Configuration Parameters – Module (Page 1)
101
Contrast
0 (%)
118
Use Module Charge Alt
102
Fast Loading Enabled
On (1), Off (0)
119
Disable CAN Speed Control
103
All Warnings Latched
On (1), Off (0)
120
CT Position
104
Lamp Test At Startup
On (1), Off (0)
121
Generator Voltage Display
105
Power Save Mode Enable On (1), Off (0)
122
Mains Voltage Display
106
RESERVED
123
Generator Frequency Display On (1), Off (0)
107
RESERVED
124
Mains Frequency Display
108
Event Log Display Format On (1), Off (0)
125
Current Display
109
Power Up Mode
0 (Power Up Mode)
126
kW Display
110
DTC String Enable
On (1), Off (0)
127
kVAr Display
111
RESERVED
128
kVA Display
Pin Protected
112
On (1), Off (0)
129
pf Display
Maintenance Reset
113
Stop Button Cooldown
On (1), Off (0)
130
kWh Display
114
Use Module Oil Pressure
On (1), Off (0)
131
kVArh Display
115
Use Module Coolant Temp On (1), Off (0)
132
kVAh Display
116
Use Module Engine Hours On (1), Off (0)
133
Hold Start Button to Crank
117
Use Module RPM
On (1), Off (0)
Configuration Parameters – CAN Application (Page 2)
201
CAN Alternative Engine Speed
On (1), Off (0)
203
CAN ECU Data Fail Action
202
CAN ECU Data Fail Enable
On (1), Off (0)
204
CAN ECU Data Fail Delay
Configuration Parameters – Digital Inputs (Page 3)
301
Digital Input A Source
302
Digital Input A Polarity
303
Digital Input A Action (If Source = User Config)
304
Digital Input A Arming (If Source = User Config)
305
Digital Input A Activation Delay (If Source = User Config)
306
Digital Input B Source
307
Digital Input B Polarity
308
Digital Input B Action (If Source = User Config)
309
Digital Input B Arming (If Source = User Config)
310
Digital Input B Activation Delay (If Source = User Config)
311
Digital Input C Source
312
Digital Input C Polarity
313
Digital Input C Action (If Source = User Config)
314
Digital Input C Arming (If Source = User Config)
315
Digital Input C Activation Delay (If Source = User Config)
316
Digital Input D Source
317
Digital Input D Polarity
318
Digital Input D Action (If Source = User Config)
319
Digital Input D Arming (If Source = User Config)
320
Digital Input D Activation Delay (If Source = User Config)
321
Digital Input E Source
322
Digital Input E Polarity
323
Digital Input E Action (If Source = User Config)
324
Digital Input E Arming (If Source = User Config)
325
Digital Input E Activation Delay (If Source = User Config)
326
Digital Input F Source
327
Digital Input F Polarity
328
Digital Input F Action (If Source = User Config)
329
Digital Input F Arming (If Source = User Config)
330
Digital Input F Activation Delay (If Source = User Config)
331
Analogue Input A (Set As Digital) Source
332
Analogue Input A (Set As Digital) Polarity
333
Analogue Input A (Set As Digital) Action (If Source = User Config)
334
Analogue Input A (Set As Digital) Arming (If Source = User Config)
335
Analogue Input A (Set As Digital) Activation Delay (If Source = User Config)
336
Analogue Input B (Set As Digital) Source
337
Analogue Input B (Set As Digital) Polarity
338
Analogue Input B (Set As Digital) Action (If Source = User Config)
339
Analogue Input B (Set As Digital) Arming (If Source = User Config)
340
Analogue Input B (Set As Digital) Activation Delay (If Source = User Config)
341
Analogue Input C (Set As Digital) Source
342
Analogue Input C (Set As Digital) Polarity
343
Analogue Input C (Set As Digital) Action (If Source = User Config)
344
Analogue Input C (Set As Digital) Arming (If Source = User Config)
345
Analogue Input C (Set As Digital) Activation Delay (If Source = User Config)
346
Analogue Input D (Set As Digital) Source
347
Analogue Input D (Set As Digital) Polarity
348
Analogue Input D (Set As Digital) Action (If Source = User Config)
349
Analogue Input D (Set As Digital) Arming (If Source = User Config)
350
Analogue Input D (Set As Digital) Activation Delay (If Source = User Config)
Pressure Sensor List
Temperature Senor List
Index
Type
Index
Type
0
Not used
0
Not Used
1
Dig Closed for Alarm
1
Dig Closed for Alarm
2
Dig Open for Alarm
2
Dig Open for Alarm
3
VDO 5 Bar
3
VDO 120 °C
4
VDO 10 Bar
4
Datcon High
5
Datcon 5 Bar
5
Datcon Low
6
Datcon 10 Bar
6
Murphy
7
Datcon 7 Bar
7
Cummins
8
Murphy 7 Bar
8
PT100
9
CMB812
9
Veglia
10
Veglia
10
Beru
11
User Defined
11
User Defined
Configuration Parameters – Outputs (Page 4)
On (1), Off (0)
401
Digital Output A Source
On (1), Off (0)
402
Digital Output A Polarity
Gen (0), Load(1)
403
Digital Output B Source
On (1), Off (0)
404
Digital Output B Polarity
On (1), Off (0)
405
Digital Output C Source
406
Digital Output C Polarity
On (1), Off (0)
Configuration Parameters – Timers (Page 5)
On (1), Off (0)
501
Mains Transient Delay
On (1), Off (0)
502
Start Delay
On (1), Off (0)
503
Preheat Timer
On (1), Off (0)
504
Crank Time
505
Crank Rest Time
On (1), Off (0)
506
Smoke Limiting
On (1), Off (0)
507
Smoke Limiting Off
On (1), Off (0)
508
Safety On Delay
On (1), Off (0)
509
Warm Up Time
On (1), Off (0)
Configuration Parameters – Generator (Page 6)
601
Alternator Fitted
602
Alternator Poles
0 (Action)
603
Under Voltage Shutdown Enable On (1), Off (0)
0 s
604
Under Voltage Trip Shutdown
605
Under Voltage Warning Enable
0 (Input Source)
606
Under Voltage Warning Trip
0 (Polarity)
607
RESERVED
0 (Action)
608
Loading Voltage
0 (Arming)
609
Over Voltage Warning Enable
0 s
610
Over Voltage Warning Return
0 (Input Source)
0 (Polarity)
611
Over Voltage Warning Trip
0 (Action)
612
Over Voltage Shutdown Trip
0 (Arming)
Under Frequency Shutdown
613
Enable
0 s
614
Under Frequency Shutdown Trip 0.0 Hz
0 (Input Source)
0 (Polarity)
Under Frequency Warning
615
Enable
0 (Action)
616
Under Frequency Warning Trip
0 (Arming)
617
RESERVED
0 s
618
Loading Frequency
0 (Input Source)
619
Nominal Frequency
0 (Polarity)
0 (Action)
Configuration Parameters – Mains (Page 7)
0 (Arming)
701
AC System
0 s
702
Mains Failure Detection
0 (Input Source)
703
Immediate Mains Dropout
0 (Polarity)
704
Under Voltage Enable
0 (Action)
705
Under Voltage Level
0 (Arming)
706
Under Voltage Return
0 s
707
Over Voltage Enable
0 (Input Source)
708
Over Voltage Return
0 (Polarity)
Configuration Parameters – Engine (Page 8)
0 (Action)
801
Start Attempts
0 (Arming)
802
Over Speed Overshoot
0 s
803
Over Speed Delay
0 (Input Source)
Gas Choke Timer
804
0 (Polarity)
(Gas Engine Only)
0 (Action)
Gas On Delay
805
0 (Arming)
(Gas Engine Only)
0 s
Gas Ignition Off Delay
806
0 (Input Source)
(Gas Engine Only)
0 (Polarity)
Crank Disconnect On Oil
807
0 (Action)
Pressure Enable
0 (Arming)
Check Oil Pressure Prior To
808
0 s
Starting
809
Crank Disconnect On Oil
0 (Input Source)
0 (Polarity)
810
Crank Disconnect On Frequency 0.0 Hz
0 (Action)
Crank Disconnect On Engine
811
Speed
0 (Arming)
0 s
812
Under Speed Enable
813
Under Speed Trip
0 (Input Source)
814
Over Speed Trip
0 (Polarity)
815
Low Battery Voltage Enable
0 (Action)
816
Low Battery Voltage Trip
0 (Arming)
0 s
817
Low Battery Voltage Return
Percentage Sensor List
818
Low Battery Voltage Delay
Index
Type
Sensor Type
0
Not Used
Index
Type
1
Dig Closed for Alarm
0
Percentage Sensor
2
Dig Open for Alarm
1
Pressure Sensor
3
VDO Ohm (10-180)
2
Temperature Sensor
4
VDO Tube (90-0)
5
US Ohm (240-33)
6
GM Ohm (0-90)
7
GM Ohm (0-30)
8
Ford (73-10)
9
User Defined
Functionality in DSE6010 and DSE6020 MKII
Functionality in DSE6020 MKII only
0 (Output Source)
407
Digital Output D Source
0 (Output Source)
0 (Output Polarity)
408
Digital Output D Polarity
0 (Output Polarity)
0 (Output Source)
409
Digital Output E Source
0 (Output Source)
0 (Output Polarity)
410
Digital Output E Polarity
0 (Output Polarity)
0 (Output Source)
411
Digital Output F Source
0 (Output Source)
0 (Output Polarity)
412
Digital Output F Polarity
0 (Output Polarity)
510
Return Delay
519
Delayed Load Output 2
511
Cooling Time
520
Delayed Load Output 3
512
ETS Solenoid Hold
521
Delayed Load Output 4
513
Failed To Stop Delay
522
Power Save Mode Delay
514
Generator Transient Delay
523
RESERVED
515
Transfer Time
524
Page Timer
516
Breaker Trip Pulse
525
Cooling Time at Idle
517
Breaker Close Pulse
526
Manual Crank Limit
518
Delayed Load Output 1
On (1), Off (0)
620
Over Frequency Warning Enable
On (1), Off (0)
0
621
Over Frequency Warning Return
0.0 Hz
622
Over Frequency Warning Trip
0.0 Hz
0 V
623
Over Frequency Shutdown Enable
On (1), Off (0)
On (1), Off (0)
624
Over Frequency Shutdown Trip
0.0 Hz
0 V
625
AC System
0 (Ac System)
626
CT Primary
0 A
0 V
627
Full Load Rating
0 A
On (1), Off (0)
628
Immediate Over Current Enable
On (1), Off (0)
Delayed Over Current Alarm
0 V
629
On (1), Off (0)
Enable
0 V
630
Delayed Over Current Alarm Action 0 (Action)
0 V
631
Over Current Delay Time
0 s
On (1), Off (0)
632
Over Current Trip
0 %
633
kW Rating
0 kW
On (1), Off (0)
634
Over kW Protection Enable
On (1), Off (0)
0.0 Hz
635
Over kW Protection Action
0 (Action)
636
Over kW Protection Trip
0 %
0.0 Hz
637
Over kW Protection Trip Delay
0 s
0.0 Hz
0 (AC System)
709
Over Voltage Level Trip
On (1), Off (0)
710
Under Frequency Enable
On (1), Off (0)
711
Under Frequency Trip
On (1), Off (0)
712
Under Frequency Return
0 V
713
Over Frequency Enable
0 V
714
Over Frequency Return
On (1), Off (0)
715
Over Frequency Trip
0 V
0
819
High Battery Voltage Enable
0 %
820
High Battery Voltage Return
0 s
821
High Battery Voltage Trip
High Battery Voltage Warning
0 s
822
Delay
0 s
823
Charge Alt Shutdown Enable
0 s
824
Charge Alt Shutdown Trip
On (1), Off (0)
825
Charge Alt Shutdown Delay
On (1), Off (0)
826
Charge Alt Warning Enable
0.00 Bar
827
Charge Alt Warning Trip
828
Charge Alt Warning Delay
0 RPM
829
Low Battery Start Arming
On (1), Off (0)
830
Low Battery Start Threshold
0 RPM
831
Low Battery Start Delay
0 RPM
832
Low Battery Start Run Time
On (1), Off (0)
833
Magnetic Pickup Fitted
0.0 V
834
Flywheel Teeth
Crank Disconnect On Oil Pressure
0.0 V
835
Delay
0:00:00
AC System
Digital Input Alarm Arming
Power Up Mode
Index
Type
Index
Arming
Index Mode
0
2 Phase 3 Wire (L1-L2)
0
Always
0
1
2 Phase 3 Wire (L1-L3)
1
From Safety On
1
2
3 Phase 3 Wire
2
From Starting
2
3
3 Phase 4 Wire
3
Never
4
3 Phase 4 Wire (Delta)
5
Single Phase 2 Wire
Configuration Parameters – Analogue Inputs (Page 9)
901
Low Oil Pressure Enable
902
Low Oil Pressure Trip
903
Oil Pressure Sender Open Circuit
904
Analogue Input A Sensor Usage
905
Analogue Input A Flexible Senor Type
906
Analogue Input A Sensor Selection
907
Flexible Sensor A Arming
908
Flexible Sensor A Low Alarm Action
909
Flexible Sensor A Low Alarm Trip
910
RESERVED
911
Flexible Sensor A Low Pre-Alarm Enable
912
Flexible Sensor A Low Pre-Alarm Trip
913
Flexible Sensor A Low Pre-Alarm Return
914
RESERVED
915
Flexible Sensor A High Pre-Alarm Enable
916
Flexible Sensor A High Pre-Alarm Return
917
Flexible Sensor A High Pre-Alarm Trip
918-919
RESERVED
920
Flexible Sensor A High Alarm Action
921
Flexible Sensor A High Alarm Trip
922
RESERVED
923
Analogue Input B Sensor Usage
924
Analogue Input B Sensor Selection
925
High Engine Temperature Trip
926
Temperature Sender Open Circuit
927
Analogue Input C Sensor Usage
928
Analogue Input C Flexible Senor Type
929
Analogue Input C Sensor Selection
930
Flexible Sensor C Arming
931
Flexible Sensor C Low Alarm Action
932
Flexible Sensor C Low Alarm Trip
933
RESERVED
934
Flexible Sensor C Low Pre-Alarm Enable
935
Flexible Sensor C Low Pre-Alarm Trip
936
Flexible Sensor C Low Pre-Alarm Return
937
RESERVED
938
Flexible Sensor C High Pre-Alarm Enable
939
Flexible Sensor C High Pre-Alarm Return
940
Flexible Sensor C High Pre-Alarm Trip
941-942
RESERVED
943
Flexible Sensor C High Alarm Action
0 V
944
Flexible Sensor C High Alarm Trip
On (1), Off (0)
945-946
RESERVED
0.0 Hz
947
Fuel Sensor C Low Shutdown Enable
0.0 Hz
948
Fuel Sensor C Low Shutdown Trip
On (1), Off (0)
949
Fuel Sensor C Low Shutdown Delay
0 Hz
950
Fuel Sensor C Low Pre-Alarm Enable
0.0 Hz
951
Fuel Sensor C Low Pre-Alarm Trip
952
Fuel Sensor C Low Pre-Alarm Return
953
Fuel Sensor C Low Pre-Alarm Delay
On (1), Off (0)
954
Fuel Sensor C High Pre-Alarm Enable
0.0 V
955
Fuel Sensor C High Pre-Alarm Return
0.0 V
956
Fuel Sensor C High Pre-Alarm Trip
957
Fuel Sensor C High Pre Alarm Delay
0 s
959
Fuel Sensor C High Alarm Action
960
Fuel Sensor C High Alarm Trip
On (1), Off (0)
961
Fuel Sensor C High Alarm Delay
962
Analogue Input D Sensor Usage
0.0 V
963
Analogue Input D Sensor Type
0 s
964
Analogue Input D Sensor Selection
965
Analogue Input D Sensor Signal
On (1), Off (0)
966
Flexible Sensor D Arming
967
Flexible Sensor D Low Alarm Enable
0.0 V
968
Flexible Sensor D Low Alarm Trip
0 s
969
RESERVED
On (1), Off (0)
970
Flexible Sensor D Low Pre-Alarm Enable
971
Flexible Sensor D Low Pre-Alarm Trip
0.0 V
972
Flexible Sensor D Low Pre-Alarm Return
0 s
973
RESERVED
0 s
974
Flexible Sensor D High Pre-Alarm Enable
On (1), Off (0)
975
Flexible Sensor D High Pre-Alarm Return
0
976
Flexible Sensor D High Pre-Alarm Trip
0 s
977-978
RESERVED
979
Flexible Sensor D High Alarm Action
980
Flexible Sensor D High Alarm Trip
981
RESERVED
982
Fuel Sensor Units
Stop
983
Fuel Tank Size
Manual
984
Fuel Pump Enable
Auto
985
Fuel Pump On Level
986
Fuel Pump Off Level
On (1), Off (0)
0 Bar
On (1), Off (0)
Digital Input (0), Flexible (1), Oil Pressure (3) Sensor
0 (Sensor Type)
0 (Pressure, Temperature, Percentage Sensor List)
0 (Arming)
0 (Action)
0 % / Bar / °C
On (1), Off (0)
0 % / Bar / °C
0 % / Bar / °C
On (1), Off (0)
0 % / Bar / °C
0 % / Bar / °C
0 (Action)
0 % / Bar / °C
Digital Input (0), Temperature (2) Sensor
0 (Pressure, Temperature, Percentage Sensor List)
0.00 °C
On (1), Off (0)
Digital Input (0), Flexible (1), Fuel Level (2) Sensor
0 (Sensor Type)
0 (Pressure, Temperature, Percentage Sensor List)
0 (Arming)
0 (Action)
0 % / Bar / °C
On (1), Off (0)
0 % / Bar / °C
0 % / Bar / °C
On (1), Off (0)
0 % / Bar / °C
0 % / Bar / °C
0 (Action)
0 % / Bar / °C
On (1), Off (0)
0 %
0 s
On (1), Off (0)
0 %
0 %
0 s
On (1), Off (0)
0 %
0 %
0 s
0 (Action)
0 %
0 s
Digital Input (0), Flexible (1), Oil Pressure (3) Sensor
0 (Sensor Type)
0 (Pressure / Temperature / Percentage Sensor List)
Current (0), Resistive (1), Voltage (2)
0 (Arming)
On (1), Off (0)
0 % / Bar / °C
On (1), Off (0)
0 % / Bar / °C
0 % / Bar / °C
On (1), Off (0)
0 % / Bar / °C
0 % / Bar / °C
0 (Action)
0 % / Bar / °C
0 (Fuel Sensor Units)
0
On (1), Off (0)
0 %
0 %

Advertisement

loading
Need help?

Need help?

Do you have a question about the DSE6010 MKII and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for DEEP SEA ELECTRONICS DSE6010 MKII

  • Page 1 Configuration Parameters – Module (Page 1) Configuration Parameters – Outputs (Page 4) Configuration Parameters – Analogue Inputs (Page 9) Contrast 0 (%) Use Module Charge Alt On (1), Off (0) Digital Output A Source 0 (Output Source) Digital Output D Source 0 (Output Source) Low Oil Pressure Enable On (1), Off (0)
  • Page 2 Air Maintenance Alarm Action 0 (Action) Configuration Parameters – Alternate Configuration (Page 20) For information on this section, refer to DSE Publication: 057-218 DSE6010 MKII & DSE6020 MKII Operators Manual • Press the ( ) or ( ) buttons to cycle through the front panel editor in Output Sources increments of 1.