Wired Controller
Installation and Operation Manual
GACT17B
Table of Contents
Parts and Functions
Interface Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Icons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Dip Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Operation
Mode Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fan Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Temperature Adjustment Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Special Function
Special Function Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installer Settings
Adjust ECO Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Child Lock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Lock Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Fahrenheit / Celsius. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Temperature Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Forced Defrost/Cooling/Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Error Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Mode Restriction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Mode Combination Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Wired Controller Wiring Instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
• Please read this manual before use
• Please keep this manual for future reference.
GE is a trademark of the General Electric Company. Manufactured under trademark license.
1
49-5001091 Rev. 1
03-25

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GACT17B and is the answer not in the manual?

Questions and answers

Summary of Contents for GE GACT17B

  • Page 1 Wired Controller Wiring Instruction ......16 • Please read this manual before use • Please keep this manual for future reference. GE is a trademark of the General Electric Company. Manufactured under trademark license. 49-5001091 Rev. 1 03-25...
  • Page 2: Parts And Functions

    Parts and Functions Interface Display MAIN Full Display...
  • Page 3 Parts and Functions Icons Room temperature display ( dip switch SW1- 2 on). Set temperature display Filter HRV (Heat Reclaim Ventilation), if HRV function is set, it will display this icon Error icon displays detected fault ECO mode on Central/lock when connected to a central controller UP/DOWN louver swing LEFT/RIGHT louver swing...
  • Page 4 Parts And Functions Main / Subordinate wired MAIN / SUB controller Quiet Fan Speed (some models) Low Fan Speed Medium Fan Speed High Fan Speed Turbo Fan Speed (some models) Auto Fan speed is indicated by the display automatically stepping from low to high repeatedly. Auto Mode Cooling Mode Heating Mode...
  • Page 5: Dip Switch

    Dip Switch Dip Switch SW1 Default Sw1-1 Subordinate wired Main wired controller controller Room temperature Sw1-2 Room temperature display on Sw1-3 Room temperature Room temperature collected from indoor unit collected from controller Auto restart after power Sw1-4 power loss loss Old protocol (models Sw1-5 New protocol...
  • Page 6: Audible Alert

    Dip Switch Dip Switch SW2 Default Sw2-1 Mode Lock Normal Sw2-2 still sound when command is sent by Tone on wireless remote. Sw2-3 following backlight when ton light, turned on always on when turned on Sw2-4 Reserved Reserved Initialization tween the Room Temperature display and the Set Temperature display until communication is established with the indoor unit.
  • Page 7 Mode Key / Fan Key Mode key: • Each press of the MODE button will change the operating – Auto … • Each mode has its initial default fan speed. Mode Fan speed Temperature Auto Auto 76°F Cool High 76°F Initial Heat 76°F...
  • Page 8 Temperature Temperature Adjustment Keys: • Press the TEMP+ or TEMP- keys to change the temperature by 1°F increments. • The temperature set point range for Auto, Cooling, Heating then temperature range will change per the ECO setting parameters). • The temperature is set independently under Auto, Cooling, Heating and Dehumidify modes.
  • Page 9: Function Selection

    Function Selection Special Function Selection: With the control powered on, press and hold the TEMP+ for 5 seconds to enter the special function menu. All the special function icons will display. Use the TEMP+ and TEMP- buttons to move between icons. Use FAN button to select function.
  • Page 10 Function Selection Self-Cleaning (Some models)
  • Page 11: Installer Settings

    Installer Settings Adjust ECO Parameters: • Cooling: Power on the unit. Adjust set temperature to 86°F. Press and hold FAN and TEMP+ for 5 seconds. The minimum allowable set temperature will be displayed in the top right corner. Use TEMP+/- to change the parameter, then press FAN save.
  • Page 12 Lock Settings / Fahrenheit Setting Central/Lock Function: This function requires the addition of a Central Controller. When the Central Controller is added to the system, the wired controller will have either limited functionality or no functionality. Limited Control temperature functions available. Central Lock No functions available.
  • Page 13: Temperature Compensation

    Temperature Compensation Set Temperature Compensation: The display will then show 00 (default) or current compensation setting. Use TEMP+/- buttons to adjust the compensation. Compen- sation can be set in 1°F increments up to +/- 8°F (0.5°C increments up to +/-4°C). •...
  • Page 14: Error Checks

    Error Checks How to check error: • If there is an error, will display. • Check error: Press and hold TEMP- button for 5 seconds. The error history will appear in the top right corner. The indoor unit number will appear in the middle of the screen.
  • Page 15 Static Pressure (Ducted Indoor Units Only) for 10 seconds. The static pressure will appear in the middle of the screen. Use TEMP+/- buttons to adjust the static pres- • The indoor address will appear in the top right corner. There is nothing displayed when there is no indoor address.
  • Page 16 Checking Parameters (only applies to some models): • Press and hold TEMP+ for 10 seconds to check the parameters. The parameters will appear in the middle of the screen to show indoor address, Letters will appear after decimal display (AbCdEF). The detailed parameters will show on the top right corner.
  • Page 17 Wired Controller Wiring Instruction The wired controller supports two communication methods. 1. ABC communication:Adapt to models that support ABC communication. Use the wiring harness in the attachment to connect the ABC terminal of the indoor unit. If an external length is required, please note that the wire sequence needs to correspond to ABC, otherwise communication will not be possible.
  • Page 18 Wired Controller Wiring Instruction ABC Wiring Connections One controller controls multiple indoor units (up to 16) 1. Connecting to indoor units that do not require WK/B adapter (Please refer to indoor unit submittal to see if WK/B is required.) Indoor N Indoor 15 Indoor 16 Indoor 2...
  • Page 19 Wired Controller Wiring Instruction ABC Wiring Connections 2. Connecting to indoor unit that requires WK/B adapter (Please refer to indoor unit submittal to see if WK/B is required). High Wall ..Unit 1 Unit 0 Unit 15 WK-B (main unit) A B C A B C A B C...
  • Page 20: Communication Wiring

    Wired Controller Wiring Instruction Communication Wiring Wire Size Communication wiring length (m/ft) 22 AWG Stranded, 3 Wire < 100m/328ft (0.3mm x3 wire) 20 AWG Stranded, 3 Wire (0.5mm x3 wire) 18 AWG Stranded, 3 Wire (0.75mm x3 wire) 16 AWG Stranded, 3 Wire (1.25mm x3 wire) 14 AWG Stranded, 3 Wire...
  • Page 21 Wired Controller Wiring Instruction XY Wiring Connections (R454b indoor) Figure A : Figure B : One controller controls multiple One controller indoor units (up to 16) controls one indoor unit. Indoor 16 Indoor 15 Indoor N Indoor 2 Indoor 1 ……...
  • Page 22 Wired Controller Wiring Instruction XY Communication Wiring (Does not ship with unit; supplied by installer) Communication wiring length Dimensions of wiring <=250m 18/2 AWG Shielded SOOW NOTE: One side of the shielded layer of Communication wire must be grounded.
  • Page 23: Installation Diagrams

    Wired Controller Wiring Instruction Installation Diagrams 1. To take the front panel and back panel apart, slide the front panel up and press down on the back panel. 2. Secure the back panel to the wall using screws. 3. Connect the control wires. 4.
  • Page 24: Can Ices3(B)/Nmb3(B)

    Increase the separation between the equipment and receiver. from that to which the receiver is connected. —Consult the dealer or an experienced radio/TV technician for help. CAN ICES3(B)/NMB3(B) MANUFACTURER GE Appliances, a Haier Company Appliance Park Louisville, KY 40225 WEBSITE www.Haierductless.com...
  • Page 25 GACT17B Table des matières Composants et fonctions ........1 .
  • Page 26 MAIN...
  • Page 27 Filtre...
  • Page 29: Commutateur Dip

    Commutateur DIP Commutateur DIP SW1 Sw1-1 Sw1-2 Sw1-3 Sw1-4 Sw1-5 Sw1-6 Sw1-7 Sw1-8...
  • Page 30 Commutateur DIP Commutateur DIP SW2 Sw2-1 Normal Sw2-2 Sw2-3 Sw2-4 Alerte audible...
  • Page 31 Touche Mode: • Auto Auto État Auto Touche Ventilateur:...
  • Page 32 Touches de réglage de température...
  • Page 34 tialiser. Self-Cleaning...
  • Page 35 Réglage des paramètres ECO • Verrouillage pour enfants : •...
  • Page 36 Fonction Centrale/Verrouillage...
  • Page 37 Compensation de température réglée: Dégivrage forcé (Certains modèles): Climatisation forcée (Certains modèles) : (Certains modèles) :...
  • Page 38 Remarque : GEAppliancesAirandWater.com Codes d’erreur du capteur de fuite de réfrigérant...
  • Page 39 • Fonction de verrouillage de mode :...
  • Page 40 Demande de Paramètre: Réglage de la combinaison de modes: •...
  • Page 41 A B C Polar wire A B C A B C A B C A B C...
  • Page 42 A B C A B C A B C A B C A B C A B C • • • • • • • •...
  • Page 43 High Wall ..Unit 1 Unit 0 Unit 15 WK-B (main unit) A B C A B C A B C W ired controller CN1 ou CN2.
  • Page 44 REMARQUE :...
  • Page 45 Indoor 16 Indoor 15 Indoor N Indoor 2 Indoor 1 …… …… Indoor Wired controller REMARQUE : Wired controller...
  • Page 46 <=250m REMARQUE : terre.
  • Page 48 REMARQUE : FABRICANT a Haier Company SITE WEB...
  • Page 49: Table Of Contents

    Manual de Instalación y Funcionamiento GACT17B Índice Piezas y Funciones Pantalla de Interfaz ......... . .1 Íconos .
  • Page 50: Piezas Y Funciones

    Piezas y Funciones Pantalla de Interfaz MAIN Pantalla Completa...
  • Page 51: Íconos

    Piezas y Funciones Íconos (interruptor DIP SW1-2 encendido). Filtro falla ECO mode on conectado a un controlador central. Bloqueo para niños...
  • Page 52 Piezas y Funciones Velocidad de Ventilación Velocidad de Ventilación Baja Velocidad de Ventilación Media Velocidad de Ventilación Alta Velocidad de Ventilación repetida. Modo Automático Modo de Calefacción Modo de Ventilación Modo de Deco...
  • Page 53: Interruptor Dip

    Interruptor DIP ENCENDIDO APAGADO Omisión APAGADO Sw1-1 principal Pantalla de temperatura Sw1-2 Pantalla de temperatura APAGADO Sw1-3 recolectada de la unidad recolectada del interior controlador Sw1-4 El sistema permanece APAGADO Sw1-5 Nuevo protocolo APAGADO elos desarrollados antes APAGADO Sw1-6 encendida Sw1-7 APAGADO izquierda/ derecha...
  • Page 54: Alerta Sonora

    Dip Switch ENCENDIDO APAGADO Omisión Sw2-1 Bloqueo del Modo Normal APAGADO mación. (El tono aún sonará Sw2-2 Tono activado APAGADO cuando el comando sea enviado sistema Sw2-3 APAGADO trasera cuando se enciende pre encendido cuando se activa Sw2-4 APAGADO Inicio cación con la unidad interna.
  • Page 55: Funcionamiento Tecla De Modo

    Tecla de Modo / Tecla del Ventilador • Cada modo cuenta con su velocidad de ventilación inicial. Modo Velocidad del ventilador Temperatura Automático Automático 76°F Alta 76°F Estado Calor Bajo 76°F Inicial Ventilador Bajo Sin pantalla de temperatura Automático 76°F Velocidad de Ventilación Velocidad de Ventilación Baja Velocidad de Ventilación...
  • Page 56: Teclas De Ajuste De Temperatura

    Temperatura por incrementos de 1°F.
  • Page 57: Selección De Funciones

    Selección de Funciones para seleccionar la función.
  • Page 58 Selección de Funciones de TEMP (Temperatura) para seleccionar la posición de ones de TEMP (Temperatura) para seleccionar la posición dor para reiniciar. Calor). (Versión futura) en el modo Heat (Calor) a 50°F. Usado para el modo de vacaciones. tal en la posición superior. Comúnmente usada durante la en la posición inferior.
  • Page 59: Parámetros De Ajuste Eco

    temperatura máxima permitida aparecerá en la esquina superior • controlada por la unidad interior. Bloqueo para Niños: •...
  • Page 60: Fahrenheit / Celsius

    Esta función requiere la adición de un Controlador Central. Cuando se una funcionalidad limitada o no tendrá funcionalidad. Bloqueo Central pantalla pasará a Celsius. Fahrenheit.
  • Page 61: Compensación De Temperatura

    Compensación de Temperatura a encenderlo. a encenderlo.
  • Page 62: Controles De Errores

    Controles de Errores • Si se produce un error El número de la unidad interior aparecerá en el medio de la pantalla. El medio dispersado.
  • Page 63: Presión Estática

    Presión Estática (Unidades Interiores Con Conducto Únicamente) consulte el manual de instalación de la unidad interior. •...
  • Page 64 de la pantalla para mostrar el manejo interno. Aparecerán letras unidades internas conectadas. Monitor Descripción Valor Temperatura °F (°C) Sensor de interior - Vapor (Tc1) Temperatura °F (°C) Temperatura °F (°C) Posición interior EEV Dirección de la unidad interior Se muestra en hexadecimal Dirección central de la unidad interior Se muestra en hexadecimal •...
  • Page 65 1. Comunicación ABC: Se adapta a modelos que soportan la conectar la terminal ABC a la unidad interior. Si se requiere una interior. A: Un controlador controla una unidad interior Por favor consulte la presentación de la unidad interior para ve- (número de modelo: WK/B).
  • Page 66 Un controlador controla múltiples unidades interiores (hasta 16). 1. Conexión a unidades interiores que no requieren un adaptador WK/B (Por un WK/B). Indoor N Indoor 15 Indoor 16 Indoor 2 Indoor 1 (main unit) Wired controller Wired controller Wired controller Wired controller Wired controller A B C...
  • Page 67 2. Conexión a una unidad interior que requiere un adaptador WK/B (Por favor WK/B). High Wall ..Unit 1 Unit 0 Unit 15 WK-B (main unit) A B C A B C A B C W ired controller Dipswitch position Dipswitch position pared alta para conectar con el WK-B es considerada la unidad...
  • Page 68 comunicación (m/ pies) < 100m/328ft (0.3mm (0.5mm (0.75mm (1.25mm (2mm yellow white...
  • Page 69 controlador con- unidades interiores (hasta 16) trola una unidad interior. Indoor 16 Indoor 15 Indoor N Indoor 2 Indoor 1 …… …… Indoor Wired controller Wired controller cualquier unidad interior. interiores. puede controlar hasta 16 unidades interiores. Todas las unidades interiores secundaria del sistema.
  • Page 70 <=250m con conexión a tierra.
  • Page 71 1. Para separar el panel frontal del panel el panel trasero. usando tornillos.
  • Page 72 interferencias perjudiciales en la instalación residencial. Este que no se presenten interferencias en una instalación en particular. Si este equipo provoca interferencias perjudiciales un circuito diferente del tomacorriente al que se encuentra CAN ICES3(B)/NMB3(B) a Haier Company www.Haierductless.com...