Honeywell HPFF12 Installation And Operation Manual page 14

Notification appliance circuit expander
Hide thumbs Also See for HPFF12:
Table of Contents

Advertisement

System Overview
End-of-line Resistor Reference – TB3 (on Control circuit board); terminals REF+ and REF–.
Used for the ELR compare feature.
Range: 1.9K ohms to 25K ohms.
12 AWG (3.31 mm²) to 22 AWG (0.326 mm²).
NAC Output Circuits — TB4 (on Control circuit board); terminals 1L1(+), 1L2(–), 2L1(+),
2L2(–), 3L1(+), 3L2(–), 4L1(+), and 4L2(–) — alarm polarity in parentheses. (See below for
other TB4 terminals.)
Supervised, special application, and power-limited.
Voltage rating: 24 VDC filtered.
Current:
– Maximum for any one circuit: 3.0 A.
– Maximum total continuous for all outputs: HPFF12, HPFF12CM, HPFF12E, HPFF12CME:
12.0 A
Output circuit types:
– four Class B (Style Y); or
– two Class A (Style Z);
– two Class B (Style Y) and one Class A (Style Z) NACs; or
– four Class A (Style Z) NACs with optional HPP31076 Class A adaptor.
12 AWG (3.31 mm²) to 18 AWG (0.75 mm²).
Refer to Appendix A, "Device Compatibility", on page 53 for listed compatible devices.
Trouble Contact Rating — TB2 (on Control circuit board); terminals TROUBLE: N/C,
COM, and N/O.
Not supervised.
Fail-safe Form-C relay.
Normally energized, transfers with NAC, battery, charger (in standby), AC loss, ground fault,
and auxiliary output trouble.
2.0 A @ 30 VDC.
AC loss trouble can be delayed for 2 hours (see "Programming Options").
12 AWG (3.31 mm²) to 18 AWG (0.75 mm²).
AC Fail Contact Rating — TB2 (on Control circuit board); terminals AC FAIL: N/C, COM,
N/O. (See above for other TB4 terminals.)
Not supervised.
Fail-safe Form-C relay.
Normally energized, always transfers with AC loss.
2.0 A @ 30 VDC.
12 AWG (3.31 mm²) to 18 AWG (0.75 mm²).
Battery Charging Circuit — TB1 (on Control circuit board); terminals +BATT and –BATT.
Supervised, non-power-limited.
Supports lead-acid type batteries only.
Float charge voltage: 26.6 VDC.
Charger disabled if battery voltage falls below 15 VDC.
Maximum charge current: 0.75 A.
Battery fuse (F1): 15 A, 32 V.
Maximum battery capacity: 26.0 AH.
Minimum battery capacity: 7.0 AH.
Power supply draws a maximum standby current of 75 mA from batteries.