CONTENTS Safety Instructions ..........4 Phase Monitor ............ 33 General Information ..........12 Condenser Fan Operation ........33 Shipping Damage ..........12 Service Hints ............. 33 Additional Publications ........12 Sequence of Operation ........33 Heat Pump Wall Mount Model Nomenclature ..13 Cooling Stage 1 ..........
Page 3
FIGURES TABLES Figure 1 Front Control Panel Cover ....14 Table 1 Clearance Required for Service Access Figure 2 Removing Left Filter ......14 and Adequate Condenser Airflow ... 20 Figure 3 Removing Second Filter ....... 15 Table 2 Minimum Clearances Required to Figure 4 Filter Tabs in Up Position .....
SAFETY INSTRUCTIONS READ ALL INSTRUCTIONS BEFORE USE Your safety and the safety of others are very important. We have provided many important safety messages in this manual and on your appliance. Always read and follow all safety messages. ANSI Z535.5 Definitions: DANGER: Indicate[s] a hazardous situation which, if not avoided, will result in death or serious injury.
Page 5
WARNING CAUTION Electrical shock hazard. Sharp metallic edges. Have a properly trained individual perform Take care and wear appropriate protective these tasks. devices to avoid accidental contact with sharp edges. Failure to do so could result in electric shock or death. Failure to do so can result in personal injury.
Page 6
IMPORTANT SAFETY INSTRUCTIONS WARNING To reduce the risk of explosion, fire, death, electric shock, scalding or injury to persons when using this product, follow basic precautions, including the following: GENERAL · The equipment covered in this manual is to be installed by trained, experienced service and installation technicians.
IMPORTANT SAFETY INSTRUCTIONS WARNING OPERATION · This appliance is not intended for use by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. ·...
INSTRUCTIONS DE SÉCURITÉ LIRE TOUTES LES INSTRUCTIONS AVANT UTILISATION Votre sécurité et celle des autres sont très importantes. Nous avons fourni de nombreux messages de sécurité importants dans ce manuel et sur votre appareil. Lisez et suivez toujours tous les messages de sécurité. Définitions ANSI Z535.5 : DANGER : Indique une situation dangereuse qui, si elle n’est pas évitée, entraînera certainement la mort ou des blessures graves.
Page 9
AVERTISSEMENT ATTENTION Risque de choc électrique. Arêtes métalliques vives. Ces tâches doivent être réalisées par une Faites attention et portez des dispositifs de personne parfaitement qualifiée et formée. protection appropriés pour éviter tout contact accidentel avec des arêtes vives. Le non-respect de cette consigne peut entraîner des chocs électriques ou la mort.
INSTRUCTIONS DE SÉCURITÉ IMPORTANTES AVERTISSEMENT Pour réduire le risque d’explosion, d’incendie, de décès, de choc électrique, d’échaudure ou de blessures pour les personnes lors de l’utilisation de ce produit, suivez les précautions de base, notamment les suivantes : GÉNÉRALITÉS · L’équipement couvert dans ce manuel doit être installé par des techniciens de service et d’installation formés et expérimentés.
INSTRUCTIONS DE SÉCURITÉ IMPORTANTES AVERTISSEMENT OPÉRATION · Cet appareil n’est pas destiné à être utilisé par des personnes (y compris des enfants) ayant des capacités physiques, sensorielles ou mentales réduites, ou un manque d’expérience et de connaissances, à moins qu’elles n’aient reçu une supervision ou une instruction concernant l’utilisation de l’appareil par une personne responsable de leur sécurité.
GENERAL INFORMATION General Additional Publications The equipment covered in this manual is to be installed These publications can help when installing the heat by trained, experienced service and installation pump. They can usually be found at the local library technicians. or purchased directly from the publisher.
Wall Mount Heat Pump Model Nomenclature – 0Z X MODEL SERIES ACCESSORIES & 2 Stage Quiet Climate CONTROL OPTIONS X – Standard Controls CAPACITY (HPS, LPS, CCM) 36 – 3.0 Ton E – Low Ambient Control 42 – 3.5 Ton (LAC) 48 –...
5/8". Any grille that meets with 5/8" louver criteria may be FIGURE 2 used. It is recommended that Bard Return Air Grille Removing Left Filter Kits RG5 or RFG5 be installed when no return duct is used.
FIGURE 3 2. Locate the filter support brackets and remove the four (4) screws holding them to the top of the Removing Second Filter control panel (see Figure 6). FIGURE 6 Remove Four Screws 3. Reverse the order for new filter installation. 3.
Fresh Air Intake 6. Install the right 2" filter first followed by the left filter (see Figures 9 and 10). All units are built with fresh air inlet louvers punched NOTE: When installing new filters, make sure that in the side grilles. airflow arrows on filters point up.
INSTALLATION Basic Installation Design and Portable or modular building placement must be in a way that the wall mount units have a constant supply Application Planning of outdoor air for proper unit operation. Make sure that Successful unit installations require proper planning the service panels of the unit are accessible.
5/8". It is recommended that a unit supply and return flanges before unit installation to Bard Return Air Grille Kit is installed that is designed help with duct connections inside the structure. Supply specifically for the wall mount product. Contact the and return ducts must be properly sized for the design local Bard distributor or visit www.bardhvac.com for...
Materials/Tools List is not required. Review all requirements listed on unit labels and on serial plate located on the side Additional hardware and miscellaneous supplies are of the unit. needed for installation. These items are field supplied and must be sourced before installation. This list also 2.
TABLE 1 TABLE 2 Clearance Required for Service Access and Minimum Clearances Required Adequate Condenser Airflow to Combustible Materials Left Right Discharge – Model Supply Air Duct (1st 3') Cabinet Model Side* Side* Front C36HF C36HF C42HF C42HF 1/4" 0" 20"...
FIGURE 14 Mounting Instructions SEAL WITH BEAD UNITS REQUIRED DIMESIONS OF CAULKING ALONG REQUIRED DIMESIONS TO ENTIRE LENGTH OF MAINTAIN 1/4" MIN. CLEARANCE 30 1/2 10 1/2 6 1/4 1 1/4 29 3/4 16 1 7/8 TOP. FROM COMBUSTIBLE MATERIALS C36HF-42HF C36HY-C42HY RAIN FLASHING...
FIGURE 15 Electric Heat Clearance Typical Building Wall Frame Outside Sheeting Inside Sheeting Supply Air Unit Duct 1/4" Min. Supply Air Duct See Note Below Flange of Wall Note: Side section view of supply air duct for wall mounted unit showing 1/4"...
FIGURE 16 Wall Mounting Instructions See Figure 14 Mounting Instructions FACTORY SUPPLIED RAIN FLASHING. WALL STRUCTURE MOUNT ON UNIT BEFORE INSTALLATION SUPPLY AIR OPENING RETURN AIR OPENING WOOD OR STEEL SIDING BOTTOM MOUNTING BRACKET. MOUNT ON WALL BEFORE INSTALLING UNIT. CONCRETE BLOCK WALL INSTALLATION WOOD FRAME WALL INSTALLATION SIDE VIEW...
FIGURE 18 Common Wall Mounting Installations Non-Ducted Installations Ducted Installations Unit is Unit is Ceiling Ceiling sealed to sealed to wall. wall. Supply Air Duct Adjustable Supply Grille Optional Dropped Ceiling Wall Wall Mount Mount Fixed Blade Unit Unit Fixed Blade Return Grille Return Grille Indoor Area Indoor Area...
Wiring – Main Power All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions WARNING must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material.
Unit Shutdown Feature (Standard on All Models) control panel where the connections are made. (The field wire shield can be removed for wire installation.) The RT terminal is the 24VAC transformer output, If field power is supplied to the right of side of the unit, and the R terminal is the 24VAC hot terminal for the the low voltage wires can be run under the field wire operation of the equipment.
(1120-445) If the unit is being installed with any ventilation package, Auto or Manual Changeover a Bard LAC kit must be installed. Failure to utilize an Dehumidification Output LAC with any heat pump can cause coil freeze up. 2 Stage Cool, 2 Stage Heat...
BrightStat with Heat Pump Unit and Economizer, No Electric Heat Terminal Function BrightStat See TABLE: BO1 - ON/OFF VENT OUTPUT Bard #8403-081 or Terminal Functions B02 - Y2 COMP OUTPUT Bard #8403-083 B03 - Y1 COMP OUTPUT B04 - G FAN OUTPUT...
BrightStat with Heat Pump Unit and Modulating CO2 Vent, Electric Heat Terminal Function BrightStat See TABLE: BO1 - ON/OFF VENT OUTPUT Bard #8403-081 or B02 - Y2 COMP OUTPUT Terminal Functions Bard #8403-083 B03 - Y1 COMP OUTPUT B04 - G FAN OUTPUT...
Non-Programmable Thermostat Connections T4 Pro 8403-095 8403-047 ELECTRONIC HUMIDISTAT T6 Pro 8403-090 or 8403-092 8403-100 U/DEH U/DEH ELECTRONIC HUMIDISTAT Optional CO2 Controller Bard Part #8403-096 24VAC CO2 OUT TEMP-OUT Unit Low B/W1 Voltage Term. Strip 12-Pin Vent Plug MIS-4064 L ALL VENT OPTIONS PLUG IN HERE If not equipped with a ventilation option to plug in, a jumper plug must be installed.
Topping Off System Charge of liquid, any further rise in temperature will cause it to burst. If a leak has occurred in the system, Bard Manufacturing recommends reclaiming, evacuating Important Installer Note (see manual 2100-810) and charging to the nameplate For improved start-up performance, wash the indoor charge.
Three Phase Scroll Compressor Start Condenser Fan Operation Up Information NOTE: Certain models may be equipped with a low ambient control (LAC), and if so, the condenser Scroll compressors, like several other types of fan motor will have a delayed start until system compressors, will only compress in one rotational refrigerant operating pressure builds up.
If the unit is being installed with any ventilation package, sequence in a matter of seconds and will automatically a Bard LAC kit must be installed. Failure to utilize an terminate the defrost sequence. LAC with any heat pump can cause coil freeze up.
FIGURE 23 Defrost Control Board TIME (SEC) LOW PRESSURE BYPASS TIMER SWITCH 120* *(FACTORY SETTING 120 SECONDS) ACCUMULATED DEFROST TIME TIMER (FACTORY SETTING 60 MIN.) Model Setting MIS-2668 A C36HF C42HF C48HF C60HF This can be used to check defrost operation of the unit In order to terminate the defrost test, the SEN JMP jumper must be removed.
LED will have a fast blink rate when in the compressor To change a Coremax valve without first removing the time delay. In some instances, it is helpful to the refrigerant, a special tool is required which can be service technician to override or speed up this timing obtained at www.fastestinc.com/en/SCCA07H.
SERVICE Solid State Heat Pump Control NOTE: If there was no power to 24 volt transformer, Troubleshooting Procedure the compressor and outdoor fan motor will not start for 5 minutes. This is because of the 1. NOTE: A thorough understanding of the defrost compressor short cycle protection.
Checking Temperature Sensor Outside 3. Check resistance reading to chart of resistance. Use sensor ambient temperature. (Tolerance of part Unit Circuit is ± 10%.) 1. Disconnect temperature sensor from board and 4. If sensor resistance reads very low, sensor is from outdoor coil.
Troubleshooting ECM Indoor Blower Motors CAUTION: Disconnect power from unit before removing or replacing connectors, or servicing motor. To avoid electric shock from the motor’s capacitors, disconnect power and wait at least 5 minutes before opening motor. Do’s and Dont’s Symptom Cause/Procedure Don’t...
Replacing ECM Control Module 7. Verify that the replacement control is correct for the application. Refer to the manufacturer’s The following steps must be taken to replace the authorized replacement list. Using the wrong control module for the GE variable-speed indoor blower control will result in improper or no blower motor: operation.
FIGURE 24 Winding Test Control Disassembly Control Disassembly Motor Connector (3-pin) From Motor Push until Latch Seats Over Ramp Circuit Board Motor Winding Test Control Disassembly Motor OK when R > 100k ohm Motor Connector (3-pin) From Motor Push until Latch Seats Drip Loop Over Ramp...
Refrigerant Leak Detection System Why RDS? (RDS) R-454B refrigerant carries an "A2L" safety classification, meaning it is mildly flammable in This unit is equipped with a refrigerant leak detection certain concentrations. The purpose of the RDS is to system (RDS). This system monitors the air in the prevent refrigerant from reaching potentially dangerous indoor section of the unit for refrigerant leaks.
Failure Mode and the sensor will need to be replaced. external alarm or notify a building management The sensor must be replaced with a Bard-approved system or thermostat that a leak has occurred. refrigerant sensor. See unit replacement parts manual for the correct replacement sensor information.
FIGURE 30 Refrigerant Leak Detection System (RDS) Troubleshooting Is the Unit in Mitigation Mode? Check RDS Sensor LED LED Light LED Light LED Light LED Light LED Light LED Light is Solid is Solid or is Blinking is Solid or is Blinking is Solid Blinking...
Fan Blade Setting Dimensions Condenser Coil Cleaning Access Shown in Figure 32 is the correct fan blade setting 1. Disconnect all power to the unit. for proper air delivery across the outdoor coil. Refer to 2. On the side opposite of the compressor, remove the Table 11 for unit specific dimension.
TABLE 12B Cooling Pressures – Part Load Air Temperature Entering Outdoor Coil °F Return Air Model Temp Pressure (DB/WB) Suction Pressure 75/62 Head Pressure Suction Pressure C36HF 80/67 Head Pressure Suction Pressure 85/72 Head Pressure Suction Pressure 75/62 Head Pressure Suction Pressure C42HF 80/67...
TABLE 14 Electrical Specifications − C**HF Series Single Circuit Multiple Circuit No. Field Minimum Maximum Rated Volts Model Power Circuit External Fuse or Minimum Maximum & Phase Circuits Ampacity Circuit Breaker Circuit External Fuse or Ampacity Circuit Breaker Circuit Circuit...
Unit Airflow Dirty Filter Switch These units are equipped with a variable speed (ECM) 1. Disconnect all power to the unit. Remove control indoor motor that automatically adjusts itself to panel outer cover and upper front panel. maintain approximately the same rate of indoor airflow 2.
Dirty Filter Switch Adjustment 5. Replace the upper front panel and repeat Steps 1-3. Continue to make adjustments described in 1. Apply power to the unit. Step 4 until the desired restriction is obtained. 2. Turn the unit indoor blower on (energize R-G on 6.
Need help?
Do you have a question about the 11EER CH Series and is the answer not in the manual?
Questions and answers