Sinclair ASF-60AN Service Manual

On/off series

Advertisement

Quick Links

SERVICE MANUAL
ON/OFF SERIES
ASF-60AN, ASC-60AN

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ASF-60AN and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Sinclair ASF-60AN

  • Page 1 SERVICE MANUAL ON/OFF SERIES ASF-60AN, ASC-60AN...
  • Page 3: External Appearance

    External Appearance External Appearance Indoor Units Super-slim 4-way Cassette Ceiling & floor type Outdoor Units Double fan outdoor unit...
  • Page 4 Features Features High quality coils: The coil is constructed of advanced inner grooved copper tube and aluminum fins. Anti-rust, 500 hours salt spray test. Low operation sound level: Well-known stable and quiet running fan motor. Well-known compressor. Compact design: Smaller dimension and larger stuffing capacity. Universal outdoor unit design.
  • Page 5 Model ASC-60AN Power supply (indoor ) V- Ph-Hz 220~240-1-50 Power supply (outdoor ) V- Ph-Hz 380~415-3-50 Capacity Btu/h 51000 6030 Input Cooling 10,41 Current 2,48 Capacity Btu/h 58000 6410 Input Heating 11,07 Current 2,65 Model WZDK124-38G Indoor fan motor Input 124(Output) Capacitor Speed(hi/mi/lo)
  • Page 6 Model ASF-60AN Power supply (indoor ) V- Ph-Hz 220~240-1-50 Power supply (outdoor ) V- Ph-Hz 380~415-3-50 Capacity Btu/h 52000 Input 5370 Cooling Current 9.27 2.84 Capacity Btu/h 57100 Input 5400 Heating Current 9.32 Model WZDK90-38GS-W Indoor fan motor Input 90(Output)
  • Page 7 ASF-60AN, ASC-60AN Model OUTDOOR UNIT Power supply V-ph-Hz 380~415-3-50 Max. input consumption 7000 Max. input current Model C-SBN453H8D Type Scroll Brand Sanyo Capacity Btu/h 55957 Input 5750 Compressor Rated current(RLA) 9,77 Locked rotor Amp(LRA) Thermal protector position Internal Capacitor Refrigerant oil...
  • Page 8 Indoor Units Indoor Units Super-slim Cassette Type ..........4 Ceiling & Floor Type ............17...
  • Page 9: Table Of Contents

    Super-slim Cassette Type Super-slim Cassette Type 1. Features ..............5 2. Dimensions ..............9 3. Service Space ............. 10 4. Wiring Diagrams ............11 5. Electric Characteristics ..........12 6. Sound Levels .............. 13 7. Accessories ..............14 8. The Specification of Power ........15 9.
  • Page 10: Features

    Features 1. Features Overview Compact design, super slim body size, less space requiring in installation Each louver can be separately controlled, more comfort air blowing is possible. Auto-lifting panel design, more convenient to clean and maintain the filter. (optional) Old Cassette New Slim Cassette Reduction 840*300*840...
  • Page 11 Features New air-intake Optional ionizer generator Ionizer generator is optional to get refreshing air to your room. Ionizer can be switched on or off by remote controller. When pressing the Clean Air button on the remote controller, Ionizer will work and the indicator light on display board will shine.
  • Page 12 Features External air duct design Reserve external air duct, more flexible for the air supply. Built-in draining pump Due to the improvement of structure, more convenient to repair or replace the draining pump. Draining Pump Built-in draining pump to make sure condensed water drain out reliably.
  • Page 13 Features Terminals for alarm lamp and long-distance on-off controller connection are standard Reserve terminals for the connection of alarm lamp and long-distance on-off controller, more human control. Alarm lamp Long-distance on-off controller Optional touch screen wired controller Touch screen wired controller is optional, with error code indication function. Better man-machine conversation interface.
  • Page 14: Dimensions

    Dimensions 2. Dimensions Model >317 ASC-60AN...
  • Page 15: Service Space

    Service Space 3. Service Space >1000mm >1000mm...
  • Page 16: Wiring Diagrams

    Wiring Diagrams 4. Wiring Diagrams ASC-60AN...
  • Page 17: Electric Characteristics

    Field Wiring 5. Electric Characteristics Indoor Unit Power Supply Model Voltage ASC-60AN 220-240V 198V 254V Note: MFA: Max. Fuse Amps. (A)
  • Page 18: Sound Levels

    Sound Levels 6. Sound Levels Microphone Noise level dB(A) Model ASC-60AN...
  • Page 19: Accessories

    Field Wiring 7. Accessories Name Shape Quantity Installation paper board INSTALLATION FITTINGS Bolt M5 Tubing & Fittings Soundproof / insulation sheath Out-let pipe Out-let pipe sheath Drainpipe Fittings Out-let pipe clasp Remote controller & Its Frame Remote controller holder Remote controller & Its Frame Mounting screw(ST2.9×10-C-H) Remote controller manual...
  • Page 20: The Specification Of Power

    The Specification of Power 8. The Specification of Power Model ASC-60AN Phase 1-phase Frequency and Voltage 220-240V, 50Hz INDOOR UNIT POWER POWER WIRING (mm 3×1.0 Circuit Breaker/ Fuse (A) 20/16 Phase 3-phase Frequency and Voltage 380-415V, 50Hz OUTDOOR UNIT POWER POWER WIRING (mm 5×2.5 Circuit Breaker/ Fuse (A)
  • Page 21: Field Wiring

    Field Wiring 9. Field Wiring ASC-60AN...
  • Page 22 Ceiling & Floor Type Ceiling & Floor Type 1. Features ................18 2. Dimensions ..............19 3. Service Space ..............20 4. Wiring Diagrams ............. 21 5. Electric Characteristics ..........22 6. Sound Levels ..............22 7. Accessories ..............23 8. The Specification of Power ..........23 9.
  • Page 23: Features

    Features Features 1.1. New design, more modern and elegant appearance. 1.2. Convenient installation --The ceiling type can be easily installed into a corner of the ceiling even if the ceiling is very narrow --It is especially useful when installation of an air conditioner in the center of the ceiling is impossible due to a structure such as one lighting.
  • Page 24: Dimensions

    Dimensions Dimensions Capacity (Btu/h) ASF-60AN 1650 1565...
  • Page 25: Service Space

    Service Space Service Space...
  • Page 26: Wiring Diagrams

    Wiring Diagrams Wiring Diagrams ASF-60AN...
  • Page 27: Electric Characteristics

    Electric Characteristics Electric Characteristics Indoor Units Power Supply Model Voltage Min. Max. ASF-60AN 220-240V 198V 254V Remark: MFA: Max. Fuse Amps. (A) Sound Levels Microphone 1.5m Air outlet side Microphone Ceiling Floor Noise level dB(A) Model ASF-60AN...
  • Page 28: Accessories

    3. Mounting screw (ST2.9×10-C-H) 4. Alkaline dry batteries (AM4) 5. Owner's manual Others 6. Installation manual 7. Remote controller manual The Specification of Power Model ASF-60AN Phase 1-phase Frequency and Voltage 220-240V, 50Hz INDOOR UNIT POWER POWER WIRING (mm 3×1.0...
  • Page 29: Field Wiring

    Field Wiring Field Wiring ASF-60AN...
  • Page 30 Outdoor Units Outdoor Units 1. Dimensions ....................26 2. Service Space ....................27 3. Piping Diagrams ..................28 4. Wiring Diagrams ..................29 5. Electric Characteristics ................30 6. Operation Limits ..................31 7. Sound Levels .....................32...
  • Page 31: Dimensions

    Dimensions 1. Dimensions Unit mm Model 633.5 1369 ASF-60AN, ASC-60AN...
  • Page 32: Service Space

    Service Space 2. Service Space (Wall or obstacle) More than 30cm Air inlet More than 60cm More than 30cm Maintain channel Air inlet More than 60cm Air outlet More than 200cm...
  • Page 33: Piping Diagrams

    Piping Diagrams 3. Piping Diagrams ASF-60AN, ASC-60AN INDOOR OUTDOOR CHECK VALVE LIQUID SIDE (Heating Model only) 2-WAY VALVE T3 Condenser temp. sensor CAPILIARY TUBE HEAT EXCHANGE HEAT (EVAPORATOR) T4 Ambient T1 Room temp. EXCHANGE temp. sensor sensor (CONDENSER) T2 Evaporator temp.
  • Page 34: Wiring Diagrams

    Wiring Diagrams 4. Wiring Diagrams ASF-60AN, ASC-60AN...
  • Page 35: Electric Characteristics

    Electric Characteristics 5. Electric Characteristics Outdoor Unit Model Voltage Min. Max. ASF-60AN,ASC-60AN 380~415V 342V 435V...
  • Page 36: Operation Limits

    Operation Limits 6. Operation Limits Temperature Cooling operation Heating operation Mode Room temperature Outdoor temperature Cooling Heating With Low Ambient Cooling System Indoor temperature( Indoor temperature(...
  • Page 37: Sound Levels

    Sound Levels 7. Sound Levels Outdoor Unit Microphone 1.0m Note: H= 0.5 × height of outdoor unit Model Noise level dB(A) ASF-60AN,ASC-60AN...
  • Page 38 Installation Installation 1. Installation Procedure ................34 2. Location selection ..................35 3. Indoor unit installation ................36 4. Outdoor unit installation (Side Discharge Unit) ........43 5. Refrigerant pipe installation ..............44 6. Drainage pipe installation .................45 7. Vacuum Drying and Leakage Checking ..........49 8.
  • Page 39: Installation Procedure

    Insulation Work 1. Installation Procedure Indoor unit installation Outdoor unit installation location selection location selection Indoor unit installation Outdoor unit installation Refrigerant pipe Refrigerant pipe installation and insulation installation and insulation Drainage pipe installation Drainage pipe installation and insulation and insulation Vacuum drying and leakage checking Additional refrigerant charge Insulation the joint part of refrigerant pipe...
  • Page 40: Location Selection

    Location selection 2. Location selection 2.1 Indoor unit location selection The place shall easily support the indoor unit’s weight. The place can ensure the indoor unit installation and inspection. The place can ensure the indoor unit horizontally installed. The place shall allow easy water drainage. The place shall easily connect with the outdoor unit.
  • Page 41: Indoor Unit Installation

    Indoor unit installation 3. Indoor unit inst 3.3 Super-slim cassette indoor unit installation 3.3.1 Service space for indoor unit Model Remark >317 R410A Cooling / Cooling & Heating ASC-60AN 3.3.2 Bolt pitch 3.3.3 Install the pendant bolt Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling.
  • Page 42 Insulation Work 3.3.4 Install the main body Make the 4 suspender through the 4 hanger of the main body to suspend it. Adjust the hexangular nuts on the four installation hooks evenly, to ensure the balance of the body. Use a leveling instrument to make sure the levelness of the main body is within Adjust the position to ensure the gaps between the body and the four sides of ceiling are even.
  • Page 43 Indoor unit installation 3.3.5 Install the panel Remove the grille Remove the 4 corner covers. Hang the panel to the hooks on the mainbody. If the panel is with auto-lift grille, please watch the ropes lifing the grille, DO NOT make the ropes enwinded or blocked.
  • Page 44 Insulation Work Tighten the screws under the panel hooks till the panel closely stick on the ceiling to avoid condensate water. Hang the air-in grill to the panel, then connect the lead terminator of the swing motor and that of the control box with corresponding terminators on the body respectively.
  • Page 45 Indoor unit installation 3.4 Ceiling & floor indoor unit installation 3.4.1 Service space for indoor unit 3.4.2 Bolt pitch Ceiling installation Capacity (Btu/h) ASF-60AN 1565 Wall-mounted installation...
  • Page 46 Insulation Work 3.4.3 Install the pendant bolt Ceiling installation Select the position of installation hooks according to the hook holes positions showed in upper picture. Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the expansible hooks (fittings).
  • Page 47 Indoor unit installation Locate the hanging arm on the hanging screw bolt. Prepare the mounting bolts on the unit. Put the side panels and grilles back. Wall-mounted installation Hang the indoor unit by insert the tapping screws into the hanging arms on the main unit. (The bottom of body can touch with floor or suspended, but the body must install vertically.)
  • Page 48: Outdoor Unit Installation (Side Discharge Unit)

    4.1 Service space for outdoor unit 4.2 Bolt pitch Model ASF-60AN, ASC-60AN 633.5 4.3 Install the Unit Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling.
  • Page 49: Refrigerant Pipe Installation

    Refrigerant pipe installation Do not touch the fan with hands or other objects. Do not lean it more than 45, and do not lay it sidelong. Make concrete foundation according to the specifications of the outdoor units. Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong wind. 5.
  • Page 50: Drainage Pipe Installation

    Insulation Work Flare dimension A (mm) Pipe diameter Flare shape 1/4" (6.35) 3/8" (9.52) 12.0 12.4 R0.4~0.8 1/2" (12.7) 15.4 15.8 5/8" (15.9) 18.6 19.1 3/4" (19) 22.9 23.3 After flared the pipe, the opening part must be seal by end cover or adhesive tape to avoid duct or exogenous impurity come into the pipe.
  • Page 51 Drainage pipe installation 6.2.2 Drainage pipe selection The drainage pipe diameter shall not small than the drain hose of indoor unit According to the water flowrate and drainage pipe slope to choose the suitable pipe, the water flowrate is decided by the capacity of indoor unit. Relationship between water flowrate and capacity of indoor unit Capacity (x1000Btu) Water flowrate (l/h)
  • Page 52 Insulation Work Drainage pipe Drainage pipe Drain tee Drainage pipe Water flow Water flow Water flow Water flow Water flow Drain tee Drain tee Water flow Water flow Water flow Water flow Branch pipe Water flow Water flow Main pipe Keep a certain degree Main pipe Branch pipe...
  • Page 53 Drainage pipe installation Hanger Down incline pipe A:Length of horizontal pipe 150mm B: Lift height the pump head of water pump Flexible pipe 300mm 6.2.8 Blowhole setting For the concentrated drainage pipe system, there should design a blowhole at the highest point of main pipe to ensure the condensate water discharge smoothly.
  • Page 54: Vacuum Drying And Leakage Checking

    Insulation Work 2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and then connect the plug of water level switch, check the operation sound of water pump and observe whether the water can discharge through the transparent hard pipe at drainage outlet. (In light of the length of drainage pipe, water shall be discharged about 1 minute delayed) 2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole...
  • Page 55: Additional Refrigerant Charge

    Additional refrigerant charge 1. When conduct first vacuum drying, connect pressure gauge to the infusing mouth of gas pipe and liquid pipe, and keep vacuum pump running for 1hour (vacuum degree of vacuum pump shall be reached -755mmHg). If the vacuum degree of vacuum pump could not reach -755mmHg after 1 hour of drying, it indicates that there is moisture or leakage in pipeline system and need to go on with drying for half an hour.
  • Page 56: Engineering Of Insulation

    Insulation Work 9. Engineering of insulation 9.1 Insulation of refrigerant pipe 9.1.1 Operational procedure of refrigerant pipe insulation Cut the suitable pipe insulation (except joint section) flare the pipe piping layout and connection vacuum drying insulate the joint parts 9.1.2 Purpose of refrigerant pipe insulation During operation, temperature of gas pipe and liquid pipe shall be over-heating or over-cooling extremely.
  • Page 57: Engineering Of Electrical Wiring

    Engineering of electrical wiring 9.2.3 Insulation material selection for drainage pipe The insulation material should be flame retardant material, the flame retardancy of the material should be selected according to the local law. Thickness of insulation layer is usually above 10mm. Use specific glue to paste the seam of insulation material, and then bind with adhesive tape.
  • Page 58 Insulation Work Whether the indicator lights normally. Whether the temporary buttons works well. Whether the drainage is normal. Whether there is vibration or abnormal noise during operation. Outdoor unit Whether there is vibration or abnormal noise during operation. Whether the generated wind, noise, or condensed of by the air conditioner have influenced your neighborhood.
  • Page 59 Electrical Control Electrical Control System 1. Electrical Control Function ..............55 2. Troubleshooting ..................64 3. Controller ..................... 79...
  • Page 60 Electrical Control Function 1. Electrical Control Function 1.1 Definition T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature T5: Compressor discharge temperature 1.2 Main Protection 1.2.1 Time delay at restart for compressor. 1.2.2 Sensor protection at open circuit and breaking disconnection.
  • Page 61 Electrical Control Function 1.3 Operation Modes and Functions 1.3.1 Fan mode ( 1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/(med)/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan: High Medium...
  • Page 62 Electrical Control Function 1.3.2.3 Indoor fan running rules In cooling mode, indoor fan runs all the time and the speed can be selected as high, medium, low and auto. The auto fan: T1-Ts High Medium 1.3.2.4 Low evaporator coil temperature T2 protection For Duct: When the evaporator coil temp.T2 keeps lower than TE5 for Time0, the compressor and outdoor fan will shut off.
  • Page 63 Electrical Control Function Condition 2: TE5-2 When the evaporator coil temp.T2 keeps lower than TE5-2 for 20 minutes, the compressor and outdoor fan will shut off. When T2 is higher than TE6, the compressor and outdoor fan will restart up. Condition 3: TE5-4 When the evaporator coil temp.T2 keeps lower than TE5-4 for 8 minutes, the compressor and outdoor fan...
  • Page 64 Electrical Control Function For Ceiling & Floor: TE10 TE11 When T3 TE10, the compressor will shut off. When T3 TE11,the compressor will restart. 1.3.3 Heating Mode 1.3.3.1 Compressor running rules: For Duct & super-slim cassette type: Once the compressor starts up, it keeps running 7 minutes, For Ceiling &...
  • Page 65 Electrical Control Function Auto fan action: For Duct & super-slim cassette type: For Ceiling & Floor: setting temperature-compensation.=4 C T1-Ts Medium High For Ceiling & Floor: setting temperature-compensation.=1 C T1-Ts Medium High 1.3.3.4 Defrosting mode Condition of defrosting: AC will enter defrosting mode if any of the following items is satisfied. A: T3<...
  • Page 66 Electrical Control Function Setting defrosting time Compressor 4 way valve Outdoor fan Indoor fan 1.3.3.5 High evaporator coil temp.T2 protection: For Duct and Super-slim Cassette: Compressor off Outdoor fan off Compressor on Outdoor fan off TE10 Compressor on Outdoor fan on TE11 For Ceiling &...
  • Page 67 Electrical Control Function For Duct and Super-slim Cassette: T=T1-Ts Running mode Cooling Fan-only Heating T<-1 For Ceiling & Floor: T=T1-Ts Running mode Cooling Fan-only -1< T 2 Heating T -1 Indoor fan will run at auto fan of the relevant mode. The louver operates same as in relevant mode.
  • Page 68 Electrical Control Function After pressing ECONOMIC or SLEEP button on the controller, the machine will go into economy mode. When cooling, the setting temperature rises 1 (be lower than 30 ) every hour, 2 hours later the setting temperature stops rising. For heat pump models, when they are in heating, the setting temperature reduces 1 (be higher than 17 ) every hour, 2 hours later the setting temperature stops reducing.
  • Page 69: Troubleshooting

    Troubleshooting 2. Troubleshooting 2.1 Display board 2.1.2 Icon explanation on indoor display board (Super-slim cassette). 4-way 2.1.4 Display board of 2.1.5 Icon explanation on indoor display board(Ceiling & Floor)
  • Page 70 Troubleshooting 2.2. Self-diagnosis Indoor unit’s LED indication For Super-slim 4-way Cassette Running Timer Defrosting Alarm Display(digital Malfunction lamp lamp lamp lamp tube) Communication malfunction between indoor and outdoor units Open or short circuit of T1 temperature sensor Open or short circuit of T2 temperature sensor Open or short circuit of T3 temperature sensor...
  • Page 71 Troubleshooting For Ceiling & Floor Running Timer Defrosting Alarm Malfunction lamp lamp lamp lamp Communication malfunction between indoor and outdoor units Open or short circuit of T1 temperature sensor Open or short circuit of T2 temperature sensor Open or short circuit of T3 temperature sensor Outdoor unit malfunction Indoor EEPROM malfunction Full-water malfunction...
  • Page 72 Troubleshooting 2.3. Solving steps for typical malfunction (1) For indoor unit a. Communication malfunction between indoor and outdoor units(E1) Power off, then turn on the unit 5 seconds later(reconnect the power wire).Is the error still displaying after several minutes? Check if there’s any interference. Remove interference.
  • Page 73 Troubleshooting b. Open or short circuit of temperature sensor E2 E3, E4 Check the connections between temperature Correct the connections. sensor and PCB. Are the connections good? Check the resistance value of the sensor via Appendix 1 Is it normal? Replace indoor or outdoor PCB.
  • Page 74 Troubleshooting c. Outdoor unit malfunction(E6) Outdoor unit malfunction Whether the outdoor main board has error Refer to corresponding solving steps display Whether the outdoor Check whether the power is on unit is power on Check whether the communication wire Connect the wiring well or between the indoor and replace the communication wire outdoor unit is...
  • Page 75 Troubleshooting d. Indoor EEPROM malfunction(E7) Shut off the power supply and turn it on 5 seconds later. Is it still displaying the error code? If the EEPROM chip is welded on PCB, replace the PCB directly. Otherwise, Insert the EEPROM well check whether the EEPROM chip plugged in PCB well?
  • Page 76 Troubleshooting f. Indoor fan speed has been out of control(Eb)
  • Page 77 Troubleshooting Index 1: 1.Indoor DC fan motor(control chip is inside fan motor) Measure the resistance value of each winding by using the tester. If any resistance value is zero, the fan motor must have problems and need to be replaced. Color Black White...
  • Page 78 Troubleshooting For the super-slim cassette with up-down panel a. Communication error between indoor unit and up-down panel b. Up-down panel is defective...
  • Page 79 Troubleshooting c Up-down panel is not closed...
  • Page 80 Troubleshooting (2) For the outdoor unit a. Phase sequence error: Phase sequence error Change the order of two of the wires to power supply. Switch on the unit again. If the problem cannot be solved, the outdoor PCB is defective b.
  • Page 81 Troubleshooting c. Overload of current Overload of current Check the current, normally Is the current in rated range? Possible reason The outdoor PCB is defective Outdoor fan is defective The compressor is defective Refrigerant is over charged Air enter the refrigerant system d.
  • Page 82 Troubleshooting e. High temperature protection of condenser High temperature protection of condenser Check the resistance of the temp. sensor according to Appendix 1 , is it normal? Replace the sensor Possible reason 1. Air or other gas in the refrigerant. 2.
  • Page 83 Troubleshooting Appendix 1 Temperature Sensor Resistance Value Table ( --K) K Ohm K Ohm K Ohm K Ohm 12.6431 2.35774 0.62973 115.266 108.146 12.0561 2.27249 0.61148 101.517 11.5000 2.19073 0.59386 96.3423 10.9731 2.11241 0.57683 89.5865 10.4736 2.03732 0.56038 84.2190 10.000 1.96532 0.54448 79.3110...
  • Page 84 Controller 3. Controller 3.1 Wireless Remote Controller 3.1.1 RG51Q1/BGE The R51Q1/BGE wireless remote controller is standard for Four-way cassette type and the Ceiling& floor type. General Function for wireless remote controller: Model RG51Q1/BGE Rated voltage 3.0V(2pieces of LR03 7 batteries) Min voltage for sending signal of CPU 2.4V Effective receiving distance...
  • Page 85 Controller Buttons and functions 1. Adjust : Decrease the set temp. Keeping pressing will decrease the temp with 1 per 0.5s. 2. Adjust : Increase the set temp. Keeping pressing will increase the temp with 1 per 0.5s. 3. MODE : Once pressing, running mode will be selected in the following sequence: AUTO COOL HEAT...
  • Page 86 Controller 3.1.2 RG51C/E Remote Controller Specifications Model RG51C/E Rated Voltage 3.0V Lowest Voltage of CPU Emitting Signal 2.0V Reaching Distance 8m (when using 3.0 voltage, it can get 11m) Environment Temperature Range Introduction of Function Buttons on the Remote Controller SET TEM PERATURE( C) AU TO COOL...
  • Page 87 Controller controls into faceplate setting state and the LCD shows F2.Press the TEMPUP( ) to control the faceplate up and press the TEMP DOWN( ) to control the faceplate down. Press any button to exit the faceplate setting state, then the LCD back to the normal display. 7.
  • Page 88 Controller 3.2 Wired Remote Controller (OPTIONAL) KJR-10B Name and functions of buttons on the wire controller mode selection button: It is used to select mode, push the button one time, then the operation modes will change In turn as follows: AUTO COOL HEAT...
  • Page 89 Controller Name and function of LCD on the wire controller Mode select button (MODE): Press MODE button to select “COOL”, “DRY” , "HEAT", or "FAN ONLY" mode.(HEAT is invalid for COOL ONLY wire controller.) AUTO COOL HEAT Fan speed button (FAN SPEED) Press FAN SPEED to select fan speed from "AUTO", "LOW","...
  • Page 90 Controller Remark: The wired controller will reset to factory setting with auto mode, auto fan and 24 setting temperature when the air conditioner restarts after power failure. And this may cause inconsistent displays on the wired controller and on the air conditioner. You need to readjust the running status through the wired controller.
  • Page 91 MODEL: ASC‐60AN intdoor...
  • Page 92 Description  Part Code  Actualization Qty  Price Code  MODEL: ASC‐60AN intdoor Panel assembly 201109990017 Louver motor 202400100007 Display box assembly 203342890005 Panel assembly P0000449603 1.3.1 Cover assembly of installation plate P0000449698 1.3.2 Air inlet grille assembly P0000449689 1.3.2.1 Air filter 201109901903 1.3.3 Transmission framework P0000449696 1.3.3.1 Louver P0000449731 Cover...
  • Page 93 Model: ASF-60AN indoor...
  • Page 94 Description  Part Code  Actualization Qty  Price Code  MODEL: ASF‐60AN intdoor Air inlet grille assembly II 201144790014 Air filter I 201144790023 Air inlet grille assembly I 201144790015 Air filter II 201144790024 Top cover assembly 201244790048 Display installation box 201144790016 Display board assembly 201344790040 Evaporator assembly 201544790142 Pipe temperature sensor assembly 202301300111...
  • Page 95 MODEL: ASC‐60AN, ASF‐60AN outdoor...
  • Page 96 Description  Part Code  Actualization Qty  Price Code  MODEL: ASC‐60AN, ASF‐60AN outdoor Ambient temperature sensor assembly 202440220061 Rear net 201175690001 Condenser assembly 201575790151 Condenser assembly 201575790152 Condenser assembly 201575790153 Input pipe assembly 201675890900 Fluted pipe assembly 201675890890 Pipe temperature sensor assembly 202450200331 Big Handle assembly 201157390007 Rear right clapboard assembly 201248700199 Handle...