Quick Start Guide
00825-0600-4410, Rev BH
October 2024
Emerson Wireless 1410S Gateway

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rosemount 1410S and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Emerson Rosemount 1410S

  • Page 1 Quick Start Guide 00825-0600-4410, Rev BH October 2024 Emerson Wireless 1410S Gateway...
  • Page 2 October 2024 Safety messages NOTICE This guide provides basic guidelines for the Emerson Wireless 1410S Gateway. It does not provide instructions for diagnostics, maintenance, service, or troubleshooting. Refer to the Emerson Wireless 1410S Gateway and 781S Smart Antenna Reference Manual for more information and instructions.
  • Page 3: Table Of Contents

    The Wireless 1410S Gateway contains no user serviceable components. If the device is not functioning properly, see the Troubleshooting section in the Emerson Wireless 1410S Gateway and 781S Smart Antenna Reference Manual. If these troubleshooting steps do not resolve the problem, contact the factory.
  • Page 4 Quick Start Guide October 2024 www.Emerson.com...
  • Page 5: Wireless Planning

    Quick Start Guide 1  Wireless planning For detailed guidance on WirelessHART network planning, see ® Emerson white paper System Engineering Guidelines IEC 62591 WirelessHART. 1.1  Power up sequence Ensure the gateway is operational before installing power modules in wireless devices and activate devices starting with those closest to the gateway for an efficient network setup.
  • Page 6: Personal Computer (Pc) Requirements

    Configure the gateway through a secure web interface. Recent versions of the following browsers are supported: • Google Chrome • Mozilla Firefox • Microsoft Edge 2.3  Hard disk space • AMS Wireless Configurator: 1.5 GB • Gateway Setup CD: 250 MB www.Emerson.com...
  • Page 7: Initial Connection And Configuration

    Never connect the antenna terminals directly to a power supply. For the 1410S1, the antenna terminals are located on the top of the device. For the 1410S2, after opening the cover, the antenna terminals are located on the left side of the device. www.Emerson.com...
  • Page 8 The conduit/cable entries in the transmitter housing use a ½–14 NPT thread form. When installing in a hazardous location, use only appropriately listed or Ex-certified plugs, glands, or adapters in cable/ conduit entries. Ensure external conduit/cable fittings are Type 4X rated or better (C22.2 No 94.2/UL 50E requirement). www.Emerson.com...
  • Page 9 E. Ethernet port 2. When this port is activated, the factory IP address 192.168.2.10 F. 1410S power and serial connections G. 781S power terminals H. 781S data terminals I. 10.5 to 30 Vdc power input J. Serial Modbus ® K. 781S antenna terminals (two) L. 1410S power terminal www.Emerson.com...
  • Page 10: Establishing A Connection

    Ethernet cable. For DeltaV Ready Gateways, commission the gateway to the DeltaV system first. Proceed to Change usernames and passwords for updating user information. Skip Configure the gateway using Windows through Configure the gateway for a DeltaV Ready ™ Gateway. www.Emerson.com...
  • Page 11 Internet protocol (IP) address and subnet mask of the connected network interface. Procedure 1. Select the Network icon in the lower right corner of the Windows 10 workspace. 2. Select Network & Internet settings. WiFi Connections menu Figure 3-3: www.Emerson.com...
  • Page 12 Quick Start Guide October 2024 3. Select Change adapter options. Network & Internet Settings Figure 3-4: 4. Right click the network interface connection that the gateway is plugged into, and select Properties. www.Emerson.com...
  • Page 13 Ethernet 4 Properties Figure 3-5: Note If the personal computer (PC)/laptop is from another network, record the current IP address and other settings so the PC/ laptop can be returned to the original network after the gateway has been configured. www.Emerson.com...
  • Page 14 9. Select OK for both the Internet Protocol Version 4 (TCP/IPv4) Properties window and the Local Area Connection Properties window. Note Connecting to the gateway's secondary Ethernet port will require different network settings. Table 3-1: Network settings Ethernet Gateway PC/laptop/ Subnet tablet 192.168.1.10 192.168.1.11 255.255.255.0 192.168.2.10 192.168.2.11 www.Emerson.com...
  • Page 15: Disable Proxies

    This procedure may be necessary when using a Chrome browser with Windows operating systems. Procedure 1. Open web browser. 2. Navigate to Settings → Advanced. 3. Go to System → Open proxy settings. Example Proxy settings menu. Figure 3-7: Only use if a proxy is needed. www.Emerson.com...
  • Page 16: Configure The Gateway

    Figure 3-8: Username and Password 2. Navigate to System Settings → Gateway → Ethernet Communication to enter the network settings. a) Configure a static Internet protocol (IP) address or select Obtain an IP address from DHCP server and enter a Host Name. www.Emerson.com...
  • Page 17 Procedure 1. Navigate to System Settings → Users → User Accounts to change passwords and add users with the following steps. www.Emerson.com...
  • Page 18 User Accounts page Figure 3-10: Navigating to NOTICE Emerson strongly suggests changing passwords before installing the gateway for full use. NOTICE Lost passwords cannot be recovered. Clearing all user settings with a factory reset is the only way to regain access to a gateway with no known credentials.
  • Page 19: Physical Installation

    Before installation, verify if local codes require a permit and/or an inspection before energizing. When planning the installation, account for routing the antenna cable within the enclosure. www.Emerson.com...
  • Page 20 Quick Start Guide October 2024 NOTICE Do not mount the antenna within a metal enclosure. To avoid damage to sensitive RF components, do not remove protective cap from the gateway SMA connector until ready to install the antenna. www.Emerson.com...
  • Page 21 October 2024 Quick Start Guide Figure 4-1: 1410S1 mounting www.Emerson.com...
  • Page 22 1. Insert one U-bolt around the pipe, through the top mounting holes of the gateway mounting plate, and through the washer plate. 2. Use a ½-inch wrench to fasten the nuts to the U-bolt. 3. Repeat for the second U-bolt and the lower mounting holes. Figure 4-2: 1410S2 mounting www.Emerson.com...
  • Page 23 Four appropriate fasteners for preferred mounting method • Mounting plate (supplied with gateway) • Drill (not supplied) • Wrench (not supplied) Procedure Install gateway into surface as shown in Figure 4-3. Screws shown as example. Figure 4-3: 1410S2 surface mounting www.Emerson.com...
  • Page 24 NOTICE The 1410S2 Gateway has a single screw that secures the hinged lid in place. Applying torque greater than 7 in.-lb. to this screw may permanently damage the housing. Install the screw to a torque specification of 7 in.-lb. www.Emerson.com...
  • Page 25 Procedure 1. Strip the insulation back a minimum of 0.14 in. (4 mm). 2. Attach positive and negative wires to appropriate terminals on gateway. See wiring diagrams in Figure 4-4 Figure 4-5. www.Emerson.com...
  • Page 26 If you ordered the 781S without a cable, or if you need a longer cable, see the following cable guidelines. If you are using a legacy 781S, Emerson provides the antenna with 30 ft. (9 m) of Belden 3084a cable prewired into the 781S housing.
  • Page 27 J. 781S terminal 2 power and data connections K. 781S RS-485 comm input L. 781S power input M. Tape back 781S cabling shield wire and foils at 781S side N. Connect 781S cabling shield wire at 1410S shield terminal terminal) www.Emerson.com...
  • Page 28 1410S2 Gateway hardware revision 1.0.0 configured with intrinsically safe outputs option A can only be powered by 24 Vdc power source. Check label to verify hardware revision. Second antenna can be connected to terminal 2. Wiring is same as terminal 1 antenna. www.Emerson.com...
  • Page 29 Table 4-1: 1410S LED indicator descriptions Green LED1- Power is connected, and Gateway is running. Power gateway is booting up. (Flashing Blue: Gateway Defaults DIP switch is flipped to ON position. LED will be red during boot, then flashing blue after boot is completed.) www.Emerson.com...
  • Page 30 Ground the gateway's enclosure case in accordance with national and local electrical codes using either the internal or external grounding provisions. The most effective grounding method is a direct connection to earth ground with minimal impedance. Connect the ground with a www.Emerson.com...
  • Page 31: Terminating Resistors

    Always make sure cable is rated for ambient temperature of the end installation. 4.5  Terminating resistors Emerson provides three DIP switches to enable termination and biasing resistors to the serial Modbus connection. ® Emerson Wireless 1410S Gateway and 781S Smart Antenna Reference Manual for more information.
  • Page 32: Software Installation (Optional)

    Install Security Setup Utility (only required for secure host connections or OPC-DA communications) and AMS Wireless Configurator as needed. See Emerson Wireless 1410S Gateway and 781S Smart Antenna Reference Manual for further information. The gateway firmware needs to be compatible with host connections being made.
  • Page 33: Verify Operation

    Network ID and Join Key that can be found on the gateway’s Network Settings page. 3. Verify field devices are joined to the network and displayed on the Devices page of the gateway web interface. 4. Verify host system is receiving field device data. www.Emerson.com...
  • Page 34: Product Certifications

    Quick Start Guide October 2024 7  Product certifications 7.1  Emerson Wireless 1410S1 Gateway Rev: 1.6 7.1.1  European Directive information A copy of the EC Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EC Declaration of Conformity can be found at Emerson.com.
  • Page 35 1. Installed as per control drawing 01410-1300 for Hazardous and Non-Hazardous areas. Installé conformément au dessin de contrôle 01410-1300 pour les zones dangereuses et non dangereuses. 2. Installation “ic”, Um has been defined as 30 Vdc. The 1410S1 can only be supplied with a SELV/PELV power supply. www.Emerson.com...
  • Page 36 3. The 1410S1 must be installed in an external IP54 complying to the requirements of EN IEC 60079-0: 2018. 7.1.7  IECEx N7 IECEx Zone 2 with Intrinsically Safe Outputs IECEx CSAE 22.0044X Certificate IEC 60079-0: 2017, IEC 60079-7: 2015, IEC Standards 60079-11: 2011 www.Emerson.com...
  • Page 37 ≤ +70 °C) Temperature code Special Conditions for Safe Use (X): See Certificate for Specific Conditions for Safe Use. 7.1.10  Korea NP Zone 2 with intrinsically safe outputs 23-KA4BO-0332X, 23-KA4BO-0334X Certificate Ex ec [ia Ga] IIC T4 Gc X 1410S1A www.Emerson.com...
  • Page 38 Ex ec [ic] IIC T4 Gc X; Ex ec [ic IIIC Dc] IIC T4 Gc X; 1410S1B T4 (-40 °C ≤ Ta ≤ 70 °C) Temperature code Special Conditions for Safe Use (X): See certificate for specific conditions for safe use. www.Emerson.com...
  • Page 39 (RF) spectrum. Nearly every country requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage.
  • Page 40 (-40 °C ≤ T ≤ +65 °C ) Temperature code Conditions of Acceptability (X): 1. Installed as per control drawing 01410-1300 for Hazardous and Non-Hazardous areas. Installé conformément au dessin de contrôle 01410-1300 pour les zones dangereuses et non dangereuses. www.Emerson.com...
  • Page 41 22UKEX1224X, CSAE 22UKEX1307X EN IEC 60079-0: 2018, EN IEC 60079-7: 2015+A1: Standards 2018, EN 60079-11: 2012, EN 60079-31: 2014 1410S2A: II 3(1G) D Ex tc [ia IIC Ga] IIIC T90 °C Dc 3(2)D Ex tc [ia Db] IIIC T90 Dc www.Emerson.com...
  • Page 42 Ex tc [ia IIC Ga] IIIC T90 Dc, Ex tc [ia Db] IIIC T90 1410S2A Ex tc [ic IIC Gc] IIIC T90 Dc, Ex tc [ic] IIIC T90 Dc 1410S2B (-40 °C ≤ T ≤ +65 °C) Temperature code www.Emerson.com...
  • Page 43 ABNT NBR IEC 60079-0: 2013, ABNT NBR IEC 60079-7: Standards 2008, ABNT NBR IEC 60079-11: 2013, ABNT NBR IEC 60079-15: 2012, ABNT NBR IEC 60079-31: 2014 Special Conditions for Safe Use (X): See Certificate for Specific Conditions for Safe Use. www.Emerson.com...
  • Page 44 T4 Gc X, Ex tc [ic IIC Gc] IIIC T90 Dc X, Ex tc [ic] IIIC T90 Dc X (-40 °C ≤ T ≤ +65 °C) Temperature code Special Conditions for Safe Use (X): See Certificate for Specific Conditions for Safe Use. 7.2.12  China N3 Type N GYJ21.1110X (CCC 认证) 证书: www.Emerson.com...
  • Page 45 IIC Ga] IIIC T90 °C Dc, Ex tc [ia Db] IIIC T90 °C Dc, Ex ec [ic] IIC T4 Gc, Ex ec [ic IIIC Dc] IIC T4 Gc, Ex tc [ic IIC Gc] IIIC T90 °C Dc, Ex tc [ic] IIIC T90 °C Dc www.Emerson.com...
  • Page 46: Declaration Of Conformity

    Quick Start Guide October 2024 8  Declaration of Conformity www.Emerson.com...
  • Page 47 October 2024 Quick Start Guide www.Emerson.com...
  • Page 48 2024 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.