Page 1
Air curtains: Windbox (M-ECM-G- ECG, SB-BB), Kool (M-ECM-G-ECG, SB-BB), Dam (M-ECM-G-ECG) INSTALLATION, OPERATION AND MAINTENANCE MANUAL Please, read these instructions carefully before attempting installation Deliver this manual to the final user. SECURITY ADVISE SYMBOLS Danger from electric current or high voltage! ¡Attention, Danger, Safety Advice!
15� The optimal working temperature of the fans is between 5ºC and 40ºC (41ºF to 104ºF) to protect the electrical components and at most should not exceed 50ºC (122ºF). SAVE THESE INSTRUCTIONS Instructions manual - Windbox, Kool and DAM air curtains...
INSTALLATION Tips and recomendations for a good installation LENGTH CENTERED / HEIGHT (*) Unless it has been de- signed to be installed at that height. DOOR DISTANCE Instructions manual - Windbox, Kool and DAM air curtains...
Page 6
AIR DISCHARGE AIR ASPIRATION MAINTENANCE ACCESSIBILITY CONTROL (CLEVER) Instructions manual - Windbox, Kool and DAM air curtains...
Page 7
In this case, dimension B will be 100 mm. The minimum recommended distance between the suction grille and any obstacle is 200 mm (Dimension C) Dimension D: service opening distance. Instructions manual - Windbox, Kool and DAM air curtains...
Page 8
H MAX. Maximum recommended range, MIN. Recommended minimum distance (*) The minimum recommended distance between the suction grille and any obstacle is 200 mm (Dimension C). Dimension D: service opening distance. Instructions manual - Windbox, Kool and DAM air curtains...
Page 9
In this case, dimension creases to 100 mm. (**) The minimum recommended dis- tance between the suction grille any obstacle is 200 mm (Dimension F) Dimension D: servi- ce opening distance. Instructions manual - Windbox, Kool and DAM air curtains...
Page 10
In this case, dimension B increases to 100 mm. (**) minimum recommended dis- tance between suction grille any obstacle is 200 (Dimension Dimension D: service opening distance. Instructions manual - Windbox, Kool and DAM air curtains...
Page 11
(*) Standard equipment. In case the tube outlet is lateral, the dimension is 100 mm. The minimum recommended distance between the suction grille and any obstacle is 200 mm for DAM cur- tains. (Dimensions A and C) Dimension D: service opening distance. Instructions manual - Windbox, Kool and DAM air curtains...
Page 12
(*) Standard equipment. In case the tube outlet is lateral, the dimension is 100 mm. The minimum recommended distance between the suction grille and any obstacle is 200 mm for DAM cur- tains. (Dimensions A and C) Dimension D: service opening distance. Instructions manual - Windbox, Kool and DAM air curtains...
The anchor must be sized according to the wei- ghts of each curtain indicated on the technical data page. The installation can be done using threaded rods, tensioners or other supports (see available supports in the accessories section). Instructions manual - Windbox, Kool and DAM air curtains...
In addition, it limits the heating based on the set temperature according to the room temperature (optionally also with the outside temperature) and the door status. A ‘Boost’ function is available when the door is open, which increases the heating to ensure comfort. Instructions manual - Windbox, Kool and DAM air curtains...
Page 17
- Water heated (ON/OFF): The user can select the valve’s on or off state (optional), depending on the confi gured ventilation speed and the door’s status. - Modulating heating: The user can select the heating stage based on the confi gured ventilation speed and the door’s status. Instructions manual - Windbox, Kool and DAM air curtains...
Page 18
ADVANCED PRO version: 01 version� Unit Working in P1� ADVANCED PRO subversion: 02 2 units connected to the control Scanning units� (last number shown during initiali- zation) Instructions manual - ADVANCED PRO Control Instructions manual - Windbox, Kool and DAM air curtains...
Page 19
For the door icons to appear, a door contact must be connected to the ‘PCB DIN1’ input and a door opening and closing cycle must be performed. Instructions manual - ADVANCED PRO Control Instructions manual - Windbox, Kool and DAM air curtains...
Page 20
For the door icons to appear, a door contact must be connected to the ‘PCB DIN1’ input and a door opening and closing cycle must be performed. Instructions manual - ADVANCED PRO Control Instructions manual - Windbox, Kool and DAM air curtains...
Page 21
For the door icons to appear, a door contact must be connected to the ‘PCB DIN1’ input and a door opening and closing cycle must be performed. Instructions manual - ADVANCED PRO Control Instructions manual - Windbox, Kool and DAM air curtains...
Page 22
Menu (to escape fast temperature outside (To validate) temperature setting) (**) Flashing ON (**) Only if an outside temperature sensor is installed on the air curtain PCB. Instructions manual - ADVANCED PRO Control Instructions manual - Windbox, Kool and DAM air curtains...
Page 23
To unlock the unit, the user must repeat the same combination of buttons as for locking. Then a higher-pitched beeping sound will be played, indicating that the control has been unlocked� Instructions manual - Windbox, Kool and DAM air curtains Instructions manual - ADVANCED PRO Control...
Page 24
Open door + Exterior temperature ≤ SET Temperature -7 *If you want to deactivate this function, set function 10 in the confi guration menu to 0°. Instructions manual - Windbox, Kool and DAM air curtains Instructions manual - ADVANCED PRO Control...
(*) By default, door open/close icons are not activated. First time the door contact is closed, then it is possible to choose door open heating/ventilation and door closed heating/ventilation. Instructions manual - Windbox, Kool and DAM air curtains Instructions manual - ADVANCED PRO Control...
On air curtains with water heating, it opens and closes the solenoid valve. It works with batteries or changes the stages on the modula- of type AAA / LR03. ting valve� Instructions manual - Windbox, Kool and DAM air curtains...
8� END LINE: When multiple air curtains are connected to one only control, the last PCB must incorporate a Jumper in “END LINE” pins. WIRING DIAGRAMS For the models Windbox, Kool and Dam, the following wiring diagrams are enclosed: • Air curtain with water coil or only air (AIRDOE09080) •...
Page 28
CONTROLADOR 5 VELOCIDADES CORTINA AIRE / AGUA CON ADDONS ONLY AIR / WATER WITH ADDONS CONTROLLER 5 SPEEDS In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached Instructions manual - Windbox, Kool and DAM air curtains...
Page 29
CONTROLADOR 5 VELOCIDADES CORTINA ELÉCTRICA CON ADDON E Y PRBEO <27 kW 5 SPEEDS ELECTRICAL CONTROLLER WITH ADDON E & PRBEO <27 kW In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached Instructions manual - Windbox, Kool and DAM air curtains...
Page 30
CONTROLADOR 5 VELOCIDADES ELÉCTRICO 400V~3 30 kW G, ECG 2000-2500-3000 ELECTRICAL CONTROLLER 5 SPEEDS 400V~3 30 kW G 2000-2500-3000 In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached Instructions manual - Windbox, Kool and DAM air curtains...
Page 31
Electrical heated air curtain for BB 1000 and 1500 (AIRDOE09XXX) Instructions manual - Windbox, Kool and DAM air curtains...
Page 32
Electrical heated air curtain for BB 2000-3000, B 2500 models (AIRDOE09XXX) Instructions manual - Windbox, Kool and DAM air curtains...
[**] Customizable dimensions on request WINDBOX air curtains range provide equipment suitable for all types of commercial entrances. A compact and robust air curtain from our standard range with a timeless design, ready for visible installation over the door and prepared for multiple false ceiling installation configurations.
Page 34
Water heated: connection pipes P86 and P64 are 2x3/4” female (male if lateral pipes), P54 2x1” male. P86 2 rows coil, P64 3 rows coil, P54 4 rows coil. Selection program Instructions manual - Windbox, Kool and DAM air curtains...
Page 35
1420 2000 1920 2500 2420 1210 3000 2920 1460 Foot Customizable dimensions on request. Inside ceiling surface mounting False ceiling invisible mounting CAD drawings, BIM files, installation manuals and other documentation Instructions manual - Windbox, Kool and DAM air curtains...
Included Sensors and valves Condensation Solenoid valve Valve 3 ways Proportional valve Anti-freezing sensor Magnetic Mechanical External Temperature Condensation tray V-ACT AFS-INS door contact MAG-DC door contact MEC-DC Sensor Included Instructions manual - Windbox, Kool and DAM air curtains...
Page 37
2700 0,213 1,86 DAM ECG 1500 A 3600 0,284 2,48 DAM ECG 2000 A 5400 0,426 3,72 DAM ECG 2500 A 6300 0,497 4,34 DAM ECG 3000 A 7200 0,568 5,96 Instructions manual - Windbox, Kool and DAM air curtains...
Page 38
Water heated: connection pipes P86 and P64 are 2x3/4” female (male if lateral pipes), P54 2x1” male. P86 2 rows coil, P64 3 rows coil, P54 4 rows coil. Selection program Instructions manual - Windbox, Kool and DAM air curtains...
Page 39
4/6 x M8 1000 1500 1420 2000 1920 2500 2420 1210 Customizable 3000 2920 1460 dimensions on request. Vertical installation 10 x Ø12 CAD drawings, BIM files, installation manuals and other documentation Foot Instructions manual - Windbox, Kool and DAM air curtains...
Included Sensors and valves Condensation Magnetic Mechanical External Temperature Solenoid valve Valve 3 ways Proportional valve Anti-freezing sensor Condensation tray V-ACT AFS-INS door contact MAG-DC door contact MEC-DC Sensor Included Instructions manual - Windbox, Kool and DAM air curtains...
Page 41
KECG 1000 A 2700 0,213 1,86 KECG 1500 A 3600 0,284 2,48 KECG 2000 A 5400 0,426 3,72 KECG 2500 A 6300 0,497 4,34 KECG 3000 A 7200 0,568 5,96 Selection program Instructions manual - Windbox, Kool and DAM air curtains...
Page 42
CLEVER PRO Included Included Included Sensors CAD drawings, BIM files, installation manuals and other documentation Mechanical door contact Magnetic door contact External Temperature MEC-DC MAG-DC Sensor Included Instructions manual - Windbox, Kool and DAM air curtains...
Page 43
[**] Customizable dimensions on request Commercial size air curtain with an equivalent power to an industrial unit. As all the standard range of Airtècnics air curtains, WINDBOX SB-BB has an elegant and timeless design. A highly versatile air curtain provided with a wide variety of technical specifications, mounting options and customization, gathering all the latest innovations and developments.
Page 44
P86, P64 2x1”, P54 1000-2000 2x1” and 2500-3000 2x1¼”. Connection pipes P86, P64 and P54 are male. P86 2 rows coil, P64 3 rows coil, P54 4 rows coil. Selection program Instructions manual - Windbox, Kool and DAM air curtains...
Page 45
1420 2000 1920 2500 2420 1210 3000 2920 1460 Customizable dimensions on request. Foot Inside ceiling surface mounting False ceiling invisible mounting CAD drawings, BIM files, installation manuals and other documentation Instructions manual - Windbox, Kool and DAM air curtains...
Page 46
Included Sensors and valves Condensation Valve 3 ways Proportional valve Magnetic Mechanical External Temperature Solenoid valve Anti-freezing sensor Condensation tray V-ACT AFS-INS door contact MAG-DC door contact MEC-DC Sensor Included Instructions manual - Windbox, Kool and DAM air curtains...
Page 47
[*] Consult separate DX catalogs RECESSED WINDBOX SB-BB is a high pressure compact and robust air curtain from our standard range with a timeless design, for recessed installation in false ceilings. It is a suitable air curtain for all types of commercial and industrial entrances.
Page 48
P86, P64 2x1”, P54 1000-2000 2x1” and 2500 2x1¼”. Connection pipes P86, P64 and P54 are male. P86 2 rows coil, P64 3 rows coil, P54 4 rows coil. Selection program Instructions manual - Windbox, Kool and DAM air curtains...
Page 49
Included Sensors and valves Condensation External Temperature Solenoid valve Magnetic Mechanical Valve 3 ways Proportional valve Condensation tray Anti-freezing sensor door contact MAG-DC door contact MEC-DC Sensor V-ACT AFS-INS Included Instructions manual - Windbox, Kool and DAM air curtains...
Page 50
KBB 1000 A 4020 0,873 3,87 KBB 1500 A 5360 1,164 5,16 KBB 2000 A 8040 1,746 7,74 KBB 2500 A 9380 2,037 9,03 KBB 3000 A 10720 2,328 10,32 Selection program Instructions manual - Windbox, Kool and DAM air curtains...
Page 51
CLEVER PRO Included Included Included Sensors CAD drawings, BIM files, installation manuals and other documentation Mechanical door contact Magnetical door contact External Temperature MEC-DC MAG-DC Sensor Included Instructions manual - Windbox, Kool and DAM air curtains...
110% and 85% of the value indicated on the label. Check that all fans blow air. Keep the curtain at full speed for a few minutes and listen for abnormal noises from the curtain� Instructions manual - Windbox, Kool and DAM air curtains...
Page 54
Check the inlets and outlets of the water tubes to ensure that there are no fl uid leaks. If a water leak has been detected in the battery, possible corrosion problems in both the battery and the cur- tain components should be checked. Instructions manual - Windbox, Kool and DAM air curtains...
• Use only original spare parts. For manipulation safety, being it assembling, transport or maintenance duties it’s a must to wear the correct individual protection equipment recommended. Those being gloves, insulating shoes, googles and helmet. Instructions manual - Windbox, Kool and DAM air curtains...
Page 57
EC centrifugal fan for B G9GDS 146x188L Y02-D5 B: All models AIRSEC50190 EC centrifugal fan for BB GDSV8 160X198L Q39-B0-1 BB: All models ADVANCED PRO Control ELACCO33005 CON-LCD-RJ11 All models RJ11 Instructions manual - Windbox, Kool and DAM air curtains...
Page 58
Dam model Follow the same instructions as for the Windbox curtain with plenum or suction and discharge kit. Instructions manual - Windbox, Kool and DAM air curtains...
In some cases, it is recommended to unscrew the PCB� Power board change: open the service door and unscrew the power board from the inside of the air curtain to remove the plate and carry out the necessary repair. Instructions manual - Windbox, Kool and DAM air curtains...
Before removing the screws that secure the battery: To remove the battery, unscrew the fixing screws as shown on the next page: Instructions manual - Windbox, Kool and DAM air curtains...
Page 61
Water and electric coil fixing points: door closing angle and interior angles. inside the air curtain� Air curtain size Nº angle fixing points 1000 1500 2000 2500 3000 4 - 5 Instructions manual - Windbox, Kool and DAM air curtains...
The heating is blocked and switched Flashing ON off . It is the overheating safety program. Service must check the unit and fi x the problem to avoid internal damages. Once solved, reset the unit� Instructions manual - Windbox, Kool and DAM air curtains...
Page 63
Fire Alarm (A6) Stops and locks the unit. To unlock it, the power supply must be switched off . It is activated with DIN3 digital IN on the con- trol unit� Instructions manual - Windbox, Kool and DAM air curtains...
Some fan has stopped. Check the unit. Unit operation remains normal. Not available in 2-speed range. External Alarm (E5) Indicates an external alarm. Unit operation remains normal. Only programmable with CLEVER PRO control (consult CLEVER PRO Manual). Instructions manual - Windbox, Kool and DAM air curtains...
Smart, Dam, Recessed Dam, Deco, Kool, Rund, Invisair, Rotowind, Variwind, Zen, Max, Maxwell, Compact Fly, Fly K, Fly KL-KXL, Fly KBB, Windbox BB, Recessed Windbox BB, Zen BB, Invisair BB, Kool BB, Rotowind BB, Zen L-XL, Windbox L-XL, Duojet, Triojet System is/are developed, designed and manufactured in accordance with the following directive(s) ha(n) sido desarrollado(s), diseñado(s) y fabricado(s) de acuerdo con la(s) siguiente(s) directiva(s)
Page 66
Windbox, Recessed Windbox, Smart, Dam, Recessed Dam, Deco, Kool, Rund, Invisair, Rotowind, Variwind, Zen, Max, Maxwell, Compact Fly, Fly K, Fly KL-KXL, Fly KBB, Windbox BB, Recessed Windbox BB, Zen BB, Windbox L-XL, Duojet, Triojet System. is/are developed, designed and manufactured in accordance with the following regulation(s) Electrical Equipment (Safety) Regulations 2016 No.
If you detect some error in this manual, we’ll be pleased to receive your feedback, it helps us to improve even more. Airtècnics reserves the right to modify some of the specifi cations in this manual Instructions manual - Windbox, Kool and DAM air curtains...