Dhi series 36”, 42”, 48”, 54” and 60” wide ceiling mount island hoods
Hide thumbs Also See for DHI361:

Advertisement

Document # PG07 - 002
Observe all governing codes and ordinances during planning
and installation. Contact your local building department for
further information.
This appliance must be installed in accordance with the
accompanying installation instructions.
DO NOT install an additional in-line or external blower to
increase the length of the duct run. Even small differences
between blower air flow rates can greatly reduce the air draw
of the hood.
600 CFM* (1200 CFM* for units with 2 blowers)
Blower
with electronic speed control
Blower Speeds
4
Lights
12 Vac, 20 Watt halogen
Filters
Baffle type, dishwasher safe
Exhaust
8 Inch
Finish
430 stainless steel
Total connected
120 Vac, 60 Hz (see table at right for current
load
rating)
Circuit
120 Vac, 15 Amp. grounded, dedicated 3-wire
requirements
circuit (hot, neutral, ground)
* At zero inches static pressure
GENERAL SPECIfICAtIoNS
Model
Blowers
DHI361
1
DHI421
1
DHI482
2
DHI542
2
DHI602
2
moDEL SPECIfIC SPECIfICAtIoNS
www.Dacor.com
Phone: (800) 793-0093
DHI Hoods
36", 42", 48", 54" and 60" Wide
Ceiling mount Island Hoods
warning
Maximum
Lights
Filters
Current Draw
4
1
3.8 Amp.
4
1
3.8 Amp.
4
2
6.8 Amp.
6
2
7.1 Amp.
6
3
7.1 Amp.
All tolerances: ±1/16" (±1.6 mm), -0, unless otherwise stated
15 ¾" (40.0 cm)
Chimney
* 18" 1/4 on models DHI482, DHI542 and DHI602
DHI SERIES ovERALL DImENSIoNS
Chimney can accommodate up to 10" round duct work
Maximum Duct Length
The maximum straight duct length for the hood is 50 feet. To determine the
actual maximum duct run, subtract the equivalent length of each elbow,
transition and cap from 50 feet. See the Duct Planning Guide or the
installation instructions for more details.
iMPOrTanT: The minimum installed distance from the hood to the cooking
surface must be no less than 30 inches. The minimum specified distance
may be higher for the particular range or cooktop in use. Check the
manufacturers specifications for the cooktop or range.
Specifications are subject to change without notice.
See installation instructions for additional details.
Revised 10/21/09 Page 1/1