External Appearance External Appearance Indoor Units Super-slim 4-way Cassette Ceiling & floor type Outdoor Units Double fan outdoor unit...
Page 4
Features Features High quality coils: The coil is constructed of advanced inner grooved copper tube and aluminum fins. Anti-rust, 500 hours salt spray test. Low operation sound level: Well-known stable and quiet running fan motor. Well-known compressor. Compact design: Smaller dimension and larger stuffing capacity. Universal outdoor unit design.
Page 5
Model ASC-60AN Power supply (indoor ) V- Ph-Hz 220~240-1-50 Power supply (outdoor ) V- Ph-Hz 380~415-3-50 Capacity Btu/h 51000 6030 Input Cooling 10,41 Current 2,48 Capacity Btu/h 58000 6410 Input Heating 11,07 Current 2,65 Model WZDK124-38G Indoor fan motor Input 124(Output) Capacitor Speed(hi/mi/lo)
Page 6
Model ASF-60AN Power supply (indoor ) V- Ph-Hz 220~240-1-50 Power supply (outdoor ) V- Ph-Hz 380~415-3-50 Capacity Btu/h 52000 Input 5370 Cooling Current 9.27 2.84 Capacity Btu/h 57100 Input 5400 Heating Current 9.32 Model WZDK90-38GS-W Indoor fan motor Input 90(Output)
Page 7
ASF-60AN, ASC-60AN Model OUTDOOR UNIT Power supply V-ph-Hz 380~415-3-50 Max. input consumption 7000 Max. input current Model C-SBN453H8D Type Scroll Brand Sanyo Capacity Btu/h 55957 Input 5750 Compressor Rated current(RLA) 9,77 Locked rotor Amp(LRA) Thermal protector position Internal Capacitor Refrigerant oil...
Page 8
Indoor Units Indoor Units Super-slim Cassette Type ..........4 Ceiling & Floor Type ............17...
Super-slim Cassette Type Super-slim Cassette Type 1. Features ..............5 2. Dimensions ..............9 3. Service Space ............. 10 4. Wiring Diagrams ............11 5. Electric Characteristics ..........12 6. Sound Levels .............. 13 7. Accessories ..............14 8. The Specification of Power ........15 9.
Features 1. Features Overview Compact design, super slim body size, less space requiring in installation Each louver can be separately controlled, more comfort air blowing is possible. Auto-lifting panel design, more convenient to clean and maintain the filter. (optional) Old Cassette New Slim Cassette Reduction 840*300*840...
Page 11
Features New air-intake Optional ionizer generator Ionizer generator is optional to get refreshing air to your room. Ionizer can be switched on or off by remote controller. When pressing the Clean Air button on the remote controller, Ionizer will work and the indicator light on display board will shine.
Page 12
Features External air duct design Reserve external air duct, more flexible for the air supply. Built-in draining pump Due to the improvement of structure, more convenient to repair or replace the draining pump. Draining Pump Built-in draining pump to make sure condensed water drain out reliably.
Page 13
Features Terminals for alarm lamp and long-distance on-off controller connection are standard Reserve terminals for the connection of alarm lamp and long-distance on-off controller, more human control. Alarm lamp Long-distance on-off controller Optional touch screen wired controller Touch screen wired controller is optional, with error code indication function. Better man-machine conversation interface.
The Specification of Power 8. The Specification of Power Model ASC-60AN Phase 1-phase Frequency and Voltage 220-240V, 50Hz INDOOR UNIT POWER POWER WIRING (mm 3×1.0 Circuit Breaker/ Fuse (A) 20/16 Phase 3-phase Frequency and Voltage 380-415V, 50Hz OUTDOOR UNIT POWER POWER WIRING (mm 5×2.5 Circuit Breaker/ Fuse (A)
Page 22
Ceiling & Floor Type Ceiling & Floor Type 1. Features ................18 2. Dimensions ..............19 3. Service Space ..............20 4. Wiring Diagrams ............. 21 5. Electric Characteristics ..........22 6. Sound Levels ..............22 7. Accessories ..............23 8. The Specification of Power ..........23 9.
Features Features 1.1. New design, more modern and elegant appearance. 1.2. Convenient installation --The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow --It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting.
Electric Characteristics Electric Characteristics Indoor Units Power Supply Model Voltage Min. Max. ASF-60AN 220-240V 198V 254V Remark: MFA: Max. Fuse Amps. (A) Sound Levels Microphone 1.5m Air outlet side Microphone Ceiling Floor Noise level dB(A) Model ASF-60AN...
3. Mounting screw (ST2.9×10-C-H) 4. Alkaline dry batteries (AM4) 5. Owner's manual Others 6. Installation manual 7. Remote controller manual The Specification of Power Model ASF-60AN Phase 1-phase Frequency and Voltage 220-240V, 50Hz INDOOR UNIT POWER POWER WIRING (mm 3×1.0...
Service Space 2. Service Space (Wall or obstacle) More than 30cm Air inlet More than 60cm More than 30cm Maintain channel Air inlet More than 60cm Air outlet More than 200cm...
Insulation Work 1. Installation Procedure Indoor unit installation Outdoor unit installation location selection location selection Indoor unit installation Outdoor unit installation Refrigerant pipe Refrigerant pipe installation and insulation installation and insulation Drainage pipe installation Drainage pipe installation and insulation and insulation Vacuum drying and leakage checking Additional refrigerant charge Insulation the joint part of refrigerant pipe...
Location selection 2. Location selection 2.1 Indoor unit location selection The place shall easily support the indoor unit’s weight. The place can ensure the indoor unit installation and inspection. The place can ensure the indoor unit horizontally installed. The place shall allow easy water drainage. The place shall easily connect with the outdoor unit.
Indoor unit installation 3. Indoor unit inst 3.3 Super-slim cassette indoor unit installation 3.3.1 Service space for indoor unit Model Remark >317 R410A Cooling / Cooling & Heating ASC-60AN 3.3.2 Bolt pitch 3.3.3 Install the pendant bolt Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling.
Page 42
Insulation Work 3.3.4 Install the main body Make the 4 suspender through the 4 hanger of the main body to suspend it. Adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body. Use a leveling instrument to make sure the levelness of the main body is within Adjust the position to ensure the gaps between the body and the four sides of ceiling are even.
Page 43
Indoor unit installation 3.3.5 Install the panel Remove the grille Remove the 4 corner covers. Hang the panel to the hooks on the mainbody. If the panel is with auto-lift grille, please watch the ropes lifing the grille, DO NOT make the ropes enwinded or blocked.
Page 44
Insulation Work Tighten the screws under the panel hooks till the panel closely stick on the ceiling to avoid condensate water. Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control box with corresponding terminators on the body respectively.
Page 45
Indoor unit installation 3.4 Ceiling & floor indoor unit installation 3.4.1 Service space for indoor unit 3.4.2 Bolt pitch Ceiling installation Capacity (Btu/h) ASF-60AN 1565 Wall-mounted installation...
Page 46
Insulation Work 3.4.3 Install the pendant bolt Ceiling installation Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible hooks (fittings).
Page 47
Indoor unit installation Locate the hanging arm on the hanging screw bolt. Prepare the mounting bolts on the unit. Put the side panels and grilles back. Wall-mounted installation Hang the indoor unit by insert the tapping screws into the hanging arms on the main unit. (The bottom of body can touch with floor or suspended, but the body must install vertically.)
4.1 Service space for outdoor unit 4.2 Bolt pitch Model ASF-60AN, ASC-60AN 633.5 4.3 Install the Unit Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling.
Refrigerant pipe installation Do not touch the fan with hands or other objects. Do not lean it more than 45, and do not lay it sidelong. Make concrete foundation according to the specifications of the outdoor units. Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind. 5.
Insulation Work Flare dimension A (mm) Pipe diameter Flare shape 1/4" (6.35) 3/8" (9.52) 12.0 12.4 R0.4~0.8 1/2" (12.7) 15.4 15.8 5/8" (15.9) 18.6 19.1 3/4" (19) 22.9 23.3 After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct or exogenous impurity come into the pipe.
Page 51
Drainage pipe installation 6.2.2 Drainage pipe selection The drainage pipe diameter shall not small than the drain hose of indoor unit According to the water flowrate and drainage pipe slope to choose the suitable pipe, the water flowrate is decided by the capacity of indoor unit. Relationship between water flowrate and capacity of indoor unit Capacity (x1000Btu) Water flowrate (l/h)
Page 52
Insulation Work Drainage pipe Drainage pipe Drain tee Drainage pipe Water flow Water flow Water flow Water flow Water flow Drain tee Drain tee Water flow Water flow Water flow Water flow Branch pipe Water flow Water flow Main pipe Keep a certain degree Main pipe Branch pipe...
Page 53
Drainage pipe installation Hanger Down incline pipe A:Length of horizontal pipe 150mm B: Lift height the pump head of water pump Flexible pipe 300mm 6.2.8 Blowhole setting For the concentrated drainage pipe system, there should design a blowhole at the highest point of main pipe to ensure the condensate water discharge smoothly.
Insulation Work 2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and then connect the plug of water level switch, check the operation sound of water pump and observe whether the water can discharge through the transparent hard pipe at drainage outlet. (In light of the length of drainage pipe, water shall be discharged about 1 minute delayed) 2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole...
Additional refrigerant charge 1. When conduct first vacuum drying, connect pressure gauge to the infusing mouth of gas pipe and liquid pipe, and keep vacuum pump running for 1hour (vacuum degree of vacuum pump shall be reached -755mmHg). If the vacuum degree of vacuum pump could not reach -755mmHg after 1 hour of drying, it indicates that there is moisture or leakage in pipeline system and need to go on with drying for half an hour.
Insulation Work 9. Engineering of insulation 9.1 Insulation of refrigerant pipe 9.1.1 Operational procedure of refrigerant pipe insulation Cut the suitable pipe insulation (except joint section) flare the pipe piping layout and connection vacuum drying insulate the joint parts 9.1.2 Purpose of refrigerant pipe insulation During operation, temperature of gas pipe and liquid pipe shall be over-heating or over-cooling extremely.
Engineering of electrical wiring 9.2.3 Insulation material selection for drainage pipe The insulation material should be flame retardant material, the flame retardancy of the material should be selected according to the local law. Thickness of insulation layer is usually above 10mm. Use specific glue to paste the seam of insulation material, and then bind with adhesive tape.
Page 58
Insulation Work Whether the indicator lights normally. Whether the temporary buttons works well. Whether the drainage is normal. Whether there is vibration or abnormal noise during operation. Outdoor unit Whether there is vibration or abnormal noise during operation. Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood.
Page 59
Electrical Control Electrical Control System 1. Electrical Control Function ..............55 2. Troubleshooting ..................64 3. Controller ..................... 79...
Page 60
Electrical Control Function 1. Electrical Control Function 1.1 Definition T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature 1.2 Main Protection 1.2.1 Time delay at restart for compressor. 1.2.2 Sensor protection at open circuit and breaking disconnection.
Page 61
Electrical Control Function 1.3 Operation Modes and Functions 1.3.1 Fan mode ( 1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/(med)/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan: High Medium...
Page 62
Electrical Control Function 1.3.2.3 Indoor fan running rules In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto. The auto fan: T1-Ts High Medium 1.3.2.4 Low evaporator coil temperature T2 protection For Duct: When the evaporator coil temp.T2 keeps lower than TE5 for Time0, the compressor and outdoor fan will shut off.
Page 63
Electrical Control Function Condition 2: TE5-2 When the evaporator coil temp.T2 keeps lower than TE5-2 for 20 minutes, the compressor and outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up. Condition 3: TE5-4 When the evaporator coil temp.T2 keeps lower than TE5-4 for 8 minutes, the compressor and outdoor fan...
Page 64
Electrical Control Function For Ceiling & Floor: TE10 TE11 When T3 TE10, the compressor will shut off. When T3 TE11,the compressor will restart. 1.3.3 Heating Mode 1.3.3.1 Compressor running rules: For Duct & super-slim cassette type: Once the compressor starts up, it keeps running 7 minutes, For Ceiling &...
Page 65
Electrical Control Function Auto fan action: For Duct & super-slim cassette type: For Ceiling & Floor: setting temperature-compensation.=4 C T1-Ts Medium High For Ceiling & Floor: setting temperature-compensation.=1 C T1-Ts Medium High 1.3.3.4 Defrosting mode Condition of defrosting: AC will enter defrosting mode if any of the following items is satisfied. A: T3<...
Page 66
Electrical Control Function Setting defrosting time Compressor 4 way valve Outdoor fan Indoor fan 1.3.3.5 High evaporator coil temp.T2 protection: For Duct and Super-slim Cassette: Compressor off Outdoor fan off Compressor on Outdoor fan off TE10 Compressor on Outdoor fan on TE11 For Ceiling &...
Page 67
Electrical Control Function For Duct and Super-slim Cassette: T=T1-Ts Running mode Cooling Fan-only Heating T<-1 For Ceiling & Floor: T=T1-Ts Running mode Cooling Fan-only -1< T 2 Heating T -1 Indoor fan will run at auto fan of the relevant mode. The louver operates same as in relevant mode.
Page 68
Electrical Control Function After pressing ECONOMIC or SLEEP button on the controller, the machine will go into economy mode. When cooling, the setting temperature rises 1 (be lower than 30 ) every hour, 2 hours later the setting temperature stops rising. For heat pump models, when they are in heating, the setting temperature reduces 1 (be higher than 17 ) every hour, 2 hours later the setting temperature stops reducing.
Troubleshooting 2. Troubleshooting 2.1 Display board 2.1.2 Icon explanation on indoor display board (Super-slim cassette). 4-way 2.1.4 Display board of 2.1.5 Icon explanation on indoor display board(Ceiling & Floor)
Page 70
Troubleshooting 2.2. Self-diagnosis Indoor unit’s LED indication For Super-slim 4-way Cassette Running Timer Defrosting Alarm Display(digital Malfunction lamp lamp lamp lamp tube) Communication malfunction between indoor and outdoor units Open or short circuit of T1 temperature sensor Open or short circuit of T2 temperature sensor Open or short circuit of T3 temperature sensor...
Page 71
Troubleshooting For Ceiling & Floor Running Timer Defrosting Alarm Malfunction lamp lamp lamp lamp Communication malfunction between indoor and outdoor units Open or short circuit of T1 temperature sensor Open or short circuit of T2 temperature sensor Open or short circuit of T3 temperature sensor Outdoor unit malfunction Indoor EEPROM malfunction Full-water malfunction...
Page 72
Troubleshooting 2.3. Solving steps for typical malfunction (1) For indoor unit a. Communication malfunction between indoor and outdoor units(E1) Power off, then turn on the unit 5 seconds later(reconnect the power wire).Is the error still displaying after several minutes? Check if there’s any interference. Remove interference.
Page 73
Troubleshooting b. Open or short circuit of temperature sensor E2 E3, E4 Check the connections between temperature Correct the connections. sensor and PCB. Are the connections good? Check the resistance value of the sensor via Appendix 1 Is it normal? Replace indoor or outdoor PCB.
Page 74
Troubleshooting c. Outdoor unit malfunction(E6) Outdoor unit malfunction Whether the outdoor main board has error Refer to corresponding solving steps display Whether the outdoor Check whether the power is on unit is power on Check whether the communication wire Connect the wiring well or between the indoor and replace the communication wire outdoor unit is...
Page 75
Troubleshooting d. Indoor EEPROM malfunction(E7) Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code? If the EEPROM chip is welded on PCB, replace the PCB directly. Otherwise, Insert the EEPROM well check whether the EEPROM chip plugged in PCB well?
Page 76
Troubleshooting f. Indoor fan speed has been out of control(Eb)
Page 77
Troubleshooting Index 1: 1.Indoor DC fan motor(control chip is inside fan motor) Measure the resistance value of each winding by using the tester. If any resistance value is zero, the fan motor must have problems and need to be replaced. Color Black White...
Page 78
Troubleshooting For the super-slim cassette with up-down panel a. Communication error between indoor unit and up-down panel b. Up-down panel is defective...
Page 79
Troubleshooting c Up-down panel is not closed...
Page 80
Troubleshooting (2) For the outdoor unit a. Phase sequence error: Phase sequence error Change the order of two of the wires to power supply. Switch on the unit again. If the problem cannot be solved, the outdoor PCB is defective b.
Page 81
Troubleshooting c. Overload of current Overload of current Check the current, normally Is the current in rated range? Possible reason The outdoor PCB is defective Outdoor fan is defective The compressor is defective Refrigerant is over charged Air enter the refrigerant system d.
Page 82
Troubleshooting e. High temperature protection of condenser High temperature protection of condenser Check the resistance of the temp. sensor according to Appendix 1 , is it normal? Replace the sensor Possible reason 1. Air or other gas in the refrigerant. 2.
Page 83
Troubleshooting Appendix 1 Temperature Sensor Resistance Value Table ( --K) K Ohm K Ohm K Ohm K Ohm 12.6431 2.35774 0.62973 115.266 108.146 12.0561 2.27249 0.61148 101.517 11.5000 2.19073 0.59386 96.3423 10.9731 2.11241 0.57683 89.5865 10.4736 2.03732 0.56038 84.2190 10.000 1.96532 0.54448 79.3110...
Page 84
Controller 3. Controller 3.1 Wireless Remote Controller 3.1.1 RG51Q1/BGE The R51Q1/BGE wireless remote controller is standard for Four-way cassette type and the Ceiling& floor type. General Function for wireless remote controller: Model RG51Q1/BGE Rated voltage 3.0V(2pieces of LR03 7 batteries) Min voltage for sending signal of CPU 2.4V Effective receiving distance...
Page 85
Controller Buttons and functions 1. Adjust : Decrease the set temp. Keeping pressing will decrease the temp with 1 per 0.5s. 2. Adjust : Increase the set temp. Keeping pressing will increase the temp with 1 per 0.5s. 3. MODE : Once pressing, running mode will be selected in the following sequence: AUTO COOL HEAT...
Page 86
Controller 3.1.2 RG51C/E Remote Controller Specifications Model RG51C/E Rated Voltage 3.0V Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance 8m (when using 3.0 voltage, it can get 11m) Environment Temperature Range Introduction of Function Buttons on the Remote Controller SET TEM PERATURE( C) AU TO COOL...
Page 87
Controller controls into faceplate setting state and the LCD shows F2.Press the TEMPUP( ) to control the faceplate up and press the TEMP DOWN( ) to control the faceplate down. Press any button to exit the faceplate setting state, then the LCD back to the normal display. 7.
Page 88
Controller 3.2 Wired Remote Controller (OPTIONAL) KJR-10B Name and functions of buttons on the wire controller mode selection button: It is used to select mode, push the button one time, then the operation modes will change In turn as follows: AUTO COOL HEAT...
Page 89
Controller Name and function of LCD on the wire controller Mode select button (MODE): Press MODE button to select “COOL”, “DRY” , "HEAT", or "FAN ONLY" mode.(HEAT is invalid for COOL ONLY wire controller.) AUTO COOL HEAT Fan speed button (FAN SPEED) Press FAN SPEED to select fan speed from "AUTO", "LOW","...
Page 90
Controller Remark: The wired controller will reset to factory setting with auto mode, auto fan and 24 setting temperature when the air conditioner restarts after power failure. And this may cause inconsistent displays on the wired controller and on the air conditioner. You need to readjust the running status through the wired controller.
Page 94
Description Part Code Actualization Qty Price Code MODEL: ASF‐60AN intdoor Air inlet grille assembly II 201144790014 Air filter I 201144790023 Air inlet grille assembly I 201144790015 Air filter II 201144790024 Top cover assembly 201244790048 Display installation box 201144790016 Display board assembly 201344790040 Evaporator assembly 201544790142 Pipe temperature sensor assembly 202301300111...