FireClass
FC700 Series
Panels
Installation Guide
120.515.867_FC-FC700-P-I
Doc. version 5.0
24. May 2024

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FC708 and is the answer not in the manual?

Questions and answers

Summary of Contents for FireClass FC708

  • Page 1 FireClass FC700 Series Panels Installation Guide 120.515.867_FC-FC700-P-I Doc. version 5.0 24. May 2024...
  • Page 2 © 2024 Tyco Fire & Security GmbH All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice. Tyco Fire & Security GmbH, Victor von Bruns-Strasse 21, 8212 Neuhausen am Rheinfall, Switzerland...
  • Page 3: Table Of Contents

    Read the Installation Notes ................6 Note Safety Warnings ..................6 FC702/708/718 panels ..................6 Mounting a FC702/708/718 panel to the wall ..............6 Connect the Mains Cable and Protective Earths............11 Install the Loops....................11 Run and Temporarily Connect the Loops ..............11 5.1.1...
  • Page 4 Contents FIRECLASS Fire detection system 14.2 Set the S2 DIP Switches ....................35 14.3 Mounting the IOB800 and FB800 boards ..............35 14.3.1 IOB800 Input Output Expansion Card Details ..................37 14.4 FB800 Fused 24V Outputs Board Details ..............39 14.4.1 Mount the Units in the Slot Card Cage ....................39...
  • Page 5: Introduction

    Introduction Introduction What this Manual does not Use this guide as a source of useful information when you install a FireClass FC700 series based alarm sys- cover tem. The guide does not provide information on the follow- The guide sets out a recommended series of steps to ing: follow.
  • Page 6: Read The Installation Notes

    Read the Installation Notes 5A PSU for 38AH batteries. The FC708D is a net- workable panel. There is a section of installation notes in the FireClass FC700 series panels Product Application and Design Mounting a FC702/708/718 panel to Information manual. Check these for information possi-...
  • Page 7 – Tighten the four screws until the panel is fitted securely. – Remove any debris from the housing. Fig. 1: Fixing the FC702/718/708 panel mounting plate 149.5 Fig. 2: FC702S - Mounting plate fixing and overall dimensions in mm 1 – Mounting frame holes...
  • Page 8 FIRECLASS Fire detection system Mounting a FC702/708/718 panel to the wall 214.5 Fig. 3: FC702D, FC718D and FC708D panels - Mounting plate fixing and overall dimensions in mm 1 – Mounting frame holes Installation Guide Doc. version 5.0...
  • Page 9 FIRECLASS Fire detection system Mounting a FC702/708/718 panel to the wall Fig. 4: Fitting the FC702D or FC718/708 panel housing to the deep cover mounting plate - front view Fig. 5: Fitting the FC702D or FC718/708 panel housing to the deep cover mounting plate - rear view...
  • Page 10 FIRECLASS Fire detection system Mounting a FC702/708/718 panel to the wall Fig. 6: Fitting the FC702S panel housing to the shallow cover mounting plate - front view Fig. 7: Fitting the FC702S panel housing to the shallow cover mounting plate - rear view...
  • Page 11: Connect The Mains Cable And Protective Earths

    Ensure the cabling is not connected to the supply, or that the supply is isolated. DANGER The FireClass Control Panel contains high voltages, producing a danger of death or serious injury. You must ensure adequate earthing of the system.
  • Page 12: Interface Conventional Detectors

    FIRECLASS Fire detection system Make Insulation Checks 2 At the control panel, feed the loop cables through 2 Ensure your insulation checks will be at 500 V (set the appropriate knockouts. Use suitable cable glands your meter accordingly). as needed. To maintain IP30 pass test status, use a 3 Make the usual insulation measurements.
  • Page 13: Install The Batteries

    FIRECLASS Fire detection system Install the Batteries Install the Batteries NOTICE Ensure that the battery complies with the following:  t is of the valve regulated lead acid (VRLA) type.  It has an enclosure with flammability class UL94V-1 or better.
  • Page 14: Install The Batteries - Fc700 Series

    FIRECLASS Fire detection system Install the Batteries - FC700 series Fig. 12: Battery installation - FC700 series (deep housing) the red cable to positive and the black cable to neg- ative. 2 Place the batteries at bottom of the control panel housing.
  • Page 15: Mounting Repeater Panels

    FIRECLASS Fire detection system Mounting Repeater Panels 7 Label the batteries with the current date. Fig. 13: Battery installation on a FC702S panel (shallow housing) – Drill a hole to accept the supplied wall plug and insert the plug. Mounting Repeater Panels –...
  • Page 16 40.0 330.0 40.0 410.0 Fig. 14: FireClass Single Loop Panel Shallow and FC8AS FireClass AC Repeater - Overall and Fixing Dimensions Knockouts Ø 20 mm (13x) 1 – Knockouts 2 – Mounting hole Ø 5.5 mm Installation Guide Doc. version 5.0...
  • Page 17: Connect Repeaters

    FIRECLASS Fire detection system Connect repeaters Fig. 15: FC1DS FireClass Compact DC Repeater - Overall and Fixing Dimensions. Connect repeaters 3 Connect an Ethernet cable to the switch. Connect the other end of the Ethernet cable to the connector The FC1DS and FC8AS repeaters connect to the sys- marked ‘XP15 ETH’...
  • Page 18: Fc1Ds Compact Repeater Connection

    FIRECLASS Fire detection system Connect repeaters 5 Configure the Ethernet switch as described in its instruction leaflet. Fig. 16: Mounting a FC8AS repeater with an Ethernet Switch 1 – Earth cable screw (optional) 7.1.2 FC1DS Compact Repeater connection FC-FI Power...
  • Page 19: Install The Batteries - Fc8As

    FIRECLASS Fire detection system Install the batteries - FC8AS – Ethernet cable from XP15 on the FC-FI card. on top of the PSU). There are two of each type of ter- minal – use either one. Connect the red cable to pos- –...
  • Page 20: Provide Installation Records

    FIRECLASS Fire detection system Provide Installation Records Fig. 17: Batteries for the FC8AS repeater Provide Installation Records 2 Make sure all power and signal cables are neatly routed and arranged in the housings. Make sure you provide the site personnel with all rele-...
  • Page 21: Install The Fc-Fi - Field Interface Board

    FIRECLASS Fire detection system Install the FC-FI - Field Interface Board Install the FC-FI - Field Interface Board Fig. 18: FC-FI - Field Interface Board. Installation Guide Doc. version 5.0...
  • Page 22: Make Local Fc-Fi Board Connections

    FIRECLASS Fire detection system Make Local FC-FI Board Connections 10.1 Make Local FC-FI Board Connections 10.2 Connect Local Sounders “Local sounders” are sounders connected directly to the FC-FI board, as opposed to sounders on the NOTICE addressable loop. There is a danger of signal interference Connect the sounders as shown in Fig.
  • Page 23: Connect Supervised Inputs

    Only connect to the Supervised Input if it is set up in the configuration (open the configuration in FireClass Express for example). Connect the switch using series and parallel resistors as shown in Fig.
  • Page 24: Check The Fc-Fi Connections

    FIRECLASS Fire detection system Check the FC-FI Connections 10.4 Check the FC-FI Connections The FC-FI connections are shown in Fig. 20. Not all of these are covered in this guide. For the numbered items ‘2’ and ‘3’, these should have been connected in earlier steps, (which cross-references to this figure).
  • Page 25: Note Fc-Fi Switches And Jumper Positions

    FIRECLASS Fire detection system Note FC-FI Switches and Jumper Positions 10.5 Note FC-FI Switches and PCB Label Function Jumper Positions Terminals: 24V and 5V Power for Third Party Cards The FC-FI board has many connectors, jumpers and configuration switches. These are used, for example,...
  • Page 26: Configuration Of A Fc700 Series Panel Rbus Interface

    FIRECLASS Fire detection system Make Jumper and DIP Switch Settings 10.6.1 Configuration of a FC700 series panel RBus interface The GUI and panel both have built in terminating resis- tors, so external terminating resistors should not be fit- The routing of the RBus is controlled by the DIP ted to the panel.
  • Page 27 FIRECLASS Fire detection system Make Jumper and DIP Switch Settings Jumper OPEN J1 – Relay 3 Normally Open Normally Closed J2 – Relay 4 Normally Open Normally Closed J3 – MCPU Watchdog Active (MCPU in reset) Enabled Enabled J4 – LIOMCU Watchdog...
  • Page 28: Changing A Fuse On The Fc-Fi

    FIRECLASS Fire detection system Changing a Fuse on the FC-FI 10.7 Changing a Fuse on the FC-FI RL4 activated by ALARM The FC-FI has seven user changeable fuses. See Table Position 3 13 for more information. Enabled CAUTION Table 11: FC-FI - RL4 relay activated by ALARM setting (cont.)
  • Page 29: Install Optional Cards And Modules

    FIRECLASS Fire detection system Install Optional Cards and Modules Install Optional Cards and 6 Make sure this address number has not already been allocated – you might have to read the DIP Modules switch settings of already installed cards. 7 If the address number is free, note this to be set on At this stage connect any optional cards and modules the card’s DIP switch, as covered in a later section...
  • Page 30 FIRECLASS Fire detection system Install the PLX800 - Loop Expansion Card ‘Loop E’ (for example) has ‘No addresses’ (zero addresses allocated to it), then you should not con- nect that loop. 5 Set jumper J1 to the “Pin 1 shorted to Pin 2” posi- tion.
  • Page 31: Plx800 Loop Expansion Card Details

    FIRECLASS Fire detection system PLX800 Loop Expansion Card Details 12.1 PLX800 Loop Expansion Card Details Item Function Boot Mode jumper Watchdog Options jumper DIP switch (Internal N-BUS address) Reset button Slot backplane (Internal NBUS) connec- Debug Port (RS232) connector Auxiliary JTAG port for Loop micropro-...
  • Page 32: Install The Pni800 - Network Interface Card

    FIRECLASS Fire detection system Install the PNI800 - Network Interface Card Install the PNI800 - Network State Condition Interface Card Blinking On/Off Firmware update mode 0.1seconds /0.9 seconds Install any PNI800 Network Interface Slot Cards accord- Blinking On/Off Configuration mode ing to the steps below.
  • Page 33 FIRECLASS Fire detection system Install the PNI800 - Network Interface Card SW1 Position Network Baud Rate Item Function See Table 19. 9600 See Table 20, 21, 22, and 19200 See Table 24, 25, 26, and 38400 57600 See Table 28 and 29.
  • Page 34: 13.1 Changing A Fuse On The Pni800

    FIRECLASS Fire detection system Changing a Fuse on the PNI800 NBUS address Emergency MCU FW Position 1 to 7 Upgrade Mode Position 8 Binary coded NBUS Enabled. Mode is acti- address vated after RESET SW 4.1=LSB SW 4.7=MSB Disabled* ON=1...
  • Page 35: Install Iob800 And Fb800 Boards

    If there are cables con- nected to the front of the IOB800 board, leave them connected as they will be inaccessible when the The FireClass FC702D/718/708 panels come supplied IOB800 is fitted. with a slot card adapter to mount a maximum of three 3 Remove the mounting screws from the other boards boards per panel.The FC702S panel can also support up...
  • Page 36 FIRECLASS Fire detection system Mounting the IOB800 and FB800 boards How to mount boards on a FC702S panel 7 Reconnect any cables that you disconnected in step 8 Connect the supply cable from the IOB800 to the XT8 You can mount the PNI800, IOB800, and the FB800 connector on the FC-FI board.
  • Page 37: Iob800 Input Output Expansion Card Details

    FIRECLASS Fire detection system Mounting the IOB800 and FB800 boards FC702S Fig. 28: Mounting Boards on a Panel 1 – Pillars 2 – Screws 3 – Adapter plate Item Function Open Collector outputs 1 to 8, inputs 1 to 8 14.3.1 IOB800 Input Output Expansion Card...
  • Page 38 FIRECLASS Fire detection system Mounting the IOB800 and FB800 boards S1 Position Setting Activation by Emergency Alarm 1. (XT3.1,2,3Relay_1) OFF * / ON Disabled / Enabled 2. (XT3.4,5,6Relay_2) OFF * / ON Disabled / Enabled 3. (XT3.7,8,9Relay_3) OFF * / ON Disabled / Enabled 4.
  • Page 39: Fb800 Fused 24V Outputs Board Details

    FIRECLASS Fire detection system FB800 Fused 24V Outputs Board Details 14.4 FB800 Fused 24V Outputs Board Details Fig. 30: FB800 Terminal Positions 3 Connect the IOB ribbon cable to the connector on Connector Function the FC-FI main board marked ‘XP3 IOBUS’ – this is...
  • Page 40 FIRECLASS Fire detection system FB800 Fused 24V Outputs Board Details Fig. 31: FB800 and IOB800 - Fitting to Backplane Cage Installation Guide Doc. version 5.0...
  • Page 41 FIRECLASS Fire detection system FB800 Fused 24V Outputs Board Details Fig. 32: FB800 and IOB800 - Fitting to FC700 series panels - Part 2 1 – Iron mounting plate 2 – Screw for fixing the iron mounting plate 3 – Second position (second IOB800) 4 –...
  • Page 42: Installing The Csg Connected Services Gateway

    FIRECLASS Fire detection system Installing the CSG Connected Services Gateway Installing the CSG Connected Services Gateway Fig. 34: Mounting boards on the FC702D or FC718/708 panel Callout Description A16381C5EY mounting plate Fig. 33: Connected Services Gateway module M4 screws Callout...
  • Page 43: Optional: Mounting The Cellular Module And Antenna

    FIRECLASS Fire detection system Optional: Mounting the cellular module and antenna wire sequence red wire to panel 24 V supply and black wire to 0 V. Callout Description Mounting pillars in the CIE case Notes A16381TMRV mounting plate  The CSG takes a high inrush current when hot- M3 screws and washers plugged and can blow a 1 A fuse.
  • Page 44 FIRECLASS Fire detection system Optical indicators Status Green LED Yellow LED Normal: connected to the enterprise server Not connected to the Blinking enterprise server, connected to an exter- nal network only Not connected to an external network Failure or error...
  • Page 45: Install Ccu3 And Moxa Modules

    FIRECLASS Fire detection system Install CCU3 and MOXA modules Install CCU3 and MOXA modules 16.1 Fit DIN Rail Modules You need to fit the DIN rail to the left side of the panel housing, at the top, as shown in Fig. 39. You need to purchase the DIN rail, the M4 Nyloc nut and the M4 washer separately.
  • Page 46 FIRECLASS Fire detection system Fit DIN Rail Modules Fig. 39: DIN rail devices on a FC702D, FC718 or a FC708 panel 1 – DIN rail 2 – M4 shake proof washer 3 – M4 Nyloc nut Installation Guide Doc. version 5.0...
  • Page 47: Install Fcz4X Or Fcz8X Zonal Indicators

    FIRECLASS Fire detection system Install FCZ4x or FCZ8x Zonal Indicators Install FCZ4x or FCZ8x Zonal FCZ8DS (FireClass 80 Zone Display) Details The LEDs are divided between ‘Part A’ and ‘Part B’, with Indicators 40 LEDs each. Part A has its lowest address Bit.0 = 0 and Part B has its lowest Address Bit.0 = 1 on the I2C...
  • Page 48 Install FCZ4x or FCZ8x Zonal Indicators FIRECLASS Fire detection system SW100 Address-Part B SW100 Dimming Part B Position 3 and 4 Position 6 Binary coded address Enable SW100.3=Bit.1 SW100.4=Bit.2 OFF * Disable OFF * ON=0 Table 47: FCZ8DS - Dimming setting-Part B OFF=1 * Default.
  • Page 49: Fc1Ds Graphical User Interface (Gui) Details

    FIRECLASS Fire detection system FC1DS Graphical User Interface (GUI) Details FC1DS Graphical User Interface (GUI) Details X500 X1303 X1302 X503 X501 X502 X504 X602 X1301 X601 Fig. 41: FC1DS - Jumper and terminal positions Installation Guide Doc. version 5.0...
  • Page 50: 19 Binary Dip Switch Lookup Table

    FIRECLASS Fire detection system Binary DIP Switch Lookup Table Item Function X500 FC-FI interface connector X501 Left FCNET / N-BUS (RS485) and Power (24V) terminals X502 Right MXNET / N-BUS (RS485) and Power (24V) terminals X503 Bypass Jumper for +24V*...
  • Page 51 FIRECLASS Fire detection system Binary DIP Switch Lookup Table Position Position Position Position 1..8 1..8 1..8 1..8 10100100 01010010 11110110 00000000 01100100 11010010 00001110 10000000 11100100 00110010 10001110 01000000 00010100 10110010 01001110 11000000 10010100 01110010 11001110 00100000 01010100 11110010 00101110...
  • Page 52 FIRECLASS Fire detection system Binary DIP Switch Lookup Table Position Position Position 1...8 1...8 1...8 00101001 10011101 01111011 10101001 01011101 11111011 01101001 11011101 00000111 11101001 00111101 10000111 00011001 10111101 01000111 10011001 01111101 11000111 01011001 11111101 00100111 11011001 00000011 10100111 00111001...
  • Page 53 FIRECLASS Fire detection system Installation Guide Doc. version 5.0...
  • Page 54 120.515.867_FC-FC700-P-I, doc. version 5.0, 24. May 2024 Further information about FIRECLASS can be found on the Internet at www.fireclass.com Company stamp...