Siemens SITRANS L Operating Instructions Manual
Siemens SITRANS L Operating Instructions Manual

Siemens SITRANS L Operating Instructions Manual

Radar transmitters, with ma/hart
Hide thumbs Also See for SITRANS L:
Table of Contents

Advertisement

Quick Links

SITRANS L
Radar transmitters
SITRANS LR560 with mA/HART
Operating Instructions
08/2019
A5E34647946-AF
Introduction
Safety notes
Description
Installing/mounting
Connecting
Commissioning
Operating
Parameter Reference
Service and maintenance
Diagnosing and
troubleshooting
Technical data
Dimension drawings
Technical reference
HART communications
Certificates and Support
HMI menu structure
List of abbreviations
1
2
3
4
5
6
7
8
9
10
11
12
A
B
C
D
E

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SITRANS L and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Siemens SITRANS L

  • Page 1 Introduction Safety notes Description SITRANS L Installing/mounting Radar transmitters SITRANS LR560 with mA/HART Connecting Commissioning Operating Instructions Operating Parameter Reference Service and maintenance Diagnosing and troubleshooting Technical data Dimension drawings Technical reference HART communications Certificates and Support HMI menu structure...
  • Page 2: Qualified Personnel

    Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Table of contents Introduction .............................. 10 Purpose of this documentation ....................10 Security information ........................ 10 Checking the consignment ..................... 11 Transportation and storage ..................... 11 Notes on warranty ........................11 Firmware revision history ......................12 Safety notes ............................. 13 Preconditions for use ......................
  • Page 4 Table of contents Connecting SITRANS LR560 ....................30 Basic PLC/mA configuration with HART ................31 Nameplates for hazardous area installations ................. 32 5.4.1 FM/CSA Class 1, Div 2 installation and connection drawing ..........32 Instructions specific to hazardous area installations.............. 33 5.5.1 (Reference European ATEX Directive 2014/34/EU, Annex II, 1.0.6) ........
  • Page 5 Table of contents 8.1.4 COPY PARAMETERS TO DISPLAY (1.3.) ................97 8.1.5 COPY PARAMETERS FROM DISPLAY (1.4.) ..............97 8.1.6 COPY FIRMWARE TO DISPLAY (1.5.) ................. 98 8.1.7 COPY FIRMWARE FROM DISPLAY (1.6.) ................98 SETUP (2.) ..........................99 8.2.1 DEVICE (2.1.) .........................
  • Page 6 Table of contents 8.2.7.9 FILTERING (2.7.5.) ......................112 8.2.7.10 ECHO QUALITY (2.7.6.) ...................... 112 8.2.8 TVT SETUP (2.8.) ........................ 113 8.2.8.1 AUTO FALSE ECHO SUPPRESSION (2.8.1) ..............113 8.2.8.2 AUTO FALSE ECHO SUPPRESSION RANGE (2.8.2) ............113 8.2.8.3 HOVER LEVEL (2.8.3) ......................113 8.2.8.4 SHAPER MODE (2.8.4) .......................
  • Page 7 Table of contents 8.4.4 POWERON RESETS (4.4.) ....................123 8.4.5 LCD BACKLIGHT (4.5.) ......................124 8.4.6 LCD CONTRAST (4.6.)......................124 8.4.7 SERVICE SCHEDULE (4.7.) ....................124 8.4.7.1 TIME SINCE LAST SERVICE (4.7.1.) .................. 125 8.4.7.2 TIME UNTIL NEXT SERVICE (4.7.2.) .................. 125 8.4.7.3 REMINDER 1 (REQUIRED) (4.7.3.) ..................
  • Page 8 Table of contents 11.2 Performance ......................... 144 11.3 Construction ......................... 145 11.4 Operating conditions ......................145 11.5 Process ..........................146 11.6 Approvals data ........................147 11.7 Communication: HART ......................147 11.8 Programmer (infrared keypad) ..................... 148 Dimension drawings ..........................149 12.1 SITRANS LR560 with stainless steel universal flat-faced flange ........
  • Page 9 Table of contents HART Electronic Device Description (EDD) ................. 169 HART Communicator 375 Menu Structure ................170 HART version ........................176 B.4.1 Burst Mode ..........................176 B.4.2 HART Multidrop Mode ......................176 Certificates and Support ........................177 Technical support ........................177 QR code label ........................
  • Page 10: Introduction

    Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customer’s exposure...
  • Page 11: Checking The Consignment

    The sales contract contains all obligations on the part of Siemens as well as the complete and solely applicable warranty conditions. Any statements regarding device versions described in the manual do not create new warranties or modify the existing warranty.
  • Page 12: Firmware Revision History

    Introduction 1.6 Firmware revision history Firmware revision history Firmware Hardware EDD version Date Changes version (dd/mm/yyyy) version 1.00.00 1.00.00 1.00.00 19 Oct.. 2010 Initial release 1.00.02-06 1.xx.xx 1.00.02-06 18 Nov. 2011 Maintenance release 1.00.02-08 1.xx.xx 1.00.02-08 07 Feb. 2012 Damping Filter Parameter default change to 60s 1.00.03 1.xx.xx...
  • Page 13: Safety Notes

    Safety notes Preconditions for use This device left the factory in good working condition. In order to maintain this status and to ensure safe operation of the device, observe these instructions and all the specifications relevant to safety. Observe the information and symbols on the device. Do not remove any information or symbols from the device.
  • Page 14: Laws And Directives

    2.1.5 Radio Equipment Directive (RED) compliance (Europe) Hereby, Siemens declares that the SITRANS LR560 is in compliance with the essential requirements and other relevant provisions of Directive 2014/53/EU. The LR560 complies with EN 302 372 for use in closed storage vessels, when installed according to the installation requirements of EN 302 372, and may be used in all EU countries.
  • Page 15: Federal Communications Commission (Fcc) Conformity (Us)

    The LR560 complies with ETSI EN 302 729 for use outside of closed tanks in most EU countries. (For a list of exceptions, see the LR560 Declaration to EN 302 729, which can be accessed online here (www.siemens.com/LR560).) For open air installations, the following conditions must be observed: ●...
  • Page 16: Industry Canada

    Safety notes 2.2 Use in hazardous areas 2.1.7 Industry Canada The SITRANS LR560 complies with Industry Canada standard RSS211 (March 2015). 1. The installation of the SITRANS LR560 shall be done by trained installers, in strict compliance with the manufacturer's instructions. 2.
  • Page 17: Requirements For Special Applications

    Due to the large number of possible applications, each detail of the described device versions for each possible scenario during commissioning, operation, maintenance or operation in systems cannot be considered in the instructions. If you need additional information not covered by these instructions, contact your local Siemens office or company representative. Note...
  • Page 18: Description

    Description SITRANS LR560 overview SITRANS LR560 is a 2-wire, 78 GHz FMCW radar level transmitter for continuous monitoring of solids and liquids in vessels to a range of 100 m (329 ft). The plug-and-play performance is ideal for all solids applications, including those with extreme dust and high temperatures to +200 °C (+392 °F).
  • Page 19: Installing/Mounting

    Refer to the information in Technical data (Page 144). Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
  • Page 20: Installation Location Requirements

    Installing/mounting 4.1 Basic safety instructions WARNING Pressure applications Danger to personnel, system and environment can result from improper installation. • Improper installation may result in loss of process pressure. WARNING Exceeded maximum permissible operating pressure Risk of injury or poisoning. The maximum permissible operating pressure depends on the device version, pressure limit and temperature rating.
  • Page 21: Proper Mounting

    Installing/mounting 4.1 Basic safety instructions NOTICE Direct sunlight Device damage. The device can overheat or materials become brittle due to UV exposure. • Protect the device from direct sunlight. • Make sure that the maximum permissible ambient temperature is not exceeded. Refer to the information in Technical data (Page 144).
  • Page 22: Installation Instructions

    Installing/mounting 4.2 Installation instructions Installation instructions NOTICE Damage to the flange If mating flange faces are not flat and free of distortion, then bolting the flanged process connection may produce a bending load on the device’s flange. Cracking or other damage may occur.
  • Page 23: Nozzle Location

    Installing/mounting 4.2 Installation instructions 4.2.2 Nozzle location Note False echoes For details on avoiding false echoes, see SHAPER MODE (2.8.4) (Page 114). ● Avoid central locations on tall, narrow vessels Beam angle ● Beam angle is the width of the cone where the energy density is half of the peak energy density.
  • Page 24: Sunshield

    Installing/mounting 4.2 Installation instructions ① ambient temperature: –40 °C to +80 °C (–40 °F to +176 °F) ② process temperature: –40 to +100 °C (–40 to +212 °F) or –40 to +200 °C (–40 to +392 °F) de- pending on the version 4.2.4 Sunshield The LR560 display can be protected by an optional sun shield if the instrument will be...
  • Page 25: Aimer Adjustment

    Installing/mounting 4.2 Installation instructions 4.2.5 Aimer adjustment Note Measuring material in the cone Aiming will assist in measuring material in the cone. ① ② 3" flange 4" and 6" flange ① Aiming is not required for signal optimization with 78 GHz frequency. ②...
  • Page 26: Air Purging System

    Installing/mounting 4.2 Installation instructions 4.2.6 Air purging system For convenient cleaning, a purging inlet is provided above the antenna. The system provides a 1/8" inlet (female thread) above the antenna where clean, dry air passes to the face of the antenna lens to clean it.
  • Page 27: Removable Display

    Installing/mounting 4.3 Disassembly 4.2.7 Removable display The optional display can be rotated as required, to one of 4 positions, 90 degrees apart, see Connecting SITRANS LR560 (Page 30). It can also be used to transfer parameters from one device to another, see COPY PARAMETERS TO DISPLAY (1.3.) (Page 97). Disassembly WARNING Incorrect disassembly...
  • Page 28: Connecting

    Connecting Basic safety notes WARNING Unsuitable cables, cable glands and/or plugs Risk of explosion in hazardous areas. • Use only cable glands/plugs that comply with the requirements for the relevant type of protection. • Tighten the cable glands in accordance with the torques specified in Technical data (Page 144).
  • Page 29: Incorrect Connection To Power Source

    WARNING Missing PE/ground connection Risk of electric shock. Depending on the device version, connect the power supply as follows: • Power plug: Ensure that the used socket has a PE/ground conductor connection. Check that the PE/ground conductor connection of the socket and power plug match each other.
  • Page 30: Connecting Sitrans Lr560

    WARNING Incorrect selection of type of protection Risk of explosion in areas subject to explosion hazard. This device is approved for several types of protection. 1. Decide in favor of one type of protection. 2. Connect the device in accordance with the selected type of protection. 3.
  • Page 31: Basic Plc/Ma Configuration With Hart

    8. Replace optional display and device lid. 9. Tighten locking screw. If cable is routed through conduit, use only approved suitable-size hubs for waterproof applications. Removing the lid and display Terminal block ① cable gland (or NPT cable entry ② cable shield ③...
  • Page 32: Nameplates For Hazardous Area Installations

    FM/CSA Class 1, Div 2 installation and connection drawing The FM/CSA Class 1, Div 2 connection drawing (A5E02795836) listed on the device nameplate can be downloaded from the Siemens Industry Image Database: FM/CSA Class 1, Div 2 connection drawing A5E02795836 (http://www.automation.siemens.com/bilddb/index.aspx?gridview=view2&objkey=G_FI01_XX...
  • Page 33: Instructions Specific To Hazardous Area Installations

    Instructions specific to hazardous area installations 5.5.1 (Reference European ATEX Directive 2014/34/EU, Annex II, 1.0.6) The following instructions apply to equipment covered by certificate number SIRA 09ATEX9356X and Sira 09ATEX4357X. 1. For use and assembly and details of marking/coding, refer to the main instructions. 2.
  • Page 34: Commissioning

    Commissioning Basic safety notes WARNING Improper commissioning in hazardous areas Device failure or risk of explosion in hazardous areas. • Do not commission the device until it has been mounted completely and connected in accordance with the information in Installing/mounting (Page 19). •...
  • Page 35 WARNING Hazardous contact voltage Risk of injury through hazardous contact voltage when the device is open or not completely closed. The degree of protection specified on the nameplate or in Approvals data (Page 147) is no longer guaranteed if the device is open or not properly closed. •...
  • Page 36: Activating The Radar Device

    Activating the radar device Power up the instrument. A transition screen showing first the Siemens logo and then the current firmware revision is displayed while the first measurement is being processed. The first time the device is configured, you will be prompted to select a language (English, German, French, Spanish or Chinese).
  • Page 37 PROGRAM mode display Navigation view ● A visible menu bar indicates the menu list is too long to display all items. ● The depth of the item band on the menu bar indicates the length of the menu list: a deeper band indicates fewer items.
  • Page 38: Commissioning Via Local Display

    Commissioning via local display 6.4.1 Local operation SITRANS LR560 carries out its level measurement tasks according to settings made via parameters. The settings can be modified locally via the optional local graphical display which consists of an LCD display with buttons. You can use either the push buttons or an infrared handheld programmer to make changes.
  • Page 39: Commissioning Via Handheld Programmer

    4. Use UP or DOWN to modify the highlighted digit. Scroll past 9 to reach the decimal point. 5. When the value is complete, press RIGHT until the Enter icon is highlighted, then press RIGHT to accept the value. To modify a text string: 1.
  • Page 40: Lithium Batteries

    6.5.2 Lithium batteries Lithium batteries are primary power sources with high energy content designed to provide the highest possible degree of safety. WARNING Potential hazard Lithium batteries may present a potential hazard if they are abused electrically or mechanically. Observe the following precautions when handling and using lithium batteries: •...
  • Page 41: Key Functions In Measurement Mode

    6.5.3 Key functions in measurement mode Key functions in measurement mode Function Result Updates the loop New value is shown in secondary region of local display. current Updates internal enclosure tempera- ture reading Updates echo confi- New value is shown in secondary region of local display. dence value Updates distance measurement...
  • Page 42: Programming

    6.5.4 Programming Note • While the device is in PROGRAM mode the output remains fixed and does not respond to changes in the device. • The device automatically returns to Measurement mode after a period of inactivity in PROGRAM mode (between 15 seconds and 2 minutes, depending on the menu level). Change parameter settings and set operating conditions to suit your specific application.
  • Page 43 Note Navigation • In Navigation mode, ARROW keys move to the next menu item in the direction of the arrow. • For Quick Access to parameters via the handheld programmer, press Home , and then enter the menu number, for example: 3.2. Echo Profile. Key functions in Navigation mode Name Menu level...
  • Page 44 Key functions in Program mode Name Function UP or DOWN Selecting options Scrolls to item. arrow Alphanumeric editing • Increments or decrements digits • Toggles plus and minus sign • RIGHT arrow Selecting options Accepts the data (writes the parameter) •...
  • Page 45: Quick Start Wizard Via The Handheld Programmer

    6.5.4.1 Quick Start Wizard via the handheld programmer Note • A reset to factory defaults should be performed before running the Quick Start Wizard if the device has been used in a previous application. See Quick Start Wizard via the local display push buttons (Page 38).
  • Page 46 Response rate Factory setting: Setting range: Response rate Fill rate per Minute/Empty rate per Minute Damping Filter SLOW 0.1 m/min (0.32 ft/min) 600 s 1.0 m/min (3.28 ft/min) 60 s FAST 10.0 m/min (32.8 ft/min) Purpose: Sets the reaction speed of the device to measurement changes in the target range.
  • Page 47 Level Space Distance ① ② sensor reference point high calibration point ③ ④ 20 mA, 100% 4 mA, 0% ⑤ low calibration point Low calibration point Factory setting: 40.000 m or 100.000 m Setting range: 0.000 to 40.000 m or 0.000 to 100.000 m Purpose: Distance from Sensor Reference to Low Calibration Point: usually process empty level.
  • Page 48: Requesting An Echo Profile

    Wizard complete Setting range: BACK, CANCEL, FINISH (Display returns to 1.1 Quick Start Wizard menu when Quick Start is successfully completed.) Description: To transfer Quick Start values to the device and return to Program menu, press DOWN (Finish). Then press LEFT to return to Measurement mode.
  • Page 49: Application Example

    Application example The application is a vessel that takes an average 3 hours (180 minutes) to fill and 3 weeks to empty. Fill rate = 0.08 m/minute [(Low Cal Pt. minus High Cal Pt.) / fastest of fill or empty time] = (15.5 m –...
  • Page 50: Operating

    SIMATIC PDM Version Check the support page of our website to make sure you have the latest version of SIMATIC PDM, the most recent Service Pack (SP) and the most recent hot fix (HF): Siemens Industry Online Support (https://support.industry.siemens.com/cs/?lc=en-WW) Browse to Product Support >...
  • Page 51: Configuring A New Device

    • Application Guides for setting up HART and Profibus PA devices with SIMATIC PDM can be downloaded from our website: LR560 (www.siemens.com/LR560). 1. Check that you have the most recent EDD, and if necessary update it. See Updating the Electronic Device Description (EDD) (Page 50).
  • Page 52: Quick Start Wizard Via Simatic Pdm

    2. Launch SIMATIC Manager and create a new project. Application Guides for setting up HART and PROFIBUS PA devices with SIMATIC PDM can be downloaded from the product page of our website: LR560 (www.siemens.com/LR560) Quick start Note • A reset to Factory Defaults should be performed before running the Quick Start Wizard if device has been used in a previous application.
  • Page 53 Step 1 – Identification Note The layout of the dialog boxes shown may vary according to the resolution setting for your computer monitor. 1. Click on Read Data from Device to upload Quick Start parameter settings from the device to the PC/PG and ensure PDM is synchronized with the device. 2.
  • Page 54 Step 2 – Application Note Application selection • Selecting STEEL changes the setting for POSITION DETECT (2.7.3.3) (Page 109) to Rising Edge. and for ALGORITHM (2.7.3.1) (Page 109) to F. • Selecting CONCRETE changes the setting for POSITION DETECT (2.7.3.3) (Page 109) to Rising Edge and for ALGORITHM (2.7.3.1) (Page 109) to ALF.
  • Page 55 Step 3 – Ranges Note SLOW Response Rate Selecting SLOW Response Rate changes setting for AVERAGE AMOUNT (2.7.5.3.) (Page 112) to 0.9. Set the parameters, and click on NEXT. SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 56: Changing Parameter Settings Using Simatic Pdm

    Step 4 – Summary Check parameter settings, and click on BACK to return and revise values, FINISH to save settings offline, or FINISH AND DOWNLOAD to save settings offline and transfer them to the device. The message Quick Start was successful will appear. Click on OK. 7.1.1.6 Changing parameter settings using SIMATIC PDM Note...
  • Page 57: Parameters Accessed Via Pull-Down Menus

    7.1.1.7 Parameters accessed via pull-down menus Click on Device, View or Diagnostics to open the associated pull-down menus. Pull-down menus Device menu View menu Diagnostics menu Download to device Process variables Update diagnostics (Page 157) Upload to PC/PG Device diagnostics Start Life List Update Diagnostic Status Assign address to TAG...
  • Page 58: Echo Profile Utilities

    Echo profile utilities Open the menu Device – Echo Profile Utilities and click on the appropriate tab for easy access to: ● Echo profile (Page 59) ● View Saved Echo Profiles (Page 59) ● TVT Shaper (Page 58) ● Auto False Echo Suppression (Page 60) ●...
  • Page 59: View Saved Echo Profiles

    Note Transferring the new values to the device If the TVT Shaper tab is closed without transferring new values to the device, the new values will appear in the PDM list even though they have not been transferred to the device. Echo profile Note •...
  • Page 60: Auto False Echo Suppression

    Auto false echo suppression Note • Ensure material level is below all known obstructions when using Auto False Echo Suppression to learn the echo profile. An empty or almost empty vessel is recommended. • Note the distance to material level when learning the echo profile, and set Auto False Echo Suppression Range to a shorter distance to avoid the material echo being screened out.
  • Page 61 4. Make sure Auto False Echo Suppression Range is On. 5. Enter the value for Auto False Echo Suppression Range. 6. Click Learn. The message appears: 'This will learn a new echo profile. Once done it cannot be undone'. Click OK. 7.
  • Page 62: Echo Setup

    After Auto False Echo Suppression ① ④ False echo Material level ② ⑤ Learned TVT Default TVT ③ ⑥ Auto False Echo Suppression Range Echo marker Echo setup Provides quick access to echo selection, filtering, and response rate parameters. Open the menu Device – Echo Profile Utilities and click on Echo Setup. Maintenance You can set schedules and reminders for: ●...
  • Page 63: Select Analog Output

    To set Device/Sensor Maintenance schedules: 1. Open the menu Device – Maintenance, and click on the Remaining Device/Sensor Lifetime tab. 2. Modify desired values, and if desired, set reminders for either or both of Reminder 1 before Lifetime (Required)/Reminder 2 before Lifetime (Demanded). 3.
  • Page 64: Configuration Flag Reset

    Loop test Note The simulated AO (Analog Output) value influences output to the control system. Allows you to input a simulated value (4 mA, 20 mA, or a user-defined value) in order to test the functioning of the mA connections during commissioning or maintenance of the device. The range is 3.56 mA to 22.6 mA, see mA Output Value (2.6.6.).
  • Page 65: Hart Communication

    HART Communication Sets the number of request/response preambles (default 5). The preamble consists of three or more hexadecimal FF characters (all 1s). This allows the receiving modem to get its frequency-detection circuits synchronized to the signal after any pause in transmission. We recommend you do not change the default value (5).
  • Page 66: Device Status

    Trend Open the menu View – Process Variables and click on Trend. The mA Output follows Primary Value (PV), and can be set to either Level, Space, or Distance. Select analog output (Page 63) Device status Open the menu Diagnostics – Device Diagnostics to view Diagnostics, Device Status, Hardware/Firmware (HW/FW) Status, and Maintenance status.
  • Page 67: Operating Via Fdt (Field Device Tool)

    EDD but an EDD is independent of the operating system. SITRANS DTM ● SITRANS DTM is an EDDL interpreter developed by Siemens to interpret the EDD for that device. ● To use SITRANS DTM to connect to an instrument, you must first install SITRANS DTM on your system and then install the instrument EDD written for SITRANS DTM.
  • Page 68: Functions In Ams Device Manager

    You can locate the EDD in Device Catalog, under Sensors/Level/Echo/Siemens Milltronics/SITRANS LR560. Check the product page of our website (www.siemens.com/LR560), under Support > Software Downloads, to make sure you have the latest version of the EDD for AMS Device Manager. If you need to install a new EDD, see Configuring a new device below.
  • Page 69: Master Reset

    Configuring a new device 1. Check our website to make sure you have the most recent EDD. website (www.siemens.com/LR560) Go to Support > Software Downloads and if necessary download it. Save the files to your computer, and extract the zipped file to an easily accessed location.
  • Page 70: Pull-Down Menu Access

    Pull-down menu access ① Action menu items A pull-down menu under Actions gives alternative access to several features. Scan Device • Open the menu Actions – Scan Device. • Scan Device uploads parameters from the device (synchronizes parameters). Device configuration 1.
  • Page 71 3. Open the pull-down menu Actions – Scan Device to synchronize parameters (upload parameters from the device to AMS). 4. Configure the device via the Quick Start wizard. ① Master Reset Quick Start Wizard via AMS Device Manager Note • A reset to Factory Defaults should be performed before running the Quick Start Wizard if device has been used in a previous application.
  • Page 72 Quick Start Wizard via AMS Device Manager Step 1 – Identification 1. Navigate to Configure/Setup > Wizard > Quick Start. 2. Click on Step 1. 3. You can accept the default values without modification. (Description, Message, and Installation Date fields can be left blank.) If desired, make changes then click on Apply. SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 73 Step 2 – Application Note Application type settings • Selecting either STEEL or CONCRETE does a functional reset, see Master reset (Page 69). • Selecting STEEL changes the setting for POSITION DETECT (2.7.3.3) (Page 109) to Rising Edge. and for ALGORITHM (2.7.3.1) (Page 109) to F. •...
  • Page 74 Step 3 – Ranges Note Response rate Selecting SLOW Response Rate changes setting for AVERAGE AMOUNT (2.7.5.3.) (Page 112) to 0.9. 1. Click on Step 3. 2. Change units if desired (in meters by default). 3. Set High and Low Calibration points. 4.
  • Page 75: Changing Parameter Settings Using Ams Device Manager

    Step 4 – Summary 1. Check parameter settings, and click on Cancel to abort, or Apply to transfer values to the device. Changing parameter settings using AMS Device Manager Note For a complete list of parameters, see Parameter Reference (Page 94). For more detailed explanations of the parameters listed below see the pages referenced.
  • Page 76 Operation Navigate to Configure/Setup > Operation and click on Operation to open the dialog window for access to: General ● Select Analog Output, see Select analog output (Page 63) ● Master Reset, see Master reset (Page 69) Simulation/Test ● Self Test, see Self test (Page 63) ●...
  • Page 77 Sensor Navigate to Configure/Setup > Setup and click on Sensor for access to: SENSOR (2.2.) (Page 100) ● Units ● Sensor Mode ● Damping Filter CALIBRATION (2.3.) (Page 101) ● Low Calibration Point ● High Calibration Point ● Sensor Offset RATE (2.4.) (Page 102) ●...
  • Page 78 Analog Output Scale Navigate to Configure/Setup > Setup and click on Analog Output Scaling for access to: Analog Output Scaling, see ANALOG OUTPUT SCALING (2.6.) (Page 105) ● Current Output Function ● 4 mA Setpoint ● 20 mA Setpoint ● Minimum mA Limit ●...
  • Page 79: Echo Select (2.7.3.)

    Signal Processing General Navigate to Configure/Setup > Setup > Signal Processing and click on General for access to: SIGNAL PROCESSING (2.7.) (Page 108) ● Near Range ● Far Range ECHO SELECT (2.7.3.) (Page 109) ● Algorithm ● Position Detect ● Echo Threshold ●...
  • Page 80 Modify the TVT to screen out false echoes. TVT SHAPER (2.9.) (Page 114) Navigate to Configure/Setup > Setup > Signal Processing and click on TVT. Click on one of the two tabs to access the parameters listed: TVT Setup TVT SETUP (2.8.) (Page 113) ●...
  • Page 81: Local Display

    Local Display Navigate to Configure/Setup > Setup > Local Display for access to: ● Language ● LCD Contrast, see LCD CONTRAST (4.6.) (Page 124) ● LCD Backlight, see LCD BACKLIGHT (4.5.) (Page 124) 7.1.3.2 Maintenance and diagnostics Navigate to Maintenance and Diagnostics for access to: Remaining device lifetime, see REMAINING DEVICE LIFETIME (3.6) (Page 118) ●...
  • Page 82 Remaining sensor lifetime, see REMAINING SENSOR LIFETIME (3.7.) (Page 120) ● Lifetime (expected) ● Time in operation ● Remaining lifetime ● Activation of reminders ● Reminder 1 before lifetime (Required) ● Reminder 2 before lifetime (Demanded) 1. Open the window Remaining sensor lifetime. 2.
  • Page 83: Communication

    Calibration schedule, see CALIBRATION SCHEDULE (4.8.) (Page 127) ● Calibration interval ● Time since last calibration ● Time until next calibration ● Activation of reminders ● Reminder 1 before Calibration (Required) ● Reminder 2 before Calibration (Demanded) Electronic Temperature, see ELECTRONIC TEMPERATURE (3.5.) (Page 117) ●...
  • Page 84: Device Diagnostics

    7.1.3.5 Device Diagnostics Click on the Device Diagnostics bar at the bottom of the navigation window for access to Device Status. Hardware/Firmware Status SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 85: Password Protection

    Process variables To compare outputs in real time, click on Process Variables at the bottom of the navigation window for access to: Process Variables ● Values (level, space, distance) ● Analog Output ● Trend View Echo Profile ● Navigate to Process Variables>Echo Profile. ●...
  • Page 86: User Manager Utility

    User Manager utility Usernames, passwords, and permissions, are assigned to users by an AMS Device Manager administrator, using the User Manager utility on the Server Plus Station. Only a user with AMS Device Manager System Administration rights can log in to User Manager. To configure a new user/edit existing user: 1.
  • Page 87: Ams Device Menu Structure

    7.1.3.6 AMS Device Menu Structure Configure/Setup Function Group Parameter number IDENTIFICATION Identification Identification (tab) Long Tag LONG TAG (2.1.1.) (Page 99) TAG (2.1.2.) (Page 99) Descriptor DESCRIPTOR (2.1.3.) (Page 99) Message MESSAGE (2.1.4.) (Page 99) Date Range Mode Manufacturer Product Name Order Number Final Assembly Number Hardware Revision...
  • Page 88: Operation

    Descriptor Message Date Order Number Range Mode Language Application Type Operating Mode Unit Low Calibration Point (X) High Calibration Point (Y) Response Rate Configuration Flag Reset Configuration Flag Reset (tab) OPERATION Operation Operation (tab) Long Tag Select Analog Output Master Reset MASTER RESET (4.2.) (Page 123) Self Test Loop Test...
  • Page 89 Long Tag Current Output Function Start of Scale (=4 mA) Full Scale (=20 mA) Control Range: Lower Limit Control Range: Upper Limit Signal Processing General General (tab) Long Tag Near Range NEAR RANGE (2.7.1.) (Page 108) Far Range FAR RANGE (2.7.2.) (Page 108) Algorithm ALGORITHM (2.7.3.1) (Page 109) Position Detect...
  • Page 90: Maintenance And Diagnostics

    Long Tag Breakpoints Manual TVT Curve Manual TVT Diagram (tab) Long Tag Shaper Mode Echo Profile Echo Profile (tab) Long Tag Distance Measurement Confidence CONFIDENCE (2.7.6.1) (Page 112) Near Range NEAR RANGE (2.7.1.) (Page 108) Local Display Local Display (tab) Long Tag Language LANGUAGE (7.) (Page 131)
  • Page 91 Sensor Replaced Snooze for 1 year Service Schedule Service Schedule (tab Long Tag Service Interval SERVICE INTERVAL (4.7.6.) (Page 126) Time Since Last Service TIME SINCE LAST SERVICE (4.7.1.) (Page 125) Time Until Next Service TIME UNTIL NEXT SERVICE (4.7.2.) (Page 125) Activation of Reminders REMINDER ACTIVATION (4.7.5.) (Page 125)
  • Page 92: Device Diagnostics

    Manufacturer's ID Device ID Product ID Device Revision EDD Revision Universal Command SECURITY Security Security (tab) Long Tag Write Protection WRITE PROTECTION (6.1.) (Page 131) Local Operation Enable Device Diagnostics Function Group DEVICE DIAGNOSTICS Status Device Status (tab) Long Tag Status Listing HW/FW Status (tab) Long Tag...
  • Page 93 Confidence Near Range Compare Function Group COMPARE Compare Identification (tab) Descriptor Message Date Manufacturer Product Name Universal Command Revision Device Revision Device ID Final Assembly Number Hardware Revision Software Revision Distributor Order Number Setup (tab) Long Tag Status Listing SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 94: Parameter Reference

    Parameter Reference Note • Parameter names and menu structure are almost identical for SIMATIC PDM and the local display interface (LDI). • To enter Program mode using the device buttons, press . Press to return to Measurement mode. • Mode toggles between PROGRAM and Measurement Modes via the handheld programmer.
  • Page 95: Quick Start Wizard (1.1.)

    8.1.2 QUICK START WIZARD (1.1.) The Quick Start wizard provides an easy step-by-step procedure to configure the device for a simple application. From measurement screen, press RIGHT twice to open the Quick Start Wizard menu. Select a wizard, press RIGHT to open the first step, and follow the instructions.
  • Page 96 Make sure the material level is below all known obstructions. 1. Navigate to Level Meter >DIAGNOSTICS (3.) (Page 115)> ECHO PROFILE (3.2.) (Page 116). 2. Press RIGHT to request a profile. 3. Determine a range that includes the false echo but not the true echo: in the example, 3.3 m.
  • Page 97: Copy Parameters To Display (1.3.)

    8.1.4 COPY PARAMETERS TO DISPLAY (1.3.) Transfers parameter settings from a device to the local display interface. See Connecting SITRANS LR560 (Page 30) for instructions on removing the local display interface. 1. Press RIGHT to edit. 2. Press DOWN to select Start and RIGHT to begin the transfer.
  • Page 98: Copy Firmware To Display (1.5.)

    8.1.6 COPY FIRMWARE TO DISPLAY (1.5.) Transfers firmware from a device to the local display interface. 1. Press RIGHT to edit. 2. Press DOWN to select Start and RIGHT to begin the transfer. SW UPLOAD is displayed, then the device returns to Measurement mode. 8.1.7 COPY FIRMWARE FROM DISPLAY (1.6.) Note...
  • Page 99: Setup (2.)

    SETUP (2.) Note Handheld programmer Values shown in the following tables can be entered via handheld programmer. 8.2.1 DEVICE (2.1.) 8.2.1.1 LONG TAG (2.1.1.) Text that can be used in any way. A recommended use is as a unique label for a field device in a plant.
  • Page 100: Menu Timeout (2.1.9.)

    8.2.1.9 MENU TIMEOUT (2.1.9.) Factory setting: 120 s Setting range: 15 to 65535 s Purpose: Time menu stays visible before switching back to Measurement view if no key is pressed. 8.2.1.10 MANUFACTURE DATE (2.1.10.) The date of manufacture of the device (dd mm yyyy). 8.2.2 SENSOR (2.2.) 8.2.2.1...
  • Page 101: Damping Filter (2.2.3.)

    8.2.2.3 DAMPING FILTER (2.2.3.) Note Response rate For time constant values corresponding to response rate settings, please see RESPONSE RATE (2.4.1.) (Page 102). Factory setting: 60 s Setting range: 0 to 1500 s Purpose: The time constant for the damping filter. The damping filter smooths out the response to a sudden change in level.
  • Page 102: Sensor Offset (2.3.3.)

    Description: When setting the High Calibration Point value, note that echoes are ignored within NEAR RANGE (2.7.1.) (Page 108). Any change to High Calibration Point will cause the mA setpoints to be updated. Related parame- UNITS (2.2.1.) (Page 100) ters: FAR RANGE (2.7.2.) (Page 108) The point from which level measurement is referenced.
  • Page 103: Fill Rate/Min (2.4.2.)

    8.2.4.2 FILL RATE/MIN (2.4.2.) Factory setting: Medium Setting range: 0 to 999 999 m / min.(when using AMS, max. value is 99 999 m/min.) RESPONSE RATE (2.4.1.) (Page 102) Fill rate/min Slow 0.1 m/min (0.32 ft/min) Medium 1.0 m/min (3.28 ft/min) Fast 10.0 m/min (32.8 ft/min) Purpose:...
  • Page 104: Fail-Safe (2.5.)

    Note The selected rate will also impact the AVERAGE AMOUNT (2.7.5.3.) (Page 112) parameter. For example, a SLOW setting will change it to 0.9, and a FAST setting may require it to be reduced to a very low value. 8.2.5 FAIL-SAFE (2.5.) Note Default settings...
  • Page 105: Analog Output Scaling (2.6.)

    8.2.6 ANALOG OUTPUT SCALING (2.6.) 8.2.6.1 CURRENT OUTPUT FUNCTION (2.6.1.) Note • Level, space, and distance, have different reference points. • Use caution when changing Current Output Function while the device is connected to a HART network. Current Output Function controls the primary value and the loop current for the device.
  • Page 106: Ma Setpoint (2.6.2.)

    8.2.6.2 4 mA SETPOINT (2.6.2.) Factory setting: 0.00 m Setting range: –999999 to +999999 (limits vary with current function and units) Purpose: Sets the process level corresponding to the 4 mA value. 4 mA always de- faults to 0, and CURRENT OUTPUT FUNCTION (2.6.1.) (Page 105) de- termines whether this is a Level, Space, or Distance measurement.
  • Page 107: Max. Ma Limit (2.6.5.)

    8.2.6.5 MAX. mA LIMIT (2.6.5.) Factory setting: 20.50 mA Setting range: 3.56 to 22.6 mA Purpose: Prevents the mA output from rising above this maximum level for a meas- urement value. This does not restrict the Fail-safe or Manual settings. 8.2.6.6 mA OUTPUT MODE (2.6.6.) Note...
  • Page 108: Ma Output Value (2.6.8.)

    8.2.6.8 mA OUTPUT VALUE (2.6.8.) Setting range: Read only, 3.56 to 22.6 mA Purpose: Allows you to view the simulated value entered to test the functioning of the loop. Related parameters: MANUAL VALUE (2.6.7.) (Page 107) 8.2.7 SIGNAL PROCESSING (2.7.) 8.2.7.1 NEAR RANGE (2.7.1.) Factory setting:...
  • Page 109: Echo Select (2.7.3.)

    8.2.7.3 ECHO SELECT (2.7.3.) ALGORITHM (2.7.3.1) Factory setting: F: First Echo Setting range: Area Largest First Echo Area Largest Echo First Echo Echo Area Largest Echo Area First Echo Largest First Best of First and Largest echo Best Largest Echo Best First Echo LAST Last...
  • Page 110: Sampling (2.7.4.)

    CLEF RANGE (2.7.3.4) Note CLEF range • CLEF Range is referenced from Far Range. • The value for CLEF Range must include the difference between Far Range and Low Calibration Point, plus any level above the Low Calibration Point to be managed by the CLEF algorithm.
  • Page 111: Echo Lock (2.7.4.1.)

    8.2.7.5 ECHO LOCK (2.7.4.1.) Factory setting: Material Agitator Setting range: Lock Off Maximum Verification (not recommended for radar) Material Agitator Total Lock (not recommended for radar) Purpose: Selects the measurement verification process. Related parameters: FILL RATE/MIN (2.4.2.) (Page 103) EMPTY RATE/MIN (2.4.3.) (Page 103) UP SAMPLING (2.7.4.2.) (Page 111) DOWN SAMPLING (2.7.4.3.) (Page 111) 8.2.7.6...
  • Page 112: Filtering (2.7.5.)

    8.2.7.9 FILTERING (2.7.5.) NARROW ECHO FILTER (2.7.5.1.) Factory setting: 0 = OFF Setting range: 0 to 255, greater = wider Purpose: Filters out echoes of a specific width. Description: To remove a false echo from the Echo Profile, take its width in mm and multiply it by 0.006.
  • Page 113: Tvt Setup (2.8.)

    8.2.8 TVT SETUP (2.8.) 8.2.8.1 AUTO FALSE ECHO SUPPRESSION (2.8.1) Note AFES wizard We recommend setting Auto False Echo Suppression either via SIMATIC PDM or via local operation using the Auto False Echo Suppression wizard. Used together with SHAPER MODE (2.8.4) (Page 114) to screen out false echoes in a vessel with known obstructions.
  • Page 114: Shaper Mode (2.8.4)

    8.2.8.4 SHAPER MODE (2.8.4) Factory setting: Setting range: ON, OFF Purpose: Enables/disables the TVT shaper. 8.2.9 TVT SHAPER (2.9.) Note • SHAPER MODE (2.8.4) (Page 114) must be turned ON in order for TVT shaper points to be transferred • We recommend using SIMATIC PDM to access this feature Factory setting: 0 dB Setting range:...
  • Page 115: Measured Values (2.10.)

    8.2.10 MEASURED VALUES (2.10.) Purpose: Read only. Allows you to view measured values for diagnostic purposes. Description: To access measured values via SIMATIC PDM: • Open the menu View – Process Variables. Process variables: The value for Level/Volume, al- ways displayed here in percent. MAIN OUTPUT (2.10.1.) (Page 115) OUTPUT NO LINEARIZATION (2.10.2.) The value for Level, always dis-...
  • Page 116: Echo Profile (3.2.)

    8.3.2 ECHO PROFILE (3.2.) Purpose: Allows you to request the current echo profile either locally via the handheld programmer, or remotely via SIMATIC PDM, or AMS Device Manager, see Pro- cess Intelligence (Page 157) Description: To acknowledge a reminder via SIMATIC PDM: 1.
  • Page 117: Minimum Primary Value (3.4.3.)

    8.3.7 MINIMUM PRIMARY VALUE (3.4.3.) The minimum recorded Primary Value from the Analog Input Function Block 1. 8.3.8 MAXIMUM PRIMARY VALUE (3.4.4.) The maximum recorded Primary Value from the Analog Input Function Block 1. 8.3.9 MINIMUM SECONDARY VALUE (3.4.5.) The minimum recorded Secondary Value from the Analog Input Function Block 1. 8.3.10 MAXIMUM SECONDARY VALUE (3.4.6.) The maximum recorded Secondary Value from the Analog Input Function Block 1.
  • Page 118: Internal Temperature (3.5.3)

    8.3.11.3 INTERNAL TEMPERATURE (3.5.3) Read only. Displays (in °C) the current temperature on the circuit board recorded by the internal electronics. For access via SIMATIC PDM open the menu View – Process Variables and check the field Electronics Temperature. 8.3.12 REMAINING DEVICE LIFETIME (3.6) Note •...
  • Page 119: Remind. 1 (Required) (3.6.3.)

    8.3.12.3 REMIND. 1 (REQUIRED) (3.6.3.) Factory setting: 0.164 years Setting range: 0 to 20 years Purpose: If REMAINING LIFETIME (3.6.2.) (Page 118) is equal to or less than this value, the device generates a Maintenance Required reminder. Description: 1) Modify values as required. 2) Set REMINDER ACTIVATION (3.6.5.) (Page 119).
  • Page 120: Acknowledge Status (3.6.8.)

    8.3.12.8 ACKNOWLEDGE STATUS (3.6.8.) Indicates which level of maintenance reminder has been acknowledged. In SIMATIC PDM, open the menu Diagnostics > Device Diagnostics, click on the Maintenance tab, and check the Calibration Schedule Status window. 8.3.12.9 ACKNOWLEDGE (3.6.9.) Purpose: Acknowledges the current maintenance reminder. Description: To acknowledge a reminder via SIMATIC PDM: •...
  • Page 121: Time In Operation (3.7.1.)

    8.3.13.1 TIME IN OPERATION (3.7.1.) Read only. The amount of time the sensor has been operating. 8.3.13.2 REMAINING LIFETIME (3.7.2.) Read only. LIFETIME EXPECTED (3.7.6.) (Page 122) less TIME IN OPERATION (3.7.1.) (Page 121). 8.3.13.3 REMINDER 1 (REQUIRED) (3.7.3.) Factory setting: 0.164 years Setting range: 0 to 20 years...
  • Page 122: Lifetime Expected (3.7.6.)

    8.3.13.6 LIFETIME EXPECTED (3.7.6.) Note The device always operates in years. Changing the units affects only the parameter view of the Remaining Sensor Lifetime parameters in SIMATIC PDM. Factory setting: 10.00 years Setting range: 0 to 20 years Purpose: Allows you to override the factory default. Description: Units: hours, days, years, are selectable only via SIMATIC PDM.
  • Page 123: Service (4.)

    SERVICE (4.) 8.4.1 DEMO MODE (4.1.) Factory setting: Setting range: ON or OFF Purpose: Used to set up for demonstrations: reduces the time between measure- ments and the accuracy for demonstration purposes. 8.4.2 MASTER RESET (4.2.) Note • Following a reset to Factory Defaults, the LCD displays the Quick Start wizard. •...
  • Page 124: Lcd Backlight (4.5.)

    8.4.5 LCD BACKLIGHT (4.5.) Factory setting: 128 seconds Setting range: 0 (backlight off) to 128 seconds (>120 means backlight always on) Purpose: Time the backlight remains on. 8.4.6 LCD CONTRAST (4.6.) Factory setting: Setting range: 0 to 20 Purpose: The factory setting is for optimum visibility at room temperature and in av- erage light conditions.
  • Page 125: Time Since Last Service (4.7.1.)

    8.4.7.1 TIME SINCE LAST SERVICE (4.7.1.) Time elapsed since last service. Can be reset to zero after performing a service. Can be reset locally by entering 0 in this parameter. To reset to zero: ● In SIMATIC PDM, open the menu Device – Maintenance, click on the Service Schedule tab, and click on Service Performed to restart the timer and clear any fault messages.
  • Page 126: Service Interval (4.7.6.)

    Factory setting: Timer OFF Setting range: Timer OFF ON NO LIMITS ON REMinders 1 and 2 checked ON REMinder 2 (Maintenance Demanded) checked Purpose: Allows you to enable a maintenance reminder. Description: 1. First set the values in REMINDER 1 (REQUIRED) (4.7.3.) (Page 125) / REMINDER 2 (DEMANDED) (4.7.4.) (Page 125).
  • Page 127: Acknowledge (4.7.9.)

    8.4.7.9 ACKNOWLEDGE (4.7.9.) Purpose: Acknowledges the current maintenance reminder. Description: To acknowledge a reminder via SIMATIC PDM: • Open the menu Diagnostics > Device Diagnostics and click on the tab Maintenance. • In the Calibration Schedule section, click on Acknowledge Warnings. To acknowledge a reminder via the local control buttons or hand-held program- mer: •...
  • Page 128: Time Since Last Calibration (4.8.1.)

    8.4.8.1 TIME SINCE LAST CALIBRATION (4.8.1.) Time elapsed since last calibration. Can be reset to zero after performing a calibration. Can be reset locally by entering 0 in this parameter. To reset to zero: ● In SIMATIC PDM, open the menu Device – Maintenance, click on the Calibration Schedule tab, and click on Calibration Performed to restart the timer and clear any fault messages.
  • Page 129: Reminder Activation (4.8.5.)

    8.4.8.5 REMINDER ACTIVATION (4.8.5.) Note Access To modify this parameter via SIMATIC PDM it must be accessed via the pull-down menu Device > Maintenance. Factory setting: Timer OFF Setting range: Timer OFF ON NO LIMITS ON REMinders 1 and 2 checked ON REMinder 2 (Maintenance Demanded) checked Purpose: Allows you to enable a maintenance reminder.
  • Page 130: Acknowledge (4.8.9.)

    8.4.8.9 ACKNOWLEDGE (4.8.9.) Purpose: Acknowledges the current maintenance reminder. Description: To acknowledge a reminder via SIMATIC PDM: • Open the menu Diagnostics > Device Diagnostics and click on the tab Mainte- nance. • In the Calibration Schedule section, click on Acknowledge Warnings. To acknowledge a reminder via the local control buttons or hand-held programmer: •...
  • Page 131: Remote Lockout (5.2.)

    8.5.2 REMOTE LOCKOUT (5.2.) Factory setting: Setting range: OFF, ON Purpose: Enables/disables the read/write access to parameters via remote commu- nications. If locked via the handheld programmer, it can be unlocked only via the handheld programmer. If locked via AMS, it can be reset via AMS. SECURITY (6.) 8.6.1 WRITE PROTECTION (6.1.)
  • Page 132: Service And Maintenance

    ● Reliability of power supply, lightning protection, and grounds WARNING Impermissible repair and maintenance of the device • Repair and maintenance must be carried out by Siemens authorized personnel only. WARNING Impermissible repair of explosion protected devices Risk of explosion in hazardous areas •...
  • Page 133: Cleaning

    WARNING Leaks in the sample gas path Risk of poisoning. When measuring toxic process media, these can be released or collect in the device if there are leaks in the sample gas path. • Purge the device as described in Commissioning (Page 34). •...
  • Page 134 WARNING Humid environment Risk of electric shock. • Avoid working on the device when it is energized. • If working on an energized device is necessary, ensure that the environment is dry. • Make sure when carrying out cleaning and maintenance work that no moisture penetrates the inside of the device.
  • Page 135 WARNING Hot, toxic or corrosive process media Risk of injury during maintenance work. When working on the process connection, hot, toxic or corrosive process media could be released. • As long as the device is under pressure, do not loosen process connections and do not remove any parts that are pressurized.
  • Page 136: Return Procedure

    – Number of returned devices/replacement parts – Reason for returning the item(s) ● Decontamination declaration (http://www.siemens.com/sc/declarationofdecontamination) With this declaration you warrant "that the device/replacement part has been carefully cleaned and is free of residues. The device/replacement part does not pose a hazard for humans and the environment."...
  • Page 137: Disposal

    Observe the specific regulations valid in your country. Further information about devices containing batteries can be found at: Information about battery / product return (WEEE) (https://support.industry.siemens.com/cs/document/109479891/) SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 138: Diagnosing And Troubleshooting

    Diagnosing and troubleshooting 10.1 Device status icons Icon Priority Level Meaning • Maintenance alarm • Measurement values are not valid • Maintenance warning: maintenance demanded immediately • Measured signal still valid • Maintenance required • Measured signal still valid • Process value has reached an alarm limit •...
  • Page 139: Fault Codes

    Adjust process conditions to minimize foam or other adverse conditions. • Correct configuration range. • If fault persists, contact your local Siemens rep- resentative. S: 2 Unable to collect profile because of a power condition Repair required: contact your local Siemens repre- that is outside the operating range of the device.
  • Page 140 • Inspect for heat-related damage and contact your local Siemens representative if repair is re- quired. • Fault code will persist until a manual reset is performed using SIMATIC PDM or the local dis- play.
  • Page 141 1. Voltage low at the LR560 modify wiring or increase source voltage according- 2. Hardware defect ly, see Typical connection drawing (Page 167). For 2: Repair required: contact your local Siemens representative. S: 95 Device error. Repair required: contact your local Siemens repre- NOTE: Fault text and icons appear only on the local sentative.
  • Page 142: Operation Troubleshooting

    10.3 Operation troubleshooting Operating symptoms, probable causes, and resolutions. Symptom Cause Action • Display shows level or target is out of range check specifications • check LOW CALIBRATION POINT (2.3.1.) (Page 101). • increase CONFIDENCE (2.7.6.1) (Page 112). • Display shows material build-up on antenna Use the air purge feature to clean the antenna •...
  • Page 143: Communication Troubleshooting

    Try pressing Mode to put the device into PROGRAM mode. If you continue to experience problems, go to our website (www.siemens.com/LR560) and check the FAQs for SITRANS LR560, or contact your Siemens representative. SITRANS LR560 with mA/HART...
  • Page 144: Technical Data

    Technical data Note Device specifications Siemens makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. 11.1 Power Nominal 24 V DC at 550 Ohm loop resistance . For other configurations, refer to Loop Power (Page 167).
  • Page 145: Construction

    11.3 Construction Process connection: Universal flat-faced flange 3"/80 mm, 4"/100 mm, 6"/150 mm Material: 316L (1.4404 or 1.4435), or 304 stainless steel Aimer flange 3"/80 mm, 4"/100 mm, 6"/150 mm Material: Polyurethane powder-coated cast aluminum Universal stamped 3"/80 mm, 4"/100 mm, 6"/150 mm flange Material: 304 stainless steel Enclosure...
  • Page 146: Process

    Reference operating conditions according to IEC 60770-1 Ambient temperature 15 to 25 °C (59 to 77 °F) Humidity 45 to 75% relative humidity Ambient pressure 860 to 1060 mbar a (86000 to 106000 N/m 11.5 Process Temperature and pressure Note Pressure Universal stamped flanges are to be used for 0.5 bar max pressure only.
  • Page 147: Approvals Data

    11.6 Approvals data Note Approvals The device label lists the approvals that apply to your device. General , FM, CE, RCM US/C Radio Europe (RED), FCC, Industry Canada Hazardous Non- Europe/International ATEX II 3G Ex nA/nL IIC T4 Gc sparking/Energy Brazil INMETRO: DNV 12.0085 X Limited...
  • Page 148: Programmer (Infrared Keypad)

    Year 2014: Alpha code = E Year 2020: Alpha code = M Year 2015: Alpha code = F Siemens Milltronics Infrared IS (Intrinsically Safe) Handheld Programmer for hazardous and all other locations (battery is non-replaceable). Approvals FM/CSA Class I, II, III, Div. 1, Gr. A to G T6 ATEX 1 GD Ex ia op is IIC T4 Ga Ex ia op is IIIC T135°C Da...
  • Page 149: Dimension Drawings

    Dimension drawings 12.1 SITRANS LR560 with stainless steel universal flat-faced flange Note Bolt hole patterns and dimensions Refer to Universal slotted flange (Page 153) for bolt hole patterns and dimensions. Dimensions are in mm (inch) ① ⑧ lid lock height: 176 (6.93) ②...
  • Page 150: Sitrans Lr560 With 3" Aimer Flange

    12.2 SITRANS LR560 with 3" aimer flange Note Bolt hole patterns and dimensions Refer to Universal slotted flange (Page 153) for bolt hole patterns and dimensions. Dimensions are in mm (inch) ① ⑦ lid lock device label ② ⑧ cable gland height: 166.1 (6.54) ③...
  • Page 151: Sitrans Lr560 With 4" And 6" Aimer Flange

    12.3 SITRANS LR560 with 4" and 6" aimer flange Note Bolt hole patterns and dimensions Refer to Universal slotted flange (Page 153) for bolt hole patterns and dimensions. Dimensions are in mm (inch) ① ⑧ lid lock 166.1 (6.54) ② ⑨...
  • Page 152: Sitrans Lr560 With Stamped Flange

    12.4 SITRANS LR560 with stamped flange Note Bolt hole patterns and dimensions Refer to Stamped flange (Page 155) for bolt hole patterns and dimensions. Dimensions in mm (inch) ① ⑥ lid lock 110 (4.33) ② ⑦ cable gland flange OD: 2": 200 (7.87) 3": 234 (9.21) 6": 290 (11.42)
  • Page 153: Universal Slotted Flange

    12.5 Universal slotted flange Note Bolting and gasket materials The user is responsible for the selection of bolting and gasket materials which will fall within the limits of the flange and its intended use and which are suitable for the service conditions. ①...
  • Page 154 Slotted flange dimensions and aimer Pipe size Flange O.D. Thickness Bolt hole Bolt hole Bolt hole No. of circle min Ø circle max Ø radius slotted holes 3 (80) 7.87 (200) 0.38 (9.65) 6.30 (160) 5.91 (150) 0.37 (9.5) 4 (100) 9.00 (229) 0.38 (9.65) 7.52 (191)
  • Page 155: Stamped Flange

    12.6 Stamped flange ① ④ bolt hole circle min. diameter flange OD ② ⑤ bolt hole radius thickness ③ ⑥ bolt hole circle max. diameter section A-A Stamped flange dimensions Pipe size Flange O.D. Thickness Bolt hole Bolt hole Bolt hole No.
  • Page 156: Process Connection Label (Pressure Rated Versions)

    12.7 Process connection label (pressure rated versions) For pressure-rated versions only, the process connection label lists the following information: Item Sample Text Comments/Explanation CONNECTION SERIES ASME B16.5 / EN 1092-1/ JIS B Flange Series: dimensional 2220 pattern based on ASME B16.5/EN 1092-1/JIS B 2 220 flange standards NOM.
  • Page 157: Technical Reference

    (distance from sensor reference point to the material surface), or Space (distance from high calibration point to the material surface). Echo processing A.3.1 Process Intelligence The signal processing technology embedded in Siemens radar level devices is known as Process Intelligence. SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 158: Echo Selection

    Process intelligence provides high measurement reliability regardless of the dynamically changing conditions within the vessel being monitored. The embedded Process Intelligence dynamically adjusts to the constantly changing material surfaces within these vessels. Process Intelligence is able to differentiate between the true microwave reflections from the surface of the material and unwanted reflections being returned from obstructions such as seam welds or supports within a vessel.
  • Page 159 The device characterizes all echoes that rise above the TVT as potential good echoes. Each peak is assigned a rating based on its strength, area, height above the TVT, and reliability, amongst other characteristics. ALGORITHM (2.7.3.1) (Page 109) The true echo is selected based on the setting for the Echo selection algorithm. For a list of options, see ALGORITHM (2.7.3.1) (Page 109).
  • Page 160: Clef Range (2.7.3.4.)

    ① default TVT ② material echo ③ vessel bottom echo selected ④ echo marker Example: CLEF enabled Vessel height: 1.5 m; CLEF range set to 0.5 m ① default TVT ② material echo selected ③ vessel bottom echo ④ echo marker A.3.3 CLEF RANGE (2.7.3.4.) Determines the level below which the CLEF algorithm will be used.
  • Page 161: Echo Threshold (2.7.3.2.)

    A.3.4 ECHO THRESHOLD (2.7.3.2.) CONFIDENCE (2.7.6.1) (Page 112) describes the quality of an echo. Higher values represent higher quality. Echo Threshold defines the minimum confidence value required for an echo to be accepted as valid and evaluated. A.3.5 ECHO LOCK (2.7.4.1.) If the echo selected by ALGORITHM (2.7.3.1) (Page 109) is within the Echo Lock window, the window is centered about the echo, which is used to derive the measurement.
  • Page 162 Example before Auto False Echo Suppression ① default TVT ② false echo ③ material echo ④ sensor reference point ⑤ High Cal. Pt = 1 m ⑥ obstruction at 13 m ⑦ material level at 31 m ⑧ Low Cal. Pt. = 45 m Example after Auto False Echo Suppression Auto False Echo Suppression...
  • Page 163: Measurement Range

    A.3.7 Measurement range NEAR RANGE (2.7.1.) (Page 108) Near Range programs SITRANS LR560 to ignore the zone in front of the antenna. The default blanking distance is 27.8 cm (0.91 ft) from the sensor reference point. Near Range allows you to increase the blanking value from its factory default. But SHAPER MODE (2.8.4) (Page 114) is generally recommended in preference to extending the blanking distance from factory values.
  • Page 164: Damping

    A.3.9 Damping DAMPING FILTER (2.2.3.) (Page 101) smooths out the response to a sudden change in level. This is an exponential filter and the engineering unit is always in seconds. In 5 time constants the output rises exponentially: from 63.2% of the change in the first time constant, to almost 100% of the change by the end of the 5th time constant.
  • Page 165: Current Output Function

    You also have the option to put the device out of service, in which case the device defaults to Fail-safe mode, and the reported level depends on the device type. A standard device reports the last valid reading, and a NAMUR NE 43-compliant device reports the user- defined value for Material Level (3.58 mA by default).
  • Page 166: Fail-Safe Mode

    A.4.4 Fail-safe Mode The purpose of the Fail-safe setting is to put the process into a safe mode of operation in the event of a fault or failure. The value to be reported in the event of a fault is selected so that a loss of power or loss of signal triggers the same response as an unsafe level.
  • Page 167: Loop Power

    ① ambient temperature –40 °C to 80 °C (–40 °F to 176 °F) ② process temperature: –40 to +100 °C (–40 to +212 °F) or –40 to +200 °C (–40 to +392 °F) depending on the version Loop Power A.6.1 Typical connection drawing Note Loop voltage is the voltage at the terminals of the power supply (not the voltage at the...
  • Page 168: Startup Behavior

    A.6.2 Startup behavior ● The device draws less than 3.6 mA at startup. ● Time to first measurement is 60 seconds nominal. A.6.3 Loop voltage versus loop resistance ① Operation - with HART SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 169: Hart Communications

    The radar device can be configured over the HART network using either the HART Communicator 375 by Fisher-Rosemount, or a software package. The recommended software package is the SIMATIC Process Device Manager (PDM) by Siemens. This device supports HART communication protocol. Signals are processed using Process Intelligence which has been field-proven in over 1,000,000 applications worldwide (ultrasonic and radar).
  • Page 170: Hart Communicator 375 Menu Structure

    HART Communicator 375 Menu Structure Note HART Communicator 375 is supported by SITRANS LR560 HART. The menu structure is aligned with the menu structure of SIMATIC PDM. SITRANS LR560 1 Configure/Setup 1 Identification 1 Identification 1 Long Tag 2 Tag 3 Descriptor 4 Message 5 Date...
  • Page 171 9 Device Image 2 Step 2 - Application 1 Application Type Steel Silo Concrete Silo 2 Operation Level Space Distance 3 Step 3 - Ranges 1 Unit 2 Low Calibration Point (X) 3 High Calibration Point (Y) 4 Response Rate 5 Tank Image 4 Step 4 - Summary 1 Identification...
  • Page 172 1 Self Test 2 Loop Test 3 Device Status Icon 4 Setup 1 Sensor 1 General 1 Unit 2 Sensor Mode 3 Damping filter 2 Calibration 1 Low Calibration Point (X) 2 High Calibration Point (Y) 3 Sensor Offset 3 Rate 1 Response Rate 2 Fill Rate per Minute 3 Empty Rate per Minute...
  • Page 173 1 Echo Lock 2 Sampling Up 3 Sampling Down 4. Echo Lock Window 4 Echo Quality 1 Confidence 2 Echo Strength 5 Filtering 1 Narrow Echo Filter 2 Reform Echo 6 Device Status Icon 2 TVT 1 TVT Setup 1 Auto False EchoSuppression 2 Auto False EchoSuppression Range 3 Hover Level 4 Shaper Mode...
  • Page 174 1 Lifetime (Expected) 2 Time in Operation 3 Remaining Lifetime 4 Activation of Reminders 5 Reminder 1 before Lifetime (Required) 6 Reminder 2 before Lifetime (Demanded) 7 Sensor Replaced 8 Snooze for 1 Year 9 Device Status Icon 3 Service Schedule 1 Service Interval 2 Time Since Last Service 3 Time Until Next Service...
  • Page 175 1 Manufacturer 2 Dev ID 3 Product Name 4 Fld dev rev 5 EDD Revision 1 6 Universal Command Revision 7 Device Status Icon 7 Security 1 Remote Access 1 Write Protection 2 Local Access 1 Local Operation Enable 3 Device Status Icon 2 Device Diagnostics 1 Device Status 1 Device status...
  • Page 176: Hart Version

    HART Multidrop Mode allows the connection of multiple field devices via HART. Details on the use of Multidrop Mode are outlined in an application guide Working with HART, which can be downloaded from the product page of our website (www.siemens.com/LR560). Go to Support and click on Application Guides.
  • Page 177: Certificates And Support

    In addition to our documentation, Siemens provides a comprehensive support solution at: ● Services & Support (http://www.siemens.com/automation/service&support) Personal contact If you have additional questions about the device, please contact your Siemens personal contact at: ● Partner (http://www.automation.siemens.com/partner) To find the personal contact for your product, go to "All Products and Branches" and select "Products &...
  • Page 178: Certificates

    Certificates You can find certificates on the Internet at LR560 (www.siemens.com/LR560) or on an included DVD. SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 179: Hmi Menu Structure

    HMI menu structure HMI menu 1. WIZARDS 1.1. QUICK START WIZ. VESSEL RESPONSE RATE UNITS OPERATION LOW CALIB. PT. HIGH CALIB. PT. 1.2. AFES WIZ. 1.3. CPY PARAMETERS TO DISP 1.4. CPY PARAMETERS FROM DISPLAY 1.5. CPY FIRMWARE TO DISPLAY 1.6.
  • Page 180 2.3.1. LOW CALIB. PT. 2.3.2. HIGH CALIB. PT. 2.3.3. SENSOR OFFSET 2.4. RATE 2.4.1. RESPONSE RATE 2.4.2. FILL RATE PER MINUTE 2.4.3. EMPTY RATE PER MINUTE 2.5. FAIL-SAFE 2.5.1. MAT. LEV. 2.5.2. TIMER 2.5.3. LEVEL 2.6. ANALOG OUTPUT SCALE 2.6.1. CURRENT OUTPUT FUNCTION 2.6.2.
  • Page 181 2.8. TVT SETUP 2.8.1. AUTO ECHO SUPP. 2.8.2. AUTO SUPP. RANGE 2.8.3. HOVER LEVEL 2.8.4. SHAPER MODE 2.9. TVT SHAPER 2.9.1. BREAKPOINT 1-9 2.9.2. BREAKPOINT 10-18 2.9.3. BREAKPOINT 19-27 2.9.4. BREAKPOINT 28-36 2.9.5. BREAKPOINT 37-45 2.9.6. BREAKPOINT 46-54 2.9.7. BREAKPOINT 55-63 2.9.8.
  • Page 182 3.6.1. TIME IN OPER. 3.6.2. REMAIN. LIFETIME 3.6.3. REMIND. 1 (REQ.) 3.6.4. REMIND. 2 (DEM.) 3.6.5. REMINDER ACTIVATION 3.6.6. LIFETIME EXPECTED 3.6.7. MAINT. STAT. 3.6.8. ACK. STATUS 3.6.9. ACK. 3.7. REMAIN. SENS LIFE 3.7.1. TIME IN OPER. 3.7.2. REMAIN. LIFETIME 3.7.3.
  • Page 183 4.8.4. REMIND 2 (DEM.) 4.8.5. REMINDER ACTIVATION 4.8.6. CALIB. INTERVAL 4.8.7. MAINT. STATUS 4.8.8. ACK. STATUS 4.8.9. ACK. 4.9. STORED SW VER. 5. COMMUNICATION 5.1 DEVICE ADDRESS 5.2 REMOTE LOCKOUT 6. SECURITY 6.1 WRITE PROTECTION 7. LANGUAGE SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 184: List Of Abbreviations

    List of abbreviations List of abbreviations Short form Long form Description Units CE / FM / CSA Conformité Européenne / Factory Mu- safety approval tual / Canadian Standards Association Distributed Control System control room apparatus dielectric constant Electronic Device Description Electrostatic Discharge FMCW Frequency Modulated Continuous...
  • Page 185: Glossary

    Glossary accuracy degree of conformity of a measure to a standard or a true value. algorithm a prescribed set of well-defined rules or processes for the solution of a problem in a finite number of steps. ambient temperature the temperature of the surrounding air that comes in contact with the enclosure of the device. antenna an aerial which sends out and receives a signal in a specific direction.
  • Page 186 capacitance the property of a system of conductors and dielectrics that permits the storage of electricity when potential differences exist between the conductors. Its value is expressed as the ratio of a quantity of electricity to a potential difference, and the unit is a Farad. confidence see Echo Confidence.
  • Page 187 Echo Lock Window a window centered on an echo in order to locate and display the echo’s position and true reading. Echoes outside the window are not immediately processed. Echo Marker a marker that points to the processed echo. Echo Processing the process by which the radar unit determines echoes.
  • Page 188 microwaves the term for the electromagnetic frequencies occupying the portion of the radio frequency spectrum from 1 GHz to 300 GHz. Near Blanking see Blanking. nozzle a length of pipe mounted onto a vessel that supports the flange. parameters in programming, variables that are given constant values for specific purposes or processes. polarization the property of a radiated electromagnetic wave describing the time-varying direction and amplitude of the electric field vector.
  • Page 189 repeatability the closeness of agreement among repeated measurements of the same variable under the same conditions. shot one transmit pulse or measurement. TVT (Time Varying Threshold) a time-varying curve that determines the threshold level above which echoes are determined to be valid. SITRANS LR560 with mA/HART Operating Instructions, 08/2019, A5E34647946-AF...
  • Page 190: Index

    Index Device Address setting via LUI, 49 Device Description (DD) see EDD, 50 Abbreviations and identifications list, 184 device status Activating, 36 view via PDM, 66 AMS Device Manager Device Status features, 68 icons, 138 analog output Disassembly, 27 select, 63 Disposal, 137 simulate via PDM, 63 Documentation, 177...
  • Page 191 Index Modifications correct usage, 13 HART Communication improper, 13 set preambles, 65 Mounting HART Communications beam angle, 23 details, 169 nozzle location, 23 Hazardous area Laws and directives, 14 Qualified personnel, 16 Hotline, (Refer to Support request) Near Range explanation, 163 Nozzle location Shaper Mode, 23 Identifications and abbreviations...
  • Page 192 Index Response Rate test explanation, 163 loop test, 64 Return procedure, 136 Test certificates, 14 trend view trend line, 66 troubleshooting communication, 143 Scan device Troubleshooting synchronize parameters via AMS, 70 operation, 142 Scope of delivery, 11 TVT (time varying threshold) security explanation, 158 password protection via AMS, 85...

This manual is also suitable for:

Sitrans lr560

Table of Contents