Air curtain: Optima INSTALLATION, OPERATION AND MAINTENANCE MANUAL Please, read these instructions carefully before attempting installation SAFETY WARNING SYMBOLS Danger from electric current or high voltage! ¡Attention, Danger, Safety Advice! Injuries risk! Danger! Do not stay underneath: Heavy load. Important information.
15� The optimal working temperature of the fans is between 5ºC and 40ºC (41ºF to 104ºF) to protect the electrical components and at most should not exceed 50ºC (122ºF). SAVE THESE INSTRUCTIONS Instructions manual - Air curtain Optima...
INSTALLATION Tips and recomendations for a good installation LENGTH CENTERED / HEIGHT (*) Unless it has been de- signed to be installed at that height. DOOR DISTANCE Instructions manual - Air curtain Optima...
Page 6
AIR DISCHARGE AIR ASPIRATION MAINTENANCE ACCESSIBILITY CONTROL (CLEVER) Instructions manual - Air curtain Optima...
Page 7
H MAX. Maximum recommended range, MIN. Recommended minimum distance. The minimum recommended distance between the suction grille and any obstacle is 200 mm (Dimension C) Dimension D: service opening distance. Instructions manual - Air curtain Optima...
The installation can be done using threaded rods, tensioners or other sup- ports (see available supports in the accessories section). Air Curtain Instructions manual - Air curtain Optima...
During the first uses, the electric battery can give off some odor that disappears in a few days. According to battery power, the regulation is carried out by: Size of the air curtain Heater power (kW) Regulation type 1000 / 1500 6 / 9 1 PRBEO 2000 2 PRBEO Instructions manual - Air curtain Optima...
In addition, it allows to select different speeds and heating stages depending on the state of the door. It has a “Boost” function that to ensure comfort, increases the heating when the door is open. Instructions manual - Air curtain Optima...
Page 13
- Water heated: a single stage (ON/OFF) can be selected depending on open and closed door. If it has a proportional valve it can be regulated on 3 stages. Instructions manual - Air curtain Optima...
Example: Space between version and subver- ADVANCED PRO version: 01 sion� Unit Working in P1� ADVANCED PRO subversion: 02 2 units connected to the control Scanning units� (last number shown during initializa- tion) Instructions manual - Air curtain Optima...
Page 15
(To validate) CLOSED DOOR (*) Flashing ON (*) If the door contact is not detected, the door open and door closed icons will not appear. Only one speed and one heating will be available� Instructions manual - Air curtain Optima...
Page 16
(To validate) CLOSED DOOR (*) Flashing ON (*) If the door contact is not detected, the door open and door closed icons will not appear. Only one speed and one heating will be available� Instructions manual - Air curtain Optima...
Page 17
Menu (To validate) (To validate) Flashing ON (*) If the door contact is not detected, the door open and door closed icons will not appear. Only one speed and one heating will be available� Instructions manual - Air curtain Optima...
Page 18
(power supply fail). Information of the Menu Menu (to escape fast temperature outside (To validate) temperature setting) (**) Flashing ON (**) Only if an outside temperature sensor is installed on the air curtain PCB. Instructions manual - Air curtain Optima...
Flashing ON To unlock the unit, the user must repeat the same combination of buttons as for locking. Then it will be hear a higher-pitched beeping sound, indicating that the control has been unlocked. Instructions manual - Air curtain Optima...
In this menu is possible to modify operation parameters of the air curtain like the door delay, the max speed and max heating with open or closed door, the frecuency of filter maintenance, temperature units system used, memory or setting the boost mode. Instructions manual - Air curtain Optima...
Page 21
SET temperature, fan can be set to continue ON and be ready for when the door is opened again, as an immediate protection. If function is set to OFF, the air curtain will stop if the same conditions are met. Instructions manual - Air curtain Optima...
In air curtains with electrical heating, it modifi es the power of the heating. On air curtains with water heating, it opens and closes the solenoid valve. It works with batteries of type AAA / LR03. Instructions manual - Air curtain Optima...
2 Velocidades 1000 / 1500 / 2000. Batería Agua / aire 2-Speed 1000 / 1500 / 2000. Water Heater & Only Air In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached. Instructions manual - Air curtain Optima...
Page 24
2 Velocidades 1000 6kW / 1500 6kW / 1500 9kW. Batería Eléctrica 400x3 2-Speed 1000 6kW / 1500 6kW / 1500 9kW. Electrical Heater 400x3 In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached. Instructions manual - Air curtain Optima...
Page 25
WIRING DIAGRAM OF AIR CURTAIN 2-SPEED CONTROLLER RJ11 ADVANCED PRO 2 Velocidades 1000 9kW. Batería Eléctrica 400x3 2-Speed 1000 9kW. Electrical Heater 400x3 In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached. Instructions manual - Air curtain Optima...
Page 26
WIRING DIAGRAM OF AIR CURTAIN 2-SPEED CONTROLLER RJ11 ADVANCED PRO 2 Velocidades 2000 12kW. Batería Eléctrica 400x3 2-Speed 2000 12kW. Electrical Heater 400x3 In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached. Instructions manual - Air curtain Optima...
Page 27
2 Velocidades 1000 6kW / 1500 6kW . Batería Eléctrica 230x1 2-Speed 1000 6kW / 1500 6kW . Electrical Heater 230x1 In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached. Instructions manual - Air curtain Optima...
Page 28
WIRING DIAGRAM OF AIR CURTAIN 2-SPEED CONTROLLER RJ11 ADVANCED PRO 2 Velocidades 1500 9kW. Batería Eléctrica 230x1 2-Speed 1500 9kW. Electrical Heater 230x1 In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached. Instructions manual - Air curtain Optima...
Page 29
WIRING DIAGRAM OF AIR CURTAIN 2-SPEED CONTROLLER RJ11 ADVANCED PRO 2 Velocidades 2000 12kW. Batería Eléctrica 230x1 2-Speed 2000 12kW. Electrical Heater 230x1 In case there is a need to connect the curtain to a PLC, the corresponding diagram is attached. Instructions manual - Air curtain Optima...
OPTIMA air curtain is ideal for most of the commercial entrances up to 2,8 meters high. A small and compact air curtain of friendly design with rounded shape and edges. It incorporates tangential fans with low noise twisted profile turbine and 2-speed external rotor motor.
Make sure that the board and internal wiring connectors are still well connected. Check that the motors do not move from their mountings and check that the turbines have no impediments to rotate freely (turn it by hand, first turn off the device). Instructions manual - Air curtain Optima...
Page 34
Check the inlets and outlets of the water tubes to ensure that there are no fluid leaks. If a water leak has been detected in the battery, possible corrosion problems in both the battery and the air curtain components should be checked. Instructions manual - Air curtain Optima...
(4 screws) and remove the motor from the air curtain. Finally, install the new motor and close the air curtain doing the process in reverse order. Turbine security screw Instructions manual - Air curtain Optima...
Page 38
Recommendation: installation with silentblocks To reduce the sound level and the vibrations of the air curtain, it is recommended to carry out an installation with silentblocks: Instructions manual - Air curtain Optima...
Page 39
3. Remove the lateral panels of the air curtain. 4.Remove the suction grille, unscrew the screws that hold it to the air curtain housing. 5� Unscrew the screws that hold the water battery� 6. Remove the battery from the air curtain housing. Instructions manual - Air curtain Optima...
Page 40
(see table at the bottom of the page to count the screws to be removed), disconnect the PRBEO cables from both parts of the battery and remove the battery with both hands. Air curtain size Nº battery fixing screws 1000 1500 2000 Instructions manual - Air curtain Optima...
The heating is blocked and switched Flashing ON off. It is the overheating safety program. Service must check the unit and fix the problem to avoid internal damages. Once solved, reset the unit� Instructions manual - Air curtain Optima...
Page 42
Fire Alarm (A6) Stops and locks the unit. To unlock it, the power supply must be switched off. It is activated with DIN3 digital IN on the con- trol unit� Instructions manual - Air curtain Optima...
Some fan has stopped. Check the unit. Unit operation remains normal. Not available in 2-speed range. External Alarm (E5) Indicates an external alarm. Unit operation remains normal. Only programmable with CLEVER PRO control (consult CLEVER PRO Manual). Instructions manual - Air curtain Optima...
If you detect some error in this manual, we’ll be pleased to receive your feedback, it helps us to improve even more. Airtècnics reserves the right to modify some of the specifi cations in this manual Instructions manual - Air curtain Optima...