oil that can damage the roof membrane. Caution should be taken to prevent POE oil from UNIT DAMAGE HAZARD spilling onto the roof surface.
  • Page 23 Filter Drier Replace whenever refrigerant system is exposed to atmosphere. Only use factory specified liquid- line filter Conduit driers with working pressures no less than 650 psig. Do not install a suction- line filter drier in liquid line. A liquid- line filter drier designed for use with Puron 0.14 in + 0.0 / -0.03 refrigerant is required on every unit.
  • Page 24 Table 6 – Heating and Cooling Troubleshooting PROBLEM CAUSE REMEDY Compressor and Power failure. Call power company. Outdoor Fan Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Determine root cause. Will Not Start. Defective thermostat, contactor, transformer, Replace component.
  • Page 25 CONVENIENCE OUTLETS 2. Loosen the two screws at the GFCI duplex outlet, until approximately -in (13 mm) under screw heads are exposed. WARNING 3. Press the gasket over the screw heads. Slip the backing plate over the screw heads at the keyhole ELECTRICAL OPERATION HAZARD slots and align with the gasket;...
  • Page 26 SMOKE DETECTORS Smoke detectors are available as factory- installed options on 581J models. Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air. Return Air smoke detectors are arranged for vertical return configurations only.
  • Page 27 Smoke Detector Sensor The Smoke Detector Sensor (see Fig. 34) includes a plastic housing, a printed circuit board, a clear plastic cover, a sampling tube inlet and an exhaust tube. The EXHAUST TUBE sampling tube (when used) and exhaust tube are attached DUCT SMOKE SENSOR during installation.
  • Page 28 Return Smoke Detector Sensor without Completing Installation of Return Air Smoke Economizer: The sampling tube is located across the Detector: return air opening on the unit basepan. See Fig. 36. The holes in the sampling tube face downward, into the return FLEXIBLE EXHAUST TUBES air stream.
  • Page 29 FIOP Smoke Detector Wiring and Response Highlight D: On smoke alarm condition, the smoke detector NO Alarm contact will close, supplying 24- v All units: FIOP smoke detector is configured to power to GRA conductor. automatically shut down all unit operations when a smoke Highlight E: GRA lead at Smoke Alarm input on LCTB condition is detected.
  • Page 30 SENSOR AND CONTROLLER 3. Reset the sensor by pressing the test/reset switch for two seconds. TESTS 4. Verify that the controller’s Alarm LED turns off. Sensor Alarm Test Dirty Controller Test The sensor alarm test checks a sensor’s ability to signal an The dirty controller test checks the controller’s ability to alarm state.
  • Page 31 Dirty Sensor Test Procedure 3. Reset the sensor by turning the key switch to the RESET/TEST position for two seconds. 1. Hold the test magnet where indicated on the side of 4. Verify that the test/reset station’s Alarm LED turns the sensor housing for two seconds.
  • Page 32 Alarm State 2. Verify that the test/reset station’s Trouble LED flashes. The smoke detector enters the alarm state when the Detector Cleaning amount of smoke particulate in the sensor’s sensing chamber exceeds the alarm threshold value. (See Table 8.) Cleaning the Smoke Detector Upon entering the alarm state: Clean the duct smoke sensor when the Dirty LED is S The sensor’s Alarm LED and the controller’s Alarm...
  • Page 33 the duct smoke detector does not differentiate which 2. Configure the sensor dirty test to activate the control- sensor signals an alarm or trouble condition. Check each ler’s supervision relay. See “Changing sensor dirty sensor for Alarm or Trouble status (indicated by LED). test operation.”...
  • Page 34 Table 8 – Detector Indicators CONTROL OR INDICATOR DESCRIPTION Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in Magnetic test/reset switch the normal state. Alarm LED Indicates the sensor is in the alarm state. Trouble LED Indicates the sensor is in the trouble state.
  • Page 35 operate with Liquid Propane (LP) fuels. These kits include LP LPS new orifice spuds, new springs for gas valves and a supply line low pressure switch. See section on Orifice J2-11 Replacement for details on orifice size selections. Low NOx models include specially- sized orifices and use of different flue flow limits and tube baffles.
  • Page 36 Regulator Heater Tube Gasket Seal Strips, Sponge Rubber Regulator Assembly Baffle Assembly (Low NOx only) Retainer Support Insulation Assembly Wind Cap Assembly (shown inverted, as shipped) Flue Baffle (Low NOx only) Inducer Fan-Motor Assembly Burner Assembly C08227 Fig. 48 - Heat Exchanger Assembly 3.
  • Page 37 7. Reinstall burner rack as described in Removal and Replacement of Gas Train section, above. Gas Valve — All three- phase models (except Low NOx) are equipped with 2- stage gas valves. Single- phase models and all Low NOx models are equipped with single- stage gas valves.
  • Page 38 LED error code can be observed through the viewport. If lockout occurs, unit may be reset by interrupting power During servicing refer to the label on the control box supply to unit for at least 5 seconds. cover or Table 13 for an explanation of LED error code descriptions.
  • Page 39 125,000/90,000 BTUH INPUT 180,000/120,000 BTUH INPUT 240,000/180,000 BTUH INPUT 250,000/200,000 BTUH INPUT C08447 Fig. 53 - Spark Adjustment (Size 08- 09) 125,000/90,000 BTUH INPUT 180,000/120,000 BTUH INPUT 240,000/180,000 BTUH INPUT 250,000/200,000 BTUH INPUT C08447 Fig. 54 - Spark Adjustment (Size 12)
  • Page 40 IGNITER AND SENSOR LOCATIONS (BRACKET HEAT COVER NOT SHOWN FOR CLARITY) 0.130 5 CELL 50TM400735 6 CELL 50TM400484 0.181 8 CELL 50TM400485 10 CELL 50TM400439 C12092 Fig. 55 - Spark Adjustment (Size 14) Table 13 – LED Error Code Description* IMPORTANT: Refer to Troubleshooting Table 13 and Table 14 for additional information.
  • Page 41 REGULATOR COVER SCREW (2) REGULATOR ON/OFF COVER SCREW PLASTIC ADJUST ON/OFF SWITCH SCREW (2) SWITCH PLASTIC ADJUST SCREW REGULATOR SPRING (2) REGULATOR SPRING NPT INLET (PROPANE - WHITE NPT INLET (PROPANE - WHITE NATURAL - SILVER) NATURAL - SILVER) LOW STAGE INLET INLET GAS PRESSURE...
  • Page 42 Table 14 – IGC Connections CONNECTION TERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O PIN NUMBER INPUTS RT, C Input power from TRAN 1 control box 24 VAC — Speed sensor gas section analog input J1, 1-3 FS, T1 Flame sensor gas section switch input...
  • Page 43 Table 16 – Altitude Compensation* (04- 06) NATURAL GAS NOMINAL HEAT INPUT ELEVATION 72k BTUH 115k BTUH 150k BTUH Orifice Input Orifice Input Orifice Input Feet Meters Size (btu/hr) Size (btu/hr) Size (btu/hr) 0 - 2000 0 - 610 72,000 115,000 †30 150,000...
  • Page 44 Table 17 – Altitude Compensation* (07- 12) NATURAL GAS NOMINAL HEAT INPUT ELEVATION 72k BTUH 125k BTUH 150k BTUH 180k BTUH 224k BTUH 250k BTUH Orifice Input Orifice Input Orifice Input Orifice Input Orifice Input Orifice Input Size (btu/hr) Size (btu/hr) Size (btu/hr)
  • Page 45 Table 18 – Altitude Compensation* (14) NATURAL GAS NOMINAL HEAT INPUT ELEVATION 150k BTUH 180k BTUH 240k BTUH 315k BTUH 350k BTUH Orifice Input Orifice Input Orifice Input Orifice Input Orifice Input Size (btu/hr) Size (btu/hr) Size (btu/hr) Size (btu/hr) Size (btu/hr) 0 - 2000...
  • Page 46 Table 19 – Altitude Compensation* (04- 06) - Low NOx Units NATURAL GAS ONLY NOMINAL HEAT INPUT ELEVATION 60k BTUH 90k BTUH 120k BTUH Orifice Input Orifice Input Orifice Input Feet Meters Size (btu/hr) Size (btu/hr) Size (btu/hr) 0 - 2000 0 - 610 60,000 90,000...
  • Page 47 Table 20 – Heating Service Troubleshooting PROBLEM CAUSE REMEDY Check flame ignition and sensor electrode positioning. Misaligned spark electrodes. Adjust as needed. Check gas line for air, purge as necessary. After purging gas line of air, allow gas to dissipate for at least 5 minutes No gas at main burners.
  • Page 48 LCTB. Field The RTU Open controller is an integrated component of the connections for RTU Open sensors will be made at the Phoenix connectors on the RTU Open board. The Bryant rooftop unit. Its internal application programming factory- installed Open control includes provides optimum performance and energy efficiency.
  • Page 49 installed, while others are only field installable. RTU-OPEN controller may also require connection to a building network system or building zoning system. All field control wiring that connects to the RTU-OPEN must be routed through the raceway built into the corner post of the unit or secured to the unit control box with electrical conduit.
  • Page 50 Board Power (AO-1) DO-6 (Dehumidification) DO-7 (Reversing Valve) DO-8 (Power Exhaust) SPT (temp Input) Protocol Selector *Remove BACnet, Modbus, or N2 both for 0-5V SPT (common) (LON connection J15) SPT (offset input) C10818 Fig. 59 - RTU- Open Control Module...
  • Page 51 ECONOMIZER SYSTEMS ECONOMI$ER IV CONTROLLER The unit may be equipped with a factory- installed or OUTSIDE AIR WIRING TEMPERATURE SENSOR HARNESS accessory (field- installed) economizer system. Two types LOW AMBIENT SENSOR are available: with a logic control system (EconoMi$er ACTUATOR IV) and without a control system (EconoMi$er2).
  • Page 52 BLACK TRANSFORMER GROUND BLUE 500 OHM RESISTOR VIOLET NOTE 1 PINK OAT SENSOR 24 VAC NOTE 3 50HJ540573 ACTUATOR ASSEMBLY 4-20 mA WHITE DIRECT DRIVE TO J9 ON 4-20mA SIGNAL ACTUATOR PremierLink BOARD ECONOMISER2 PLUG NOTES: 1. Switch on actuator must be in run position for economizer to operate. 2.
  • Page 53 C06053 Fig. 64 - EconoMi$er IV Functional View EconoMi$er IV Standard Sensors SUPPLY AIR TEMPERATURE Table 64 provides a summary of EconoMi$er IV. SENSOR MOUNTING LOCATION Troubleshooting instructions are enclosed. A functional view of the EconoMi$er is shown in Fig. 62. Typical SUPPLY AIR settings, sensor ranges, and jumper positions are also TEMPERATURE...
  • Page 54 factory with a supply- air temperature sensor and an outdoor- air temperature sensor. This allows for operation of the EconoMi$er IV with outdoor air dry bulb changeover control. Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi$er IV and unit.
  • Page 55 Outdoor Enthalpy Changeover Differential Enthalpy Control For enthalpy control, accessory enthalpy sensor (p/n: For differential enthalpy control, the EconoMi$er IV HH57AC078) is required. Replace the standard outdoor controller uses two enthalpy sensors (HH57AC078 and dry bulb temperature sensor with the accessory enthalpy CRENTDIF004A00), one in the outside air and one in the sensor in the same mounting location.
  • Page 56 Indoor Air Quality (IAQ) Sensor Input requirements. The maximum demand ventilation position is used for fully occupied ventilation. The IAQ input can be used for demand control ventilation When demand ventilation control is not being used, the control based on the level of CO measured in the space minimum position potentiometer should be used to set the or return air duct.
  • Page 57 A proportional anticipatory strategy should be taken with the following conditions: a zone with a large area, varied Use setting 1 or 2 for Bryant equipment. See Table 23. occupancy, and equipment that cannot exceed the required 1. Press Clear and Mode buttons. Hold at least 5 ventilation rate at design conditions.
  • Page 58 Differential Enthalpy 3. Use the Up/Down button to select the preset number. See Table 23. 4. Press Enter to lock in the selection. To check differential enthalpy: 5. Press Mode to exit and resume normal operation. 1. Make sure EconoMi$er IV preparation procedure has The custom settings of the CO sensor can be changed been performed.
  • Page 59 PRE- START- UP/START- UP 1. Make sure EconoMi$er IV preparation procedure has been performed. WARNING 2. Connect a 9v battery to AQ (positive node) and AQ1 (negative node). The DCV LED should turn on. The actuator should drive to between 90 and 95% open. PERSONAL INJURY HAZARD 3.
  • Page 60 START- UP, GENERAL 3. Make the following inspections: a. Inspect for shipping and handling damages such Unit Preparation as broken lines, loose parts, or disconnected wires, etc. Make sure that unit has been installed in accordance with b. Inspect for oil at all refrigerant tubing connec- installation instructions and applicable codes.
  • Page 61 relocation as intended during installation. Inspect special or remove compressor hold down bolts. wiring as directed below. Internal Wiring Gas Piping Check all electrical connections in unit control boxes. Check gas piping for leaks. Tighten as required. WARNING Refrigerant Service Ports Each unit system has two 1/4”...
  • Page 62 verify that the burners light and evaporator fan is The evaporator- fan off delay can also be modified. Once energized. Check heating effect, then lower the thermostat the call for heating has ended, there is a 10- minute period setting below the room temperature and verify that the during which the modification can occur.
  • Page 63 FASTENER TORQUE VALUES Table 24 – Torque Values Supply fan motor mounting  120 in- lbs (13.6 Nm) 12 in- lbs (1.4Nm) Supply fan motor adjustment plate  120 in- lbs (13.6 Nm) 12 in- lbs (1.4Nm) Motor pulley setscrew ...
  • Page 64 APPENDIX I. MODEL NUMBER NOMENCLATURE 13 14 Unit Type Packaging and 2-Speed Indoor Fan High Efficiency Motor Gas Heat RTU A – Standard Packaging B – LTL Packaging D – Standard Packaging and 2 speed Model J – Puron Refrigerant Model indoor fan motor E –...
  • Page 65 APPENDIX II. PHYSICAL DATA Table 25 – PHYSICAL DATA (COOLING) 3 - 4 TONS 581J*04A 581J*04B 581J*05A 581J05B Refrigeration System # Circuits / # Comp. / Type 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / Scroll R- 410a charge A/B (lbs - oz) 9 - 0...
  • Page 66 APPENDIX II. PHYSICAL DATA (CONT’D) Table 25 (cont.) - PHYSICAL DATA (COOLING) 5 - 6 TONS 581J*06A 581J*06B 581J*07A 581J*07B Refrigeration System # Circuits / # Comp. / Type 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / Scroll 1 / 1 / Scroll R- 410a charge A/B (lbs - oz) 13 - 3...
  • Page 67 APPENDIX II. PHYSICAL DATA (cont.) Table 25 (cont.) - PHYSICAL DATA (COOLING) 7- 1/2 - 8- 1/2 TONS 581J*08D 581J*09D Refrigeration System # Circuits / # Comp. / Type 2 / 2 / Scroll 2 / 2 / Scroll RTPF models R- 410a charge A/B (lbs - oz) 9 - 10 / 9 - 10 9 - 14 / 9 - 14 oil A/B (oz)
  • Page 68 APPENDIX II. PHYSICAL DATA (cont.) Table 25 (cont.) - PHYSICAL DATA (COOLING) 10 TONS 581J*11D 581J*12D Refrigeration System # Circuits / # Comp. / Type 2/2/Scroll 2 / 2 / Scroll RTPF models R- 410a charge A/B (lbs - oz) 12- 10/ 13- 0 12 - 11/ 12 - 5 Alternate (MCHX) R- 410a charge A/B (lbs - oz)
  • Page 69 APPENDIX II. PHYSICAL DATA (cont.) Table 25 (cont.) - PHYSICAL DATA (COOLING) 12.5 TONS 581J*14D Refrigeration System # Circuits / # Comp. / Type 2 / 2 / Scroll RTPF models R- 410a charge A/B (lbs - oz) 16- 7 / 15- 5 oil A/B (oz) 56/56 Metering device...
  • Page 70 Table 23 (cont.) - PHYSICAL DATA (HEATING) 3 - 6 TONS 581J*04 581J*05 581J*06 581J*07 Gas Connection # of Gas Valves Nat. gas supply line press (in. w.g.)/(PSIG) 4 - 13 / 0.18 - 0.47 4 - 13 / 0.18 - 0.47 4 - 13 / 0.18 - 0.47 4 - 13 / 0.18 - 0.47 Propane supply line press (in.
  • Page 71 APPENDIX II. PHYSICAL DATA (cont.) Table 23 - PHYSICAL DATA (HEATING) 7.5- 12.5 TONS 581J*08 581J*09 581J*11 581J*12 581J*14 Gas Connection # of Gas Valves Nat. gas supply line press 4 - 13 / 4 - 13 / 4 - 13 / 4 - 13 / 5 - 13 / (in.
  • Page 72 APPENDIX III. FAN PERFORMANCE Table 26 – 581J Size 04 1 Phase Perfect Humidity 3 Ton Vertical Supply Available External Static Pressure (in. wg) 0.14 0.25 0.38 0.53 0.69 0.17 0.28 0.41 0.56 1016 0.72 1050 0.19 0.30 0.44 0.59 1036 0.76 1125...
  • Page 73 APPENDIX III. FAN PERFORMANCE (cont.) Table 28 – 581J Size 04 3 Phase Perfect Humidity 3 Ton Vertical Supply Available External Static Pressure (in. wg) 0.14 0.25 0.38 0.53 0.69 0.17 0.28 0.41 0.56 1016 0.72 1050 0.19 0.30 0.44 0.59 1036 0.76...
  • Page 74 APPENDIX III. FAN PERFORMANCE (cont.) Table 30 – 581J Size 04 3 Phase Perfect Humidity 3 Ton Horizontal Supply Available External Static Pressure (in. wg) 0.14 0.24 0.35 0.48 1007 0.63 0.16 0.26 0.38 0.51 1023 0.66 1050 0.18 0.29 0.41 0.55 1040...
  • Page 75 APPENDIX III. FAN PERFORMANCE (cont.) Table 32 – 581J Size 05 1 Phase Perfect Humidity 4 Ton Vertical Supply Available External Static Pressure (in. wg) 1200 0.25 0.37 0.51 0.67 1077 0.84 1300 0.30 0.42 0.57 1028 0.73 1105 0.90 1400 0.35 0.48...
  • Page 76 APPENDIX III. FAN PERFORMANCE (cont.) Table 34 – 581J Size 05 3 Phase Perfect Humidity 4 Ton Vertical Supply Available External Static Pressure (in. wg) 1200 0.25 0.37 0.51 0.67 1077 0.84 1300 0.30 0.42 0.57 1028 0.73 1105 0.90 1400 0.35 0.48...
  • Page 77 APPENDIX III. FAN PERFORMANCE (cont.) Table 36 – 581J Size 05 3 Phase Non- Perfect Humidity 4 Ton Horizontal Supply Available External Static Pressure (in. wg) 1200 0.24 0.35 0.48 0.63 1074 0.78 1300 0.29 0.41 0.54 1019 0.69 1099 0.85 1400 0.34...
  • Page 78 APPENDIX III. FAN PERFORMANCE (cont.) Table 38 – 581J Size 06 1 Phase Perfect Humidity 5 Ton Vertical Supply Available External Static Pressure (in. wg) 1500 0.41 0.55 1067 0.68 1158 0.81 1240 0.93 1625 0.50 1010 0.65 1109 0.79 1198 0.93 1278...
  • Page 79 APPENDIX III. FAN PERFORMANCE (cont.) Table 40 – 581J Size 06 3 Phase Perfect Humidity 5 Ton Vertical Supply Available External Static Pressure (in. wg) 1500 0.41 0.55 1067 0.68 1158 0.81 1240 0.93 1625 0.50 1010 0.65 1109 0.79 1198 0.93 1278...
  • Page 80 APPENDIX III. FAN PERFORMANCE (cont.) Table 42 – 581J Size 06 3 Phase Non- Perfect Humidity 5 Ton Horizontal Supply Available External Static Pressure (in. wg) 0.41 1500 0.55 1002 0.71 1088 0.87 1167 1.05 1625 0.50 0.65 1041 0.81 1125 0.98 1202...
  • Page 81 APPENDIX III. FAN PERFORMANCE (cont.) Table 44 – 581J Size 07 3 Phase Non- Perfect Humidity 6 Ton Vertical Supply Available External Static Pressure (in. wg) 1800 0.34 0.53 0.75 0.99 1.26 1950 0.40 0.60 0.83 1.08 1.35 2100 0.47 0.68 0.91 1.17...
  • Page 82 APPENDIX III. FAN PERFORMANCE (cont.) Table 46 – 581J Size 08 3 Phase Non- Perfect Humidity 7.5 Ton Vertical Supply Available External Static Pressure (in. wg) 2250 0.39 0.54 0.69 0.86 1.03 2438 0.47 0.63 0.79 0.97 1.15 2625 0.56 0.73 0.90 1.08...
  • Page 83 APPENDIX III. FAN PERFORMANCE (cont.) Table 48 – 581J Size 09 3 Phase Non- Perfect Humidity 8.5 Ton Vertical Supply Available External Static Pressure (in. wg) 2250 0.39 0.54 0.69 0.86 1.03 2438 0.47 0.63 0.79 0.97 1.15 2625 0.56 0.73 0.90 1.08...
  • Page 84 APPENDIX III. FAN PERFORMANCE (cont.) Table 50 – 581J Size 11 3 Phase Non- Perfect Humidity 10 Ton Vertical Supply Available External Static Pressure (in. wg) 3000 0.79 0.97 1.16 1.36 1.57 3250 0.96 1.16 1.37 1.58 1.80 3500 1.17 1.38 1.60 1.83...
  • Page 85 APPENDIX III. FAN PERFORMANCE (cont.) Table 52 – 581J Size 12 3 Phase Non- Perfect Humidity 10 Ton Vertical Supply Available External Static Pressure (in. wg) 3000 0.79 0.97 1.16 1.36 1.57 3250 0.96 1.16 1.37 1.58 1.80 3500 1.17 1.38 1.60 1.83...
  • Page 86 APPENDIX III. FAN PERFORMANCE (cont.) Table 54 – 581J Size 14 3 phase 12.5 Ton Vertical Supply Available External Static Pressure (in. wg) 3438 0.59 0.81 1.08 1.40 1.74 3750 0.71 0.95 1.22 1.54 1.90 4063 0.86 1.11 1.39 1.71 2.07 4375 1.03...
  • Page 87 APPENDIX III. FAN PERFORMANCE (cont.) X13 MULTI- SPEED/TORQUE MOTOR Table 56 – 581J*04A Vertical Unit- Direct Drive Table 57 – 581J*04A Horizontal Unit- Direct Drive Speed Speed (Torque) (Torque) 0.30 0.19 0.30 0.19 0.17 0.17 0.17 0.17 1050 0.06 0.16 1050 0.06 0.16...
  • Page 88 APPENDIX III. FAN PERFORMANCE (cont.) X13 MULTI- SPEED/TORQUE MOTOR Table 58 – 581J*05A Vertical Unit- Direct Drive Table 59 – 581J*05AHorizontal Unit- Direct Drive Speed Speed (Torque) (Torque) 1200 0.38 0.30 1200 0.49 0.35 1300 0.24 0.28 1300 0.34 0.33 1400 0.12 0.27...
  • Page 89 APPENDIX III. FAN PERFORMANCE (cont.) X13 MULTI- SPEED/TORQUE MOTOR Table 60 – 581J*06A Vertical Unit- Direct Drive Table 61 – 581J*06A Horizontal Unit- Direct Drive Speed Speed (Torque) (Torque) 1500 0.40 0.50 1500 0.40 0.50 1625 0.20 0.48 1625 0.20 0.48 1750 0.04...
  • Page 90 APPENDIX III. FAN PERFORMANCE (cont.) X13 MULTI- SPEED/TORQUE MOTOR Table 62 – Pulley Adjustment Motor Pulley turns open UNIT Motor/Drive Combo Standard Static Phase Medium Static 1175 1135 1094 1054 1013 Standard Static* Medium Static* 1175 1135 1094 1054 1013 Phase High Static 1466...
  • Page 91 APPENDIX IV. WIRING DIAGRAMS Table 63 – Wiring Diagrams 581J*04A- 14D UNITS STANDARD PERFECT HUMIDITY SIZE VOLTAGE CONTROL POWER CONTROL POWER 230- 1- 60 48TM502525- F 48TM502526- F 48TM503098- I 48TM503099- H 208/230- 3- 60 48TM502525- F 48TM502527- F 48TM503098- I 48TM503100- I A04- A06 460- 3- 60...
  • Page 92 APPENDIX IV. WIRING DIAGRAMS C14047 Fig. 74 - 581J*04A- 06A YAC Control Diagram - 208- 1- 60; 208/230- 3- 60; 460/575- 3- 60...
  • Page 93 APPENDIX IV. WIRING DIAGRAMS C14015 Fig. 75 - 581J*07A YAC Control Diagram - 208/230- 3- 60; 460/575- 3- 60...
  • Page 94 APPENDIX IV. WIRING DIAGRAMS C14021 Fig. 76 - 581J*08D- 09D YAC Control Diagram - 208/230- 3- 60; 460/575- 3- 60...
  • Page 95 APPENDIX IV. WIRING DIAGRAMS C150231 Fig. 77 - 581J*11DYAC Control Diagram - 208/230- 3- 60, 460/575- 3- 60...
  • Page 96 APPENDIX IV. WIRING DIAGRAMS C14026 Fig. 78 - 581J*12D YAC Control Diagram - 208/230- 3- 60; 460/575- 3- 60...
  • Page 97 APPENDIX IV. WIRING DIAGRAMS C14007 Fig. 79 - 581J*04A- 06A YAC Power Diagram - 230- 1- 60...
  • Page 98 APPENDIX IV. WIRING DIAGRAMS C14010 Fig. 80 - 581J*04A- 06A YAC Power Diagram - 208/230- 3- 60; 460- 3- 60...
  • Page 99 APPENDIX IV. WIRING DIAGRAMS C14013 Fig. 81 - 581J*04A- 06A YAC Power Diagram - 575- 3- 60...
  • Page 100 APPENDIX IV. WIRING DIAGRAMS C14018 Fig. 82 - 581J*04A- 06A YAC Power Diagram - 208/230- 3- 60, 460- 3- 60...
  • Page 101 APPENDIX IV. WIRING DIAGRAMS C14019 Fig. 83 - 581J*04A- 06A YAC Power Diagram - 575- 3- 60...
  • Page 102 APPENDIX IV. WIRING DIAGRAMS C13484 Fig. 84 - 581J*08D- 09D YAC Power Diagram - 230/460- 3- 60...
  • Page 103 APPENDIX IV. WIRING DIAGRAMS C14024 Fig. 85 - 581J*08D- 09D YAC Power Diagram - 575- 3- 60...
  • Page 104 APPENDIX IV. WIRING DIAGRAMS C150232 Fig. 86 - 581J*11 YAC Power Diagram 208/230- 3- 60...
  • Page 105 APPENDIX IV. WIRING DIAGRAMS C150234 Fig. 87 - 581J*11D YAC Power Diagram 460- 3- 60...
  • Page 106 APPENDIX IV. WIRING DIAGRAMS C150235 Fig. 88 - 581J*11D YAC Power Diagram 575- 3- 60...
  • Page 107 APPENDIX IV. WIRING DIAGRAMS C14027 Fig. 89 - 581J*12D YAC Power Diagram - 230/460- 3- 60...
  • Page 108 APPENDIX IV. WIRING DIAGRAMS C14029 Fig. 90 - 581J*12D YAC Power Diagram - 575- 3- 60...
  • Page 109 APPENDIX IV. WIRING DIAGRAMS C14031 Fig. 91 - 581J*14D YAC Control Diagram - 208/230- 3- 60; 460/575- 3- 60...
  • Page 110 APPENDIX IV. WIRING DIAGRAMS C14032 Fig. 92 - 581J*14D YAC Power Diagram - 230/460- 3- 60...
  • Page 111 APPENDIX IV. WIRING DIAGRAMS C12462 Fig. 93 - 581J*14D YAC Power Diagram - 575- 3- 60...
  • Page 112 APPENDIX IV. WIRING DIAGRAMS C14008 Fig. 94 - 581J*04A- 06A YAC Control Diagram - 230- 1- 60; 230/460/575- 3- 60 with Perfect Humidity...
  • Page 113 APPENDIX IV. WIRING DIAGRAMS C14016 Fig. 95 - 581J*07A YAC Control Diagram - 230- 1- 60; 230/460/575- 3- 60 with Perfect Humidity...
  • Page 114 APPENDIX IV. WIRING DIAGRAMS C14022 Fig. 96 - 581J*08D- 09D YAC Control Diagram - 230/460/575- 3- 60 with Perfect Humidity...
  • Page 115 APPENDIX IV. WIRING DIAGRAMS C150233 Fig. 97 - 581J*07A YAC Control Diagram - 230- 1- 60; 230/460/575- 3- 60 with Perfect Humidity...
  • Page 116 APPENDIX IV. WIRING DIAGRAMS C14028 Fig. 98 - 581J*12D YAC Control Diagram - 230/460/575- 3- 60 with Perfect Humidity...
  • Page 117 APPENDIX IV. WIRING DIAGRAMS C14009 Fig. 99 - 581J*04A- 06A YAC Power Diagram - 230- 1- 60 with Perfect Humidity...
  • Page 118 APPENDIX IV. WIRING DIAGRAMS C14012 Fig. 100 - 581J*04A- 06A YAC Power Diagram - 230/460- 3- 60 with Perfect Humidity...
  • Page 119 APPENDIX IV. WIRING DIAGRAMS C14014 Fig. 101 - 581J*04A- 06A YAC Power Diagram - 575- 3- 60 with Perfect Humidity...
  • Page 120 APPENDIX IV. WIRING DIAGRAMS C14017 Fig. 102 - 581J*07A YAC Power Diagram - 230/460- 3- 60 with Perfect Humidity...
  • Page 121 APPENDIX IV. WIRING DIAGRAMS C14020 Fig. 103 - 581J*07A YAC Power Diagram - 575- 3- 60 with Perfect Humidity...
  • Page 122 APPENDIX IV. WIRING DIAGRAMS C14023 Fig. 104 - 581J*08D- 09DYAC Power Diagram - 230/460- 3- 60 with Perfect Humidity...
  • Page 123 APPENDIX IV. WIRING DIAGRAMS C14025 Fig. 105 - 581J*08D- 09D YAC Power Diagram - 575- 3- 60 with Perfect Humidity...
  • Page 124 APPENDIX IV. WIRING DIAGRAMS C150236 Fig. 106 - 581J*04A- 06A YAC Power Diagram - 230- 3- 60 with Perfect Humidity...
  • Page 125 APPENDIX IV. WIRING DIAGRAMS C150237 Fig. 107 - 581J*04A- 06A YAC Power Diagram - 460- 3- 60 with Perfect Humidity...
  • Page 126 APPENDIX IV. WIRING DIAGRAMS C150238 Fig. 108 - 581J*04A- 06A YAC Power Diagram - 575- 3- 60 with Perfect Humidity...
  • Page 127 APPENDIX IV. WIRING DIAGRAMS C14030 Fig. 109 - 581J*12D YAC Power Diagram - 230/460- 3- 60 with Perfect Humidity...
  • Page 128 APPENDIX IV. WIRING DIAGRAMS C14046 Fig. 110 - 581J*12D YAC Power Diagram - 575- 3- 60 with Perfect Humidity...
  • Page 129 APPENDIX IV. WIRING DIAGRAMS C14033 Fig. 111 - 581J*14D YAC Control Diagram - 230/460/575- 3- 60 with Perfect Humidity...
  • Page 130 APPENDIX IV. WIRING DIAGRAMS C12464 Fig. 112 - 581J*14D YAC Power Diagram - 230/460- 3- 60 with Perfect Humidity...
  • Page 131 APPENDIX IV. WIRING DIAGRAMS C12465 Fig. 113 - 581J*14D YAC Power Diagram - 575- 3- 60 with Perfect Humidity...
  • Page 132 APPENDIX IV. WIRING DIAGRAMS 50HE500751 50HE500891 C12263 Fig. 114 - RTU Open System Control Wiring Diagram...
  • Page 133 APPENDIX IV. WIRING DIAGRAMS C14035 Fig. 115 - RTU Open System Control Wiring Diagram with Perfect Humidity...
  • Page 134 APPENDIX IV. WIRING DIAGRAMS C14034 Fig. 116 - RTU- Open Wiring Diagram...
  • Page 135 APPENDIX V. MOTORMASTER SENSOR LOCATIONS C10273 C10274 Fig. 117 - 581J*04A Outdoor Circuiting Fig. 119 - 581J*07A Outdoor Circuiting C08260 C08262 Fig. 118 - 581J*05/06A Outdoor Circuiting Fig. 120 - 581J*08A Outdoor Circuiting...
  • Page 136 APPENDIX V. MOTORMASTER SENSOR LOCATIONS (cont.) C08263 Fig. 121 - 581J*09D Outdoor Circuiting SENSOR SENSOR LOCATION LOCATION CIRCUIT A CIRCUIT B C12495 Fig. 122 - 581J*12D Outdoor Circuiting (Circuit A and Circuit B) NOTE: Motormaster Sensor location for 581J*12 is unavailable.
  • Page 137 SENSOR LOCATION TIE WRAP 9.0” C12492 Fig. 123 - 581J*08D Motormaster Sensor Location - Novation Coils (MCHX) SENSOR LOCATION TIE WRAP 11.0” C12493 Fig. 124 - 581J*12D Motormaster Sensor Location - Novation Coils (MCHX)
  • Page 138 VERIFY SMOKE DETECTOR PROVIDES UNIT SHUTDOWN UTILIZING MAGNET TEST. Catalog No. SM581J- 4- 14- 01 E2015 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Edition Date: 06/15 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.