Download  Print this page

2: Power-limited Wiring, Facp Cabinet - Honeywell HPFF12 Installation And Operation Manual

Notification appliance circuit expander.
Hide thumbs

Advertisement

Power-Limited Wiring Requirements
2.5.2 Power-Limited Wiring, FACP Cabinet
HPFF12CM(E) Power-Limited Wiring, EQBB-D4 Backbox
Relay Contacts:
Non-power-limited.
AC Power:
Non-power-limited.
(See Figure 2.19 for
wiring detail.)
Maintain 0.25" in. vertical
separation where
power-limited and
non-power-limited circuits
appear to "cross"
Battery connections:
Non-power-limited
Knockout for
Non-power-limited
wiring
NOTE:
Maintain 0.25" in. vertical separation where power-limited and non-power-limited circuits appear
to "cross" (e.g. Relay Contacts and AC Power, or HPP31076 NACs and battery connections).
Figure 2.18 Power-Limited Wiring Example: EQBB-D4 with HPFF12CM(E)
HPFF12 NAC Expander — P/N 53576:B 11/24/2010
SLC Loop:
Power-limited
Installation
Input Circuits:
Power-limited
Knockouts for
Power-limited wiring
Output circuits and
Auxiliary Output:
Power-limited
Knockout for
Power-limited wiring