USER'S MANUAL
UNI DC INVERTER
FLOOR CEILING
ASF-18AIA, ASF-24AIA, ASF-36AIA, ASF-42AIA
ASGE-18AIA WK, ASGE-24AIA WK, ASGE-36AIA WK
ASGE- 36 AIA-3 WK, ASGE-42AIA-3 WK

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ASF-18AIA and is the answer not in the manual?

Questions and answers

Summary of Contents for Sinclair ASF-18AIA

  • Page 1 USER'S MANUAL UNI DC INVERTER FLOOR CEILING ASF-18AIA, ASF-24AIA, ASF-36AIA, ASF-42AIA ASGE-18AIA WK, ASGE-24AIA WK, ASGE-36AIA WK ASGE- 36 AIA-3 WK, ASGE-42AIA-3 WK...
  • Page 2: User Notice

    User Notice ● Ensure unified power supply for each indoor unit. ● Never install wired controller in wet place or under sunlight directly. ● Shielding twisted pair line must be adopted as signal line or wiring (communication) of wired controller once the unit is installed in the place where there is electromagnetic interference.
  • Page 3: Table Of Contents

    CONTENT Safety Considerations ..................... 1 1. Displaying Part ....................3 1.1 LCD Display of Wired Controller ................3 1.2 Instruction to LCD Display ..................4 2. Buttons ........................ 5 2.1 Silk Screen of Buttons ....................5 2.2 Instruction to Function of Buttons ................5 3.
  • Page 4 5. Error Display ......................23 6. Remote Control Operation Procedure(standard fitting) .........26 6.1 Name and Function-Remote Control ................26 6.2 Name and Function-Remote Control. (Remove the cover) ......... 27 6.3 COOL mode operation procedure ................28 6.4 HEAT mode operation procedure ................29 6.5 DRY mode operation procedure ..................
  • Page 5: Safety Considerations

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Safety Considerations Please read this manual carefully before use and operate correctly as instructed in the manual. You are specially warned to note the two symbols below: A symbol indicating that improper operation might cause human death or severe injury; A symbol indicating that improper operation might cause human property damage.
  • Page 6 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual ● This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
  • Page 7: Displaying Part

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 1. Displaying Part Fig. 1 Outline of wired controller 1.1 LCD Display of Wired Controller Fig.2 LCD display...
  • Page 8: Instruction To Lcd Display

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 1.2 Instruction to LCD Display Table 1 Instruction to LCD Display Description Instruction to Displaying Contents Swing Swing function. Air * Air exchange function . Sleep Sleeping states. Each kind of running mode of in Each kind of running mode of indoor Running mode unit (auto mode).
  • Page 9: Buttons

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 2. Buttons 2.1 Silk Screen of Buttons Fig.3 Silk Screen of Buttons 2.2 Instruction to Function of Buttons Table 2 Instruction to Function of Buttons Description Function of Button ①...
  • Page 10: Installation Of Wired Controller

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 3. Installation of Wired Controller Fig.4 Sketch for Installation of Wired Controller Socket’s base box Soleplate of Front panel of × × Description Screw M4 Screw ST2.2 installed in the wall controller controller Fig.4: Sketch for Installation of Wired Controller.
  • Page 11: Instruction To Operation

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 4. Instruction to Operation 4.1 On/Off Press On/Off button to turn on the unit. Repress this button to turn off the unit. Note: The state shown in Fig.5 indicates off-state of the unit after energization. The state shown in Fig.6 indicates on-state of the unit after energization.
  • Page 12: Temperature Setting

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 4.3 Temperature Setting Press ▲ or ▼button to increase or decrease of setting temperature under on-state of the unit. If press either of them continuously, temperature will be increased or decreased by 1°C every 0.5s. In Cooling, Dry, Fan and Heating mode, temperature setting range is 16°C~30°C.
  • Page 13 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Fig.10 Swing control function setting...
  • Page 14: Timer Setting

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 4.6 Timer Setting Press Timer button to set timer off of the unit. Under off-state of the unit, press Timer button to set timer on of the unit in the same way. Timer on setting: Under off-state of the unit without timer setting, if Timer button is pressed, LCD will display xx.
  • Page 15: Air Exchange Setting

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Continued Fig.11 Timer setting under on state of the unit Timer range: 0.5-24hr. Every press of▲ or ▼ button will make setting time increased or decreased by 0.5hr. If press either of them continuously, setting time will automatically increase/ decrease by 0.5hr every 0.5s. Note: ●...
  • Page 16 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Fig.12 Air exchange device Note:In air exchange mode, press Function button or there is not any operation within 5s after the last button operation, the system will be quit from air exchange setting and current energy-saving data won’t be memorized.
  • Page 17: Sleep Setting

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 4.8 Sleep Setting Sleep on: Press Function button under on-state of the unit into sleep function and then press Enter/Cancel button to turn on sleeping function. Sleep off: During sleep on-state, press Function button to go to the sleep function and then press Enter/ Cancel button to turn off this function.
  • Page 18: Turbo Function Setting

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Sleep setting is clear after power failure and then power recovery. There is not sleep function in fan and auto mode. Note: In cooling and dry mode, if the unit with sleep function has run for 1 hour, the preset temperature will be increased by 1°C and 1°C in another 1 hour.
  • Page 19: Save Function Setting

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual (continued) Fig.14 Turbo Function Setting Note: TURBO function will be turned off after power failure and then recovery. In dry, fan and auto mode, TURBO function can not be set and TURBO mark won’t be displayed. TURBO function will be automatically canceled after setting of quiet function.
  • Page 20 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Fig.15 Energy Saving Setting...
  • Page 21: E-Heater Setting

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Note: ● In Auto running mode with save function on, the unit will be forcibly quit Auto running Mode and change to current operation mode, After setting of save, sleep function will be canceled. ●...
  • Page 22: Blow Function Setting

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual (continued) Fig.16 Auxiliary Electric Heating Function Setting Note: E-HEATER can not be set in cooling, dry and fan mode, E-HEATER mark won’t be displayed. The setting is shown in Fig.16. 4.12 Blow Function Setting BLOW function: After the unit is turned off, water in evaporator of indoor unit will be automatically evaporated to avoid mildew.
  • Page 23 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Fig.17 Blow function setting...
  • Page 24: Quiet Function Setting

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Note: After setting BLOW function, turn off the unit by pressing On/Off button on remote controller, indoor fan will run at low fan speed for 10 min. (BLOW shows).Meanwhile, if BLOW function is canceled indoor fan will be turned off directly.
  • Page 25: Field Functions

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual (continued) Fig.18 Quiet function setting Note: ● During quiet function, fan speed is un-adjustable. ● When turning on auto quiet function, the unit will enter quiet running state according to temperature difference between room temperature and setting temperature.
  • Page 26: Other Functions

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual medium grades. Press Enter/Cancel button to save the setting and quit after setting. If there is not any operation within 20s after the system responds to the last button operation in this interface, the system will quit this menu and display normal off-state;...
  • Page 27: Error Display

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 5. Error Display If there is malfunction during running of the system, LCD will display error code at temperature–displayed location. Once there is more than one malfunction, error codes will be displayed circularly. If there are multiple circuit systems, the system number of failed system will be displayed before the colon (not for single system).
  • Page 28 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual The LED Indicator Display on the Main Board of Outdoor Unit (09K/12K). This table is applicable to the electric control box of the 09K and 12K C Series DC inverter air conditioners. Some of the items are not malfunction;...
  • Page 29 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Definition of Malfunction Codes of DC Inverter General Outdoor Unit (V1.6). This table is applicable to the electric control box of the other models of C-Series DC inverter air conditioners.
  • Page 30: Remote Control Operation Procedure(Standard Fitting)

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6. Remote Control Operation Procedure(standard fitting) 6.1 Name and Function-Remote Control Note: ● Be sure that there are no obstructions between receiver and remote controller. ● Don’ t drop or throw the remote controller . ●...
  • Page 31: Name And Function-Remote Control. (Remove The Cover)

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6.2 Name and Function-Remote Control. (Remove the cover) Note: This type of remote controller is a kind of new current controller. Some buttons of the controller which are not available to this air conditioner will not be described below. Fig.
  • Page 32: Cool Mode Operation Procedure

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6.3 COOL mode operation procedure ① According to difference between room temp. and set temp., microcomputer can control cooling on or not. ② If room temp. is higher than set temp., compressor runs at COOL mode. ③ If room temp.
  • Page 33: Heat Mode Operation Procedure

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6.4 HEAT mode operation procedure ① If room temp. is lower than set temp. compressor runs at HE AT mode. ② If room temp. is higher than set temp., compressor and outdoor fan motor stop, only indoor fan motor runs.
  • Page 34: Dry Mode Operation Procedure

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6.5 DRY mode operation procedure ① If room Temp. is more than 2°C below Set TEMP. , compressor and outdoor unit fan motor stop, indoor unit fan motor runs at low speed. ② If room Temp.
  • Page 35: Auto Mode Operation Procedure

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6.6 AUTO mode operation procedure ① According to room temp. microcomputer can automatically set COOL.HEAT.DRY operation mode, so as far best effect. ② At AUTO mode operation, standard TEMP. is 26°C for COOL mode, 24°C for DRY mode and 20°C for HEAT mode.
  • Page 36: Fan Mode Operation Procedure

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6.7 FAN mode operation procedure ① Connect the unit to power supply. ② Press the “ON/OFF” key. ③ Press the mode key to select the “FAN” mode. The unit shall operate under “FAN” mode. ④ Press the “FAN”...
  • Page 37: Timer Operation Procedure

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6.8 TIMER operation procedure Fig. 27...
  • Page 38: Sleep Mode Operation Procedure

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6.9 SLEEP mode operation procedure ① When the unit is cooling or drying, if SLEEP operation is set, TEMP. would increase 1°C in 1 hour and 2°C in 2 hours. Indoor fan motor runs at low speed. ② When the unit is heating , if SLEEP operation is set, TEMP.
  • Page 39: How To Insert Batteries

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 6.10 How to insert batteries Fig. 29...
  • Page 40: Part Names And Their Functions

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 7. Part Names and Their Functions Fig.30 CAUTION: ● Wrong wiring connection will cause electrical malfunction. ● Do not pull the wire when fixing it with wire. Note: ● If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
  • Page 41: Maintenance

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 8. Maintenance Before inspection and maintenance of the unit, please turn off the unit and set the power switch to “OFF” to cut off the power supply. ① Cleaning the Air Filters Remove the air filter;...
  • Page 42: Operating Guide

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 9. Operating Guide The cleaning and replacement of the filter is only permitted to be done by the professionals. Before open the grille to clean the filter, please cut off the power supply and wait unit the fan motor stops. ① The temperature should not be set lower than what you need, otherwise it would result in increased energy cost.
  • Page 43: Precautions

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 10. Precautions ① Turn off the air conditioner if it is not needed, as electricity interference may occurs while it is running .If the unit is not to be used for a long time, cut off the power supply main switch. Fig.
  • Page 44: Checking Before Contact The Service Man

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 11. Checking Before Contact the Service Man Check the followings before contact the service man. You may find the solution to your problems. After checking, if it still does not operate, please contact your local dealer. Table.3 Problem Solution(s)
  • Page 45 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Table.5 Accessories List for Installation (Indoor Unit) Number Name Shape Quantity Type Remark Nut (with gasket) Tie Line 200mm used for Installation ceiling Paperboard drilling Thermal Insulation Layer of Discharge Pipe Thermal Insulation Layer of Inlet Liquid...
  • Page 46: Installation Of The Indoor Unit

    When install the indoor unit, you can use a paper pattern for reference and make sure that the drainage side be 10mm lower than the other side in order to drain the condensation water fluently. Fig. 39 Unit: mm Model ASF-18AIA 1220 1158 ASF-24AIA ASF-36AIA...
  • Page 47 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Selection of Installation Location ① Such a place where cool air can be distributed throughout the room. ② Such a place where condensation water is easily drained out. ③ Such a place that can handle the weight of indoor unit. ④ Such a place which has easy access for maintenance.
  • Page 48 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual ④ Set the suspension bolt. (Use M10 size suspension bolts) ⑤ Adjust the distance between the unit and the ceiling slab beforehand (See Fig.43). Fix the hanger bracket to the suspension bolt. WARNING! ●...
  • Page 49: Installation Of The Outdoor Unit

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 11.3 Installation of the Outdoor Unit 11.3.1 Installation Location of the Outdoor Unit ① The foundation must be solid enough to bear the weight and vibration of the unit. ② The space around the unit is adequate for ventilation.
  • Page 50 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual ● The rated voltage and the exclusive circuit must be used. ● Leakage circuit-breaker must be installed. ● Please use the specified fuse. ● If the power supply cord of the unit is damaged it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard.
  • Page 51: Schematic Diagram Of Unit Line Connection

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual air. Ensure that there is no obstacle to the air intake and exhaust of the outdoor unit. If there is any obstacle blocking the air intake or exhaust, remove it. ③ Place of installation should be strong enough to support the weight of outdoor unit, and it should be able to insulate noise and prevent vibration.
  • Page 52 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Fig.54-2 ASGE-18AIA WK+ASF-18AIA ASGE-24AIA WK+ASF-24AIA 1.Power cord 3×4.0 mm (H07RN-F) 2.Power cord 3×1.0 mm (H05VV-F) 3.Communication Cords Fig.55 ASGE-36AIA-3 WK+ASF-36AIA ASGE-42AIA-3 WK+ASF-42AIA 1.Power cord 5×2.5 mm (H07RN-F) 2.Power cord 3×1.0 mm (H05VV-F) 3.Communication Cords...
  • Page 53 The section area of cables selected by users must not be smaller than the specifications shown in the table below. Table.8 Capability of Air Minimum Sectional Area Power Model Switch(A) Of Earth Wire (mm Supply (Outdoor/Indoor) (Outdoor/Indoor) ASF-18AIA 20/6 4.0/1.0 ASGE-18AIA WK 220-240V~ ASF-24AIA 20/6 4.0/1.0 50Hz ASGE-24AIA WK ASF-36AIA 25/6 4.0/1.0...
  • Page 54 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Rated Parameters and Outline Dimensions of the Fuse Table.9 Unit Code Rated parameter Dimensions 46010014/ 250V/3.15A 46010023 250V/30A ASGE-18AIA WK 46010014/ 250V/3.15A 46010023 250V/30A ASGE-24AIA WK 46010014/ 250V/3.15A 46010023 250V/30A ASGE-36AIA WK 46010014...
  • Page 55: Connecting Pipe Preparation

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Connecting Pipe Preparation 11.5 11.5.1 Pipe Preparation 1. Pipe & Electrical Wire Cutting ♦ Use cutting tools easily found in the market. ♦ Measure precisely both outer & inter pipes. ♦...
  • Page 56: Refrigerant Piping Work

    Indoor Unit × Wall Liquid and Outdoor Filled (For Extra Thickness) Model Pipe Pipe Unit(m) Length of Pipe) (mm) 30 g/m ASF-18AIA, ASGE-18AIA WK ASF-24AIA, ASGE-24AIA WK Φ17×1.75 60 g/m ASF-36AIA, ASGE-36AIA WK ASF-36AIA, ASGE+36AIA-3 WK ASF-42AIA, ASGE-42AIA-3 WK Fig.60...
  • Page 57: Air Purging

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Avoid pipe bending as much as possible, if it is necessary, the bending radius must be more than 3 or 4 cm. Connection between an Indoor unit and an Outdoor Unit: ① Unscrew the flare nut for releasing pressure gas in the indoor unit.
  • Page 58: Liquid Pipe And Drain Pipe

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 11.5.4 Liquid Pipe and Drain Pipe If the outdoor unit is installed lower than the indoor unit (See Fig.63). ♦ A drain pipe should be above ground and the end of the pipe does not dip into water.
  • Page 59 DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual Fig. 68 Fig. 69 Fig. 67 11.5.6 Routine Checks after Installation Check after installation Table.11 Items to be checked Possible Malfunction(s) Items to be checked Has it been fixed firmly? The unit may drop, shake or emit noise.
  • Page 60: Test Running

    DC Inverter Floor Ceiling Type Air Conditioner Installation and Operation Manual 11.5.7 Test Running Evaluation of the Performance Check the voltage of the main electrical wire. Use a thermometer to measure both inlet and outlet cool air. The difference between inlet air and outlet air temperature should not be less than 8°C .