SPECIFICATIONS AND FEATURES
MODEL
Nominal DC Input Voltage
AC Output Voltage (RMS)
Nominal Frequency
Continuous Power @ 25 °Ÿ
Continuous Current @ 25 °Ÿ C
Maximum Current (100 mSec surge)
Maximum Power (Light Bulb Rating)
Efficiency (peak)
DC INPUT REQUIREMENTS
Search Mode
On Mode (no load - idle)
At Full Rated Power
Input Voltage Range
Low Battery Cutout (w/out SB Option)
High Voltage Cutout
AC OUTPUT CHARACTERISTICS
AC Output Waveform
Voltage Regulation
Power Factor Allowed
Frequency Regulation
ENVIRONMENTAL LIMITATIONS
Enclosure Type
Specified Temperature Range
Allowed Operating Temperature Range
Dimensions - Inverter Only
Dimensions - Shipping
Mounting
Weight - Inverter only
Weight - Shipping
STAND-BY (SB) OPTION
Automatic AC Transfer Relay
Maximum Battery Charging Rate
3-stage Charger Regulation Method
Selectable Low Battery Cutout
ADDITIONAL OPTIONS
Battery Temperature Sensor
Remote Control Panel
100
90
80
70
60
50
40
0
500
1000
Output in Watts
Typical Efficiency
5916 195th St. N.E. ARLINGTON, WA. USA 98223 Phone (360) 435-8826 Fax (360) 435-2229 Web: www.traceengineering.com
Legend Series I
(rev. 1.0)
L612
12 VDC
120 VAC
60 HZ
°Ÿ
C
600 VA
5 amps AC
18 amps AC
2500 W
92% max
0.022 A (0.4W)
0.400 A (5.0W)
63 amps
10.8 to 15.5 VDC
9.5 VDC
15.7 VDC
32 °Ÿ F to 104 °Ÿ F (0 °Ÿ C to +40 °Ÿ C ) (output will meet specified tolerances)
-40 °Ÿ F to 140 °Ÿ F (-40 °Ÿ C to +60 °Ÿ C ) (output may not meet specified tolerances)
25 lbs (11.4 kg)
30 lbs (13.6 kg)
30 amps AC
25 amps DC
Bulk (constant current), Absorption (constant voltage) and Float (maintenance voltage & current)
9.5 VDC (allows deep discharge) or 11.8 VDC ( for use with starting or shallow cycle batteries)
BTS/15: 15 foot plug-in battery temperature sensor with phone jack (can be extended)
Note: All specifications are subject to change without notice
4,000
3,000
2,000
1,000
0
1500
TIME IN MINUTES
Power vs. Time
L1112
12 VDC
120 VAC
60 HZ
1100 VA
9 amps AC
22 amps AC
3000 W
90% max
0.045 A (0.5W)
0.450 A (5.5W)
120 amps
10.8 to 15.5 VDC
9.5 VDC
15.7 VDC
Modified sinewave
+/- 5% Maximum, +/- 2.5% Typical
-1 to 1
+/- 0.01% (crystal regulated)
Indoor, ventilated, steel chassis with powdercoat finish
10.5" high, 15.5" wide, 6" deep (when wall mounted)
20.5" x 27" x 15.5"
Wall or Shelf Mount
25 lbs (11.4 kg)
30 lbs (13.6 kg)
30 amps AC
50 amps DC
RC8/10: 10 foot On/Off remote with LED status indicator
RC8/25: 25 foot On/Off remote with LED status indicator
1412
1112
612
Battery Charger Method
L1412
12 VDC
120 VAC
60 HZ
1400 VA
12 amps AC
30 amps AC
3400 W
92% max
0.060 A (0.7W)
0.600 A (7.0 W)
153 amps
10.8 to 15.5 VDC
9.5 VDC
15.7 VDC
35 lbs (15.9 kg)
40 lbs (18.2 kg)
30 amps AC
50 amps DC
THE POWER COMPANY
ENGINEERING
Available From:
Rev# 4/98
Need help?
Do you have a question about the LEGEND I and is the answer not in the manual?