2: How To Calculate System Current Draw - Honeywell HPFF12 Installation And Operation Manual

Notification appliance circuit expander
Hide thumbs Also See for HPFF12:
Table of Contents

Advertisement

Power Supply Requirements
6.3.2 How to Calculate System Current Draw
Use Table 6.4 to calculate current draw as follows:
1.
Enter the quantity of devices in all three columns.
2.
Enter the current draw where required. Refer to the specifications of compatible devices for
their current draw.
3.
Calculate the current draws for each in all columns.
4.
Sum the total current for each column.
5.
Copy the totals from Column 2 and Column 3 to Table 6.4.
Following are the types of current that can be entered into Table 6.4 on page 50.
Calculation Column 1 — The primary AC supply current load that the power supply must
support during a non-alarm condition, with AC power applied
Calculation Column 2 — The primary AC supply current load that the power supply must
support during an alarm condition, with AC power applied
Calculation Column 3 — The standby current drawn from the batteries in a non-alarm
condition during a loss of AC
Table 6.4 contains three columns for calculating current draws. For each column, calculate and
enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation
Column 2 and Calculation Column 3 to Table 6.5.
Calculate Column 1
Device Type
Primary, Non-Alarm Current
(Amps RMS)
Qty X (current draw) = Total
Main Circuit Board
Trouble Contacts
1
(coil current)
1
NAC Output #1
NAC Output #2
NAC Output #3
NAC Output #4
Auxiliary Output
Current Draw from
2
TB4
Terminals
+A & –A
Sum each column
Primary Non-Alarm =
for total:
1.
Current limitation on TB4 NAC circuits is 3.0 Amps per NAC.
2.
Current limitation on TB4 AUX Output is 2.0 Amps.
3.
Total current draw cannot exceed 12.0 Amps in alarm.
50
Calculate Column 2
Primary, Fire Alarm Current
(DC Amps)
Qty X (current draw) = Total
=[0.207]
X [0.0659] =
1
[
]
[
]
[
]
[
]
[
]
[
]
[
]
Primary Alarm
Table 6.4 System Current Draw Calculations
Calculating the System Current Draw
Calculate Column 3
Secondary, Non-Alarm Current
(DC Amps)
Qty Excrement draw) = Total
=[0.206]
X [0.0659] =
X[
] =
X[
] =
X[
] =
X[
] =
X[
] =
[
X[
] =
[
X[
] =
[
3
=
Secondary Non-Alarm =
HPFF12 NAC Expander — P/N 53576:B 11/24/2010
= [0.075]
= 0.0
]
[
] =
]
[
] =
]
[
] =

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hpff12eHpff12cme