Configuration Parameters – Module (Page 1)
101
Contrast
0 (%)
121 Generator Voltage Display
102
Fast Loading Enabled
On (1), Off (0)
122 Mains Voltage Display
103
All Warnings Latched
On (1), Off (0)
123 Generator Frequency Display
104
Lamp Test at Startup
On (1), Off (0)
124 Mains Frequency Display
105
Power Save Mode Enable
On (1), Off (0)
125 Current Display
106
Deep Sleep Mode Enable
On (1), Off (0)
126 kW Display
107
Protected Start Enable
On (1), Off (0)
127 kvar Display
108
Event Log Display Format
On (1), Off (0)
128 kVA Display
109
Power Up Mode
0 (Power Up Mode)
129 pf Display
110
DTC String Enable
On (1), Off (0)
130 kWh Display
111
RESERVED
131 kvarh Display
Pin Protected Maintenance
112
On (1), Off (0)
132 kVAh Display
Reset
113
Stop Button Cooldown
On (1), Off (0)
133 RESERVED
114
Use Module Oil Pressure
On (1), Off (0)
134 Show Load Switching Icons
115
Use Module Coolant Temp
On (1), Off (0)
135 Backlight Inactivity Timer
116
Use Module Engine Hours
On (1), Off (0)
136 ECU Periodic Wake Up
117
Use Module RPM
On (1), Off (0)
137 Coolant Temp Persistence
118
Use Module Charge Alt
On (1), Off (0)
138 Limit Audible Alarm Duration
119
Disable CAN Speed Control
On (1), Off (0)
139 Transducer Power Supply
120
CT Position
Gen (0), Load (1)
140 English Text Mode
Configuration Parameters – CAN Application (Page 2)
201 CAN Alternative Engine Speed
On (1), Off (0)
203
CAN ECU Data Fail Action
202 CAN ECU Data Fail Arming
0 (Arming)
204
CAN ECU Data Fail Delay
Configuration Parameters – Digital Inputs (Page 3)
301
Digital Input A Source
302
Digital Input A Polarity
303
Digital Input A Action (If Source = User Config)
304
Digital Input A Arming (If Source = User Config)
305
Digital Input A Activation Delay (If Source = User Config)
306
Digital Input B Source
307
Digital Input B Polarity
308
Digital Input B Action (If Source = User Config)
309
Digital Input B Arming (If Source = User Config)
310
Digital Input B Activation Delay (If Source = User Config)
311
Digital Input C Source
312
Digital Input C Polarity
313
Digital Input C Action (If Source = User Config)
314
Digital Input C Arming (If Source = User Config)
315
Digital Input C Activation Delay (If Source = User Config)
316
Digital Input D Source
317
Digital Input D Polarity
318
Digital Input D Action (If Source = User Config)
319
Digital Input D Arming (If Source = User Config)
320
Digital Input D Activation Delay (If Source = User Config)
Configuration Parameters – Outputs (Page 4)
401 Digital Output A Source
0 (Output Source)
407 Digital Output D Source
402 Digital Output A Polarity
0 (Output Polarity)
408 Digital Output D Polarity
403 Digital Output B Source
0 (Output Source)
409 Digital Output E Source
404 Digital Output B Polarity
0 (Output Polarity)
410 Digital Output E Polarity
405 Digital Output C Source
0 (Output Source)
411 Digital Output F Source
406 Digital Output C Polarity
0 (Output Polarity)
412 Digital Output F Polarity
Configuration Parameters – Timers (Page 5)
501
Mains Transient Delay
513
ETS Solenoid Hold
502
Start Delay
514
Failed to Stop Delay
503
Preheat Timer
515
Generator Transient Delay
504
Crank Time
516
Transfer Delay
505
Crank Rest Time
517
Breaker Trip Pulse
506
Smoke Limiting
518
Breaker Close Pulse
507
Smoke Limiting Off
519
Delayed Load Output 1
508
DPF Ramp
520
Delayed Load Output 2
509
Safety On Delay
521
Delayed Load Output 3
510
Warm Up Time
522
Delayed Load Output 4
511
Return Delay
523
Power Save Mode Delay
512
Cooling Time
524
Deep Sleep Mode Delay
Digital Input Polarity
Output Polarity
Index
Polarity
Index
Polarity
0
Close to Activate
0
Energise
1
Open to Activate
1
De-Energise
AC System
Digital Input Alarm Arming
Index
Type
Index
Arming
0
2 Phase 3 Wire (L1-L3)
0
Always
1
2 Phase 3 Wire (L1-L2)
1
From Safety On
2
3 Phase 3 Wire
2
From Starting
3
3 Phase 4 Wire
3
Never
4
3 Phase 4 Wire (Delta)
5
Single Phase 2 Wire
Functionality in DSE4510 MKII & DSE4520 MKII
Functionality in DSE4520 MKII only.
Configuration Parameters – Generator (Page 6)
On (1), Off (0)
601 Alternator Fitted
On (1), Off (0)
602 Alternator Poles
On (1), Off (0)
On (1), Off (0)
Under Voltage Shutdown
603
On (1), Off (0)
Enable
On (1), Off (0)
604 Under Voltage Trip Shutdown
On (1), Off (0)
On (1), Off (0)
605 Under Voltage Warning Enable
On (1), Off (0)
606 Under Voltage Warning Trip
607 RESERVED
On (1), Off (0)
On (1), Off (0)
608 Loading Voltage
On (1), Off (0)
609 Over Voltage Warning Enable
610 Over Voltage Warning Return
On (1), Off (0)
611 Over Voltage Warning Trip
On (1), Off (0)
612 Over Voltage Shutdown Trip
On (1), Off (0)
Under Frequency Shutdown
On (1), Off (0)
613
Enable
On (1), Off (0)
614 Under Frequency Shutdown Trip 0.0 Hz
On (1), Off (0)
Under Frequency Warning
On (1), Off (0)
615
Enable
616 Under Frequency Warning Trip
0 (Action)
617 RESERVED
0 s
618 Loading Frequency
619 Nominal Frequency
0 (Input Source)
Over Frequency Warning
620
0 (Polarity)
Enable
0 (Action)
621 Over Frequency Warning Return 0.0 Hz
0 (Arming)
Configuration Parameters – Mains (Page 7)
0 s
701
Mains AC System
0 (Input Source)
702
Mains Failure Detection
0 (Polarity)
703
Immediate Mains Dropout
0 (Action)
704
Under Voltage Enable
0 (Arming)
705
Under Voltage Level
0 s
706
Under Voltage Return
0 (Input Source)
707
Over Voltage Enable
0 (Polarity)
708
Over Voltage Return
0 (Action)
Configuration Parameters – Engine (Page 8)
0 (Arming)
0 s
801
Start Attempts
0 (Input Source)
802
Over Speed Overshoot
0 (Polarity)
803
Over Speed Delay
0 (Action)
Gas Choke Timer
0 (Arming)
804
(Gas Engine Only)
0 s
Gas On Delay
805
(Gas Engine Only)
0 (Output Source)
Gas Ignition Off Delay
806
0 (Output Polarity)
(Gas Engine Only)
0 (Output Source)
Crank Disconnect On Oil
807
0 (Output Polarity)
Pressure Enable
0 (Output Source)
Check Oil Pressure Prior to
808
Starting
0 (Output Polarity)
809
Crank Disconnect On Oil
Crank Disconnect On
525
Page Delay
810
Frequency
526
Cooling Time at Idle
Crank Disconnect On Engine
527
Backlight Power Save Delay
811
Speed
528
Audible Alarm Timer
812
Under Speed Enable
529
Fuel Pull in Coil Duration
813
Under Speed Trip
530
ECU Override Time
814
Over Speed Trip
531
ECU Periodic Wakeup Period
815
Low Battery Voltage Enable
532
Post-Heat Timer
816
Low Battery Voltage Warning
533
Delay Crank Timer
817
Low Battery Voltage Return
534
Max Star Pause Timer
818
Low Battery Voltage Delay
819
High Battery Voltage Enable
820
High Battery Voltage Return
Alarm Action
821
High Battery Voltage Warning
Index
Action
High Battery Voltage Warning
822
0
Electrical Trip
Delay
1
Shutdown
823
Charge Alt Shutdown Enable
2
Warning
824
Charge Alt Shutdown Trip
825
Charge Alt Shutdown Delay
Power Up Mode
826
Charge Alt Warning Enable
Index
Mode
827
Charge Alt Warning Trip
0
Stop
1
Manual
828
Charge Alt Warning Delay
2
Auto
829
Start on Low Battery Enable
830
Start on Low Battery Threshold
831
Start on Low Battery Start Delay 0 s
On (1), Off (0)
622 Over Frequency Warning Trip
0.0 Hz
Over Frequency Shutdown
0
623
On (1), Off (0)
Enable
On (1), Off (0)
624 Over Frequency Shutdown Trip
0.0 Hz
0 (AC
0 V
625 Generator AC System
System)
On (1), Off (0)
626 CT Primary
0 A
0 V
627 CT Secondary
1 A, 5 A
628 Full Load Rating
0 A
0 V
629 Immediate Over Current Enable
On (1), Off (0)
Delayed Over Current Alarm
On (1), Off (0)
630
On (1), Off (0)
Enable
Delayed Over Current Alarm
0 V
631
0 (Action)
Action
0 V
632 Over Current Delay Time
0 s
0 V
633 Over Current Trip
0 %
On (1), Off (0)
634 kW Rating
0 kW
635 Over kW Protection Enable
On (1), Off (0)
On (1), Off (0)
636 Over kW Protection Action
0 (Action)
0.0 Hz
637 Over kW Protection Trip
0 %
638 Over kW Protection Trip Delay
0 s
0.0 Hz
639 Enable CT Support
On (1), Off (0)
0.0 Hz
640 Over kW Protection Return
0 %
On (1), Off (0)
641 Nominal Voltage
0 V
0 (AC System)
709 Over Voltage Level Trip
0 V
On (1), Off (0)
710 Under Frequency Enable
On (1), Off (0)
On (1), Off (0)
711 Under Frequency Trip
0.0 Hz
On (1), Off (0)
712 Under Frequency Return
0.0 Hz
0 V
713 Over Frequency Enable
On (1), Off (0)
0 V
714 Over Frequency Return
0 Hz
On (1), Off (0)
715 Over Frequency Trip
0.0 Hz
0 V
Start on Low Battery
0
832
0 s
Engine Run Duration
0 %
833
RESERVED
0 s
834
RESERVED
0 s
835
J1939-75 Instruments Enable On (1), Off (0)
0 s
836
J1939-75 Alarms Enable
On (1), Off (0)
0 s
837
Engine CAN Source Address
0
Instrumentation CAN Source
On (1), Off (0)
838
0
Address
On (1), Off (0)
839
RESERVED
0.00 Bar
840
Tier 4 Home Screen Enable
On (1), Off (0)
0.0 Hz
841
Start Pause Time
0 s
0 RPM
842
Preheat Enable
On (1), Off (0)
On (1), Off (0)
843
Preheat Temperature
0 °C
0 RPM
844
Post-heat Enabled
On (1), Off (0)
0 RPM
845
Post-heat Temperature
0 °C
On (1), Off (0)
846
Coolant Heater Enabled
On (1), Off (0)
0.0 V
847
Coolant Heater On Temp
0 °C
0.0 V
848
Coolant Heater Off Temp
0 °C
0:00:00
849
Coolant Cooler Enabled
On (1), Off (0)
On (1), Off (0)
850
Coolant Cooler On Temp
0 °C
0.0 V
851
Coolant Cooler Off Temp
0 °C
0.0 V
852
RESERVED
0 s
853
Tank Bund Level High Alarm
0 (Action)
On (1), Off (0)
854
Fan Speed Low Arming
0 (Arming)
0.0 V
855
Fan Speed Low Action
0 (Action)
0 s
856
Fan Speed Low Delay
0 s
On (1), Off (0)
857
Fuel Low Switch Arming
0 (Arming)
0.0 V
858
Fuel Low Switch Action
0 (Action)
Fuel Low Switch Activation
0 s
859
0 s
Delay
Crank Disconnect on Charge
On (1), Off (0)
860
On (1), Off (0)
Alt Enable
Crank Disconnect on Charge
0.0 V
861
0.0 V
Alt Voltage
Configuration Parameters – Analogue Inputs (Page 9)
901-902
RESERVED
903
Low Oil Pressure Enable
On (1), Off (0)
904
Low Oil Pressure Trip
0 Bar
905
Oil Pressure Sensor Open Circuit
On (1), Off (0)
906-907
RESERVED
908
High Engine Temperature Trip
0.00 °C
909
Temperature Sensor Open Circuit
On (1), Off (0)
910-929
RESERVED
930
Fuel Sensor C Low Alarm Action
Shutdown (2), Electrical Trip (1), Disabled (0)
931
Fuel Sensor C Low Shutdown Trip
0 %
932
Fuel Sensor C Low Shutdown Delay
0 s
933
Fuel Sensor C Low Pre-Alarm Enable
On (1), Off (0)
934
Fuel Sensor C Low Pre-Alarm Trip
0 %
935
Fuel Sensor C Low Pre-Alarm Return
0 %
936
Fuel Sensor C Low Pre-Alarm Delay
0 s
937
Fuel Sensor C High Pre-Alarm Enable
On (1), Off (0)
938
Fuel Sensor C High Pre-Alarm Return
0 %
939
Fuel Sensor C High Pre-Alarm Trip
0 %
940
Fuel Sensor C High Pre Alarm Delay
0 s
941
RESERVED
942
Fuel Sensor C High Alarm Action
Shutdown (2), Electrical Trip (1), Disabled (0)
943
Fuel Sensor C High Alarm Trip
0 %
944
Fuel Sensor C High Alarm Delay
0 s
945-967
RESERVED
968
Fuel Usage Alarm (Run) Arming
On (1), Off (0)
969
Fuel Usage Alarm (Run) Action
0 (Action)
970
Fuel Usage Alarm (Run) Trip
0 %
971
Fuel Usage Alarm (Run) Return
0 %
972
Fuel Usage Alarm (Stopped) Arming
0 (Arming)
973
Fuel Usage Alarm (Stopped) Action
0 (Action)
974
Fuel Usage Alarm (Stopped) Trip
0 %
975
Fuel Usage Alarm (Stopped) Return
0 %
976
Low Coolant Level Arming
0 (Arming)
977
Low Coolant Level Action
0 (Action)
978
Low Coolant Level Trip
0 %
979
Low Coolant Level Return
0 %
980
Low Coolant Level Delay
00:00:00
981
Low Coolant Level Open Circuit Arming
On (1), Off (0)
982
Low Coolant Level Switch Arming
0 (Arming)
983
Low Coolant Level Switch Action
0 (Action)
984
Low Coolant Level Switch Delay
00:00:00
985
High Engine Temp Pre-Alarm Enable
On (1), Off (0)
986
High Engine Temp Pre-Alarm Return
0.00 °C
987
High Engine Temp Pre-Alarm Trip
0.00 °C
Configuration Parameters – Scheduler (Page 10)
1001
Enable Scheduler
1002
Schedule Run On or Off Load
1003
Scheduler Period
1004, 1008, 1012, 1016, 1020, 1024, 1028, 1032
Start Time (Entry 1-8)
1005, 1009, 1013, 1017, 1021, 1025, 1029, 1033
Day (Entry 1-8)
1006, 1010, 1014, 1018, 1022, 1026, 1030, 1034
Week (Entry 1-8)
1007, 1011, 1015, 1019, 1023, 1027, 1031, 1035
Duration (Entry 1-8)
Configuration Parameters – Time (Page 11)
1101
Time of Day
0:00:00
1104 Day of Month
1102
RESERVED
1105 Month of Year
1103
RESERVED
1106 Year
Configuration Parameters – Maintenance Alarms (Page 12)
Air Maintenance Alarm Engine
1201
Oil Maintenance Alarm Enable On (1), Off (0)
1206
Hours
Fuel Maintenance Alarm
1202
Oil Maintenance Alarm Action
0 (Action)
1207
Enable
Oil Maintenance Alarm Engine
1203
0 h
1208 Fuel Maintenance Alarm Action 0 (Action)
Hours
Fuel Maintenance Alarm
1204
Air Maintenance Alarm Enable On (1), Off (0)
1209
Engine Hours
1205
Air Maintenance Alarm Action
0 (Action)
Configuration Parameters – Alternate Configuration 1 (Page 20)
Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for
2001-2057
configuration parameters.
Configuration Parameters – Alternate Configuration 2 (Page 30)
Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for
3002-3057
configuration parameters.
Configuration Parameters – Alternate Configuration 3 (Page 40)
Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for
4002-4057
configuration parameters.
On (1), Off (0)
On (1), Off (0)
Weekly (0), Monthly (1)
0:00:00
0 (1=Monday)
1, 2, 3 or 4
0 s
1-31
1-12
0-99
0 h
On (1), Off (0)
0 h

Advertisement

loading

Summary of Contents for DEEP SEA ELECTRONICS DSE4510 MKII

  • Page 1 Configuration Parameters – Alternate Configuration 1 (Page 20) Index Polarity Index Polarity Index Action High Battery Voltage Warning Refer to the DSE Publication 057-260 DSE4510 MKII & DSE4520MKII Operators Manual for Tank Bund Level High Alarm 0 (Action) Close to Activate Energise Electrical Trip 2001-2057 Delay configuration parameters.