Download Print this page
Honeywell R4348B1057 Product Handbook

Honeywell R4348B1057 Product Handbook

Industrial flame switch

Advertisement

Quick Links

INDUSTRIAL FLAME SWITCH
APPLICATION
The R4348B flame switch is for application in large com-
mercial and industrial burner installations.
The function is:
flame safeguard primary controls capable of providing
system „safe start" check and flame sensing functions.
The unit can also be used in installations using an EC7800
microcomputer-based burner control system - to extend the
number of burners being controlled.
The unit includes a 3-pole flame relay which is energized when
flame is sensed and de-energized when „no-flame" is sensed
and a 3-pole line voltage „load relay".
• Standard is a green LED which is illuminated when the
flame relay is energized.
• R4348B1057 only:
– LED bar and 4-20mA output for indicating and / or
recording the flame current strength.
• Unpowered relay outputs enable Honeywell sensors
and amplifiers to be used with a wide range of logic
schemes according to customer needs.
• Plug-in unit makes wiring and servicing easy.
• Plug-in flame signal amplifiers available to match a wide
range of flame sensors.
1
R4348B
PRODUCT HAND BOOK
EN1C-9999SZ22 R1104