CONTENTS Getting Other Informations and Publications ..3 Open Loop (Well System Applications) Note .............. 21 General Information Water Connection ..........21 Water Source Nomenclature ........4 Well Pump Sizing .......... 21 & 22 Heater Package Nomenclature ....... 8 Start Up Procedure for Open Loop System ... 23 Water Corrosion ..........
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air FOR MORE INFORMATION, CONTACT conditioner or heat pump. You can usually find these at THESE PUBLISHERS: your local library or purchase them directly from the publisher. Be sure to consult current edition of each ACCA Air Conditioning Contractors of America standard.
WATER SOURCE PRODUCT LINE NOMENCLATURE Electrical Characteristics A = 230/208-60-1 Modification Code Approximate Capacity Size On High Speed Single Capacity Compressor Vertical Ground Source Heat Pump TABLE 1 1 INDOOR BLOWER PERFORMANCE (RATED CFM) f r i 1 Motor will deliver consistent CFM through voltage supply range with no deterioration (197-253V for all 230/208V models).
HEATER PACKAGE NOMENCLATURE C = Circuit Breaker Nominal KW A = 240/208-1-60 Modification Code GSV = Ground Source Vertical 3 = 3 Ton 5 = 5 Ton Electric Heater TABLE 5 ELECTRICAL SPECIFICATIONS l e i e l l l e i e l l + Based on 75F copper wire.
APPLICATION AND LOCATION compressor compartment and re-securing the control GENERAL panel on the opposite side of the water coil. (See Figure Units are shipped completely assembled and internally 2.) The two (2) access doors from the right hand return wired, requiring only duct connections, thermostat can be transferred to the left-hand return side and the wiring, 230/208 volt AC power wiring, and water one (1) left hand panel can be transferred to the right...
FIGURE 2 FIELD-CONVERSION TO LEFT HAND RETURN REMOVE SINGLE AND DOUBLE DOORS 1 REMOVE 4 SCREWS SECURING COVER 2 REMOVE 2 SCREWS HOLDING CONTROL BOX TO CORNER PANEL REMOVE 2 SCREWS SECURING PANEL TO BASE. 3 PASS CONTROL PANEL THROUGH COMPRESSOR SECTION 4 RE-SECURE CONTROL PANEL ON OPPOSITE SIDE IN SAME MANNER...
filled with water prior to start up. The use of plugged FILTER tees in place of elbows to facilitate cleaning is highly This unit must not be operated without a filter. It comes recommended. equipped with disposable filters, which should be Drain lines must be installed according to local checked often and replaced if dirty.
WIRING INSTRUCTIONS GENERAL TABLE 6 CONTROL CIRCUIT WIRING All wiring must be installed in accordance with the National Electrical Code and local codes. In Canada, all wiring must be installed in accordance with the Canadian Electrical Code and in accordance with the regulations of the authorities having jurisdiction.
THERMOSTAT INDICATORS BLOWER CONTROL SETUP 8403-058 (TH5220D1151) Thermostat: Due to the unique functions that the ECM blower motor is able to perform each installation requires that the Thermostat will display on the screen “Em Heat” when jumpers on the blower control board be checked and the thermostat is set on emergency heat.
The and circulator selection will eliminate this problem design eliminates most causes of system failure. Bard supplies a work sheet to simplify head loss Surprisingly, the heat pump itself is rarely the cause. calculations and circulator selection. Refer to Most problems occur because designers and installers “Circulating Pump Worksheet”...
START UP PROCEDURE FOR CLOSED recheck the selection of the loop pump module LOOP SYSTEM model for sufficient capacity. If the module selection is correct, there is probably trapped air or a 1. Be sure main power to the unit is OFF at disconnect. restriction in the piping circuit.
FIGURE 7 DIAL FACE PRESSURE GAUGE THERMOMETER WITH GAUGE ADAPTOR WATER COIL CONNECTION AT HEAT PUMP 1" AND 3/4" MPT BARB X INSERT BRASS ADAPTER SELF SEALING PETE’S TEST PLUG TEST PLUG CAP FIGURE 8 PERFORMANCE MODEL GPM-1 LOOP PUMP MODULE Flow (GPM) FIGURE 9 PERFORMANCE MODEL GPM-2 LOOP PUMP MODULE...
OPEN LOOP (WELL SYSTEM APPLICATIONS) NOTE: Strainer (5) installed upstream of constant flow valve (7) to collect foreign material which would clog the flow Unit shipped from factory with 27 PSIG low valve orifice. pressure switch wired into control circuit for open loop applications.
The pressure requirements put on the pump are directly that the piping is not undersized, which would create too affected by the diameter of pipe being used, as well as, much pressure due to friction loss. High pressure losses by the water flow rate through the pipe. The worksheet due to undersized pipe will reduce efficiency and included in manual 2110-078 should guarantee that the require larger pumps and could also create water noise...
SYSTEM START UP PROCEDURE FOR WATER CORROSION OPEN LOOP APPLICATIONS Two concerns will immediately come to light when 1. Be sure main power to the unit is OFF at disconnect. considering a water source heat pump, whether for ground water or for a closed loop application: Will 2.
4. Scale Formation. Of all the water problems, the for the product used as to how long the solutions to be formation of scale by ground water is by far the most circulated, but it is usually circulated for a period of common.
D. Size the pump to provide necessary GPM for the K. Locate the discharge high enough above high water ground water heat pump. A 12 GPM or greater level so the water will not back up and freeze inside water flow rate is required on all modes when used the drain pipe.
SEQUENCE OF OPERATION between “R” and “W1” will open de-energizing the BLOWER heat package time delay relay (s) and the blower. The blower on/off actuation will depend upon “Delay” selection settings on Blower Control Board, see Blower LOCKOUT CIRCUITS Control Setup section. If thermostat is set to “Manual” Each unit has two separate lockout circuits, one for the or “On”...
FIGURE 13 COMPRESSOR DESUPERHEAT COIL HIGH PRESSURE SWITCH DISCHARGE SERVICE PORT LOW PRESSURE SWITCHES REVERSING VALVE WATER COIL EXPANSION VALVE LOW VOLTAGE IN SUCTION SERVICE PORT HIGH VOLTAGE IN FIGURE 14 CONTROL PANEL Manual 2100-317J Page 27 of 39...
SERVICE This unit is equipped with a variable speed ECM motor. SERVICE HINTS The motor is designed to maintain rated airflow up to 1. Caution homeowner to maintain clean air filters at the maximum static allowed. It is important that the tall times.
TROUBLESHOOTING GE ECM MOTORS ™ CAUTION: Symptom Cause/Procedure • Noisy blower or cabinet • Check for loose blower housing, panels, etc. Disconnect power from unit before removing or replacing • High static creating high blower speed? connectors, or servicing motor. To avoid electric shock from - Check for air whistling through seams in the motor’s capacitors, disconnect power and wait at least 5 ducts, cabinets or panels...
TROUBLESHOOTING GE ECM MOTORS CONT’D. ™ 8b. IF REPLACING AN ECM 2.3 CONTROL WITH AN ECM 2.3 Replacing ECM Control Module CONTROL, the plastic tab and shorter through-bolts are not needed. To replace the control module for the GE variable-speed indoor blower motor The control can be oriented in two positions 180°...
ACCESSORIES INSTALLATION ADD-ON DPM26A PUMP MODULE KIT 1. Follow all local, state, and national codes applicable NOTE: This section applies only if a DPM26A Pump to the installation of the pump module kit. Module is added. Refer to DPM26A instructions for complete installation details.
GROUND SOURCE HEAT PUMP PERFORMANCE REPORT This performance check report should be filled out by installer and retained with unit. DATE TAKEN BY: UNIT: Mfgr Model No. THERMOSTAT: Mfgr Model No. Person Reporting Company Reporting Installed By Date Installed User’s (Owner’s) Name Address Unit Location WATER SYSTEM INFORMATION...
Page 37
THE FOLLOWING INFORMATION IS NEEDED TO CHECK PERFORMANCE OF UNIT. FLUID SIDE DATA Cooling ** Heating Entering fluid temperature Leaving fluid temperature Entering fluid pressure PSIG Leaving fluid pressure PSIG Pressure drop through coil PSIG Gallons per minute through the water coil Liquid or discharge line pressure PSIG Suction line pressure...