Revision A: • 3. SPECIFICATION has been corrected. OBD945 is void. INDOOR UNIT INDOOR UNIT No. OBD945 TECHNICAL & REVISED EDITION-A SERVICE MANUAL Models MSZ-FX06NL MSZ-FX09NL MSZ-FX12NL MSZ-FX15NL Outdoor unit technical & service manual MSZ-FX18NL MUZ-FX•NLHZ Series (OBD946) MXZ-D•NL/NLHZ Series (OBD949) MSZ-FX24NL Outdoor unit service manual MUZ-FX•NLHZ Series (OBH946)
Page 2
Use the specified refrigerant only Never use any refrigerant other than that specified. Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of. Correct refrigerant is specified in the manuals and on the spec labels provided with our products. We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to follow the instructions.
SERVICING PRECAUTIONS FOR UNITS USING REFRIGERANT R454B Servicing precautions for units using refrigerant R454B Refrigerant WARNING Safety Group This unit uses a flammable refrigerant. If refrigerant leaks and comes in contact with fire or heating part, it will create harmful gas and there is risk of fire. Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
Page 4
2. Additional refrigerant charge Additional refrigerant charge Refrigerant for the indoor units and the extended piping is not included in the outdoor unit when the unit is shipped from the factory. Therefore, charge each refrigerant piping system with additional refrigerant at the installation site. In addition, in order to carry out service, enter the size and length of each liquid pipe and additional refrigerant charge amounts in the spaces pro- vided on the “Refrigerant amount”...
Page 5
4. Cautions for the unit using R454B refrigerant Basic work procedures are the same as those for conventional units using refrigerant R410A. However, pay careful attention to the following points. ■ Information on servicing 1. Checks to the area Prior to beginning work on systems containing FLAMMABLE REFRIGERANTS, safety checks are necessary to ensure that the risk of ignition is minimized.
Page 6
■ Repairs to sealed components Sealed electrical components shall be replaced. ■ Repair to intrinsically safe components Intrinsically safe components must be replaced. ■ Cabling Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects.
Page 7
■ Decommissioning Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of recovered refrigerant.
PART NAMES AND FUNCTIONS MSZ-FX06NL MSZ-FX09NL MSZ-FX12NL MSZ-FX15NL MSZ-FX18NL MSZ-FX24NL Front panel Wireless LAN module Air inlet Air filter Horizontal vane Air outlet Air cleaning filter Remote controller (Electrostatic anti-allergy Spec name plate enzyme filter and Micro- particle Catching Filter) i-see sensor Fan guard (Deodrizing filter, option)
3-1. OPERATING RANGE (1) POWER SUPPLY Rated voltage Guaranteed voltage (V) 208/230 V Min. 187 Max. 253 Indoor unit 1 phase 60 Hz (2) OPERATION Intake air temperature (°F) Mode Condition Standard temperature Maximum temperature Cooling Minimum temperature Maximum humidity Standard temperature Heating Maximum temperature...
SERVICE FUNCTIONS MSZ-FX06NL MSZ-FX09NL MSZ-FX12NL MSZ-FX15NL MSZ-FX18NL MSZ-FX24NL 7-1. TIMER SHORT MODE For service, the following set time can be shortened by bridging the timer short mode point on the electronic control P.C. board. The time will be shortened as follows. (Refer to 9-7.) Set time : 1-minute 1-second Set time : 3-minute...
7-4. AUTO RESTART FUNCTION When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed are memorized by the indoor electronic control P.C. board. “AUTO RESTART FUNCTION” automatically starts operation in the same mode just before the shutoff of the main power.
Page 17
7-5. Wi-Fi MODULE SETTING UP 1. Connection setup of the wireless LAN module 2. Wireless LAN Module Introduction This Wireless LAN module, communicates the status infor- CAUTION mation and controls the commands from the kumocloud ® Wi-Fi enabled indoor units: ®...
Page 18
Refer to the lat- • This Wireless LAN module should not be connected to est operation manual of the kumocloud ® any Mitsubishi Electric system which is to provide cooling or heating to critical applications. OBD945A...
Page 19
• Mitsubishi Electric’s Wireless LAN module is designed for communication to Mitsubishi Electric’s kumocloud ® Mitsubishi Electric is not responsible for any (i) underper- formance of a system or any product; (ii) system or product fault; or (iii) loss or damage to any system or product;...
MICROPROCESSOR CONTROL MSZ-FX06NL MSZ-FX09NL MSZ-FX12NL MSZ-FX15NL MSZ-FX18NL MSZ-FX24NL WIRELESS REMOTE CONTROLLER Signal transmitting section Distance of signal: About 20 feet (6 m) Beep(s) is (are) heard from the indoor unit when the signal is received. Battery replacement indicator FAN speed control button Operation select button WIDE VANE button POWERFUL button...
Page 21
8-1. COOL ( ) OPERATION (1) Press OFF/ON (stop/operate) button. Operation indicator lamp of the indoor unit turns on with a beep tone. (2) Select COOL mode with Operation select button. (3) Press Temperature buttons TEMP button to select the desired temperature. The setting range is 61 - 88°F (16 - 31°C).
8-6. AUTO VANE OPERATION 1. Horizontal vane (1) Vane motor drive These models are equipped with a stepping motors for the horizontal vanes. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approximately 12 V) transmitted from indoor microprocessor. (2) The horizontal vane angle and mode change as follows by pressing VANE CONTROL ( ) button.
2. Vertical vane (1) Vane motor drive These models are equipped with a stepping motor for the vertical vane. The rotating direction, speed, and angle of the motor are controlled by pulse signals (approximately 12 V) transmitted from microprocessor. (2) The vertical vane angle and mode change as follows by pressing WIDE VANE button. (3) Positioning (SWING) To confirm the standard position, the vane moves until it touches the vane stopper.
PROGRAM TIMER • OFF timer and ON timer can be used in combination. The set time that is reached first will operate first. • “ ” and “ ” display shows the order of OFF timer and ON timer operation. (Example 1) The current time is 8:00 PM.
Page 25
(3) Press , and buttons to set ON/OFF, time, and temperature. E.g. : [ON], [AM 6:00] and [75°F (24°C)] are selected. Pressing selects ON/OFF timer. Pressing Pressing adjusts the time. adjusts the Pressing temperature. deletes timer setting. * Hold down the button to change the time quickly. * The temperature can be set between 61°F and 88°F (16°C and 31°C) at weekly timer.
Page 26
Detection range The i-see Sensor does not analyze the temperature in the following range. • The wall surface on which the air conditioner is installed • The spot beneath the air conditioner • Where there is an object (such as furniture) between the place and the air conditioner It might not detect human and objects properly on the following conditions •...
8-10. AIRFLOW CONTROL MODE Airflow Control mode offers air conditioning according to a location of an occupant in a room detected by i-see Sensor. (1) Press DIRECTION button during COOL, DRY, HEAT or AUTO mode to activate the AIRFLOW CONTROL mode. This mode is only available when the i-see control mode is effective.
8-13. EMERGENCY/TEST OPERATION In the case of test run operation or the emergency operation, use the emergency operation switch on the right side of the indoor unit. The emergency operation is available when the remote controller is missing or has failed, or when the batteries in the remote controller are running down.
TROUBLESHOOTING MSZ-FX06NL MSZ-FX09NL MSZ-FX12NL MSZ-FX15NL MSZ-FX18NL MSZ-FX24NL 9-1. CAUTIONS ON TROUBLESHOOTING 1. Before troubleshooting, check the following 1) Check the power supply voltage. 2) Check the indoor/outdoor connecting wire for miswiring. 2. Take care of the following during servicing 1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and then after confirming the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
Page 30
9-2. FAILURE MODE RECALL FUNCTION AND ERROR CODE DISPLAY MODE Outline of the function This air conditioner can memorize the failure which has occurred last time. Even though LED indication listed on the troubleshooting check table (9-4.) disappears, the memorized failure can be recalled.
Page 31
A (From previous page) Press OFF/ON (stop/operate) button of the remote controller with the remote controller headed towards the indoor unit. *1. The indoor unit is normal, but the outdoor unit might be abnormal. Does the left OPERATION INDICATOR lamp on the There are some abnormalities that cannot be recalled with this way.
Page 32
2. Flow chart of error code display mode This explains how customers can check the error code on their own. This is included in OPERATING INSTRUCTIONS. Operational procedure The remote controller is powered OFF. Get close to the front of the indoor unit. Point the remote controller at the receiving section of the indoor unit, and keep pressing CHECK with a fine- tipped object.
Page 33
3. Table of indoor unit failure mode recall function The left lamp of Error Abnormal point the operation Condition Remedy code (Failure mode) indicator lamp Not lit Normal — — The room temperature thermistor short or 1-time blink every Room temperature Refer to the characteristics of the room tempera- open circuit is detected every 8 seconds 0.5-second...
Page 34
9-3. INSTRUCTION OF TROUBLESHOOTING *2 There is possibility that diesel explosion may occur due to the air mixed in the refrigerant circuit. 1. Check of the unit. First, ensure that there are no leakage points on the valves, flare connec- tions, etc.
Page 35
2. Check of Wi-Fi module Follow the procedure below if the air conditioner cannot be monitored or controlled with a device such as a smartphone. Did the right lamp of the operation indicator lamp There is a problem in a communication between the air blink 10 times after you selected the setting of the conditioner and the Wi-Fi module.
9-4. TROUBLESHOOTING CHECK TABLE Before taking measures, make sure that the symptom reappears for accurate troubleshooting. When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the power ON), the indoor fan motor turns OFF and the operation indicator lamp blinks. •...
Page 37
Abnormal Operation indicator lamp Symptom Condition Remedy point • Press the emergency operation but- 1. Refrigerant leaks from the piping ton to turn off the buzzer. or the heat exchanger in the • Open the window to ventilate the indoor unit. •...
9-6. TROUBLESHOOTING FLOW A Check of indoor fan motor The indoor fan motor error has occurred, and the indoor fan does not operate. Turn OFF the power supply. Pay enough attention to the high voltage on the fan motor connector CN211. Turn ON the power supply, wait 5 seconds or more, and then press the emergency operation switch.
Page 39
B Check of remote controller and indoor electronic control P.C. board NOTE: Check if the remote controller is exclusive for this air conditioner. Press OFF/ON (stop/operate) *1 Look at the image of the signal transmitting section of button on the remote controller. the remote controller through the monitor of a digital camera or a camera phone.
Page 40
C Check of indoor P.C. board and indoor fan motor Turn OFF the power supply. Remove indoor fan motor connector CN211 from indoor power P.C. board and vane motor connector CN151 from the indoor electronic control P.C. board and turn ON Measure the resistance between Short circuit: the power supply.
Page 41
D How to check miswiring and serial signal error Turn ON the power supply. Is there rated voltage in the power supply? Check the power supply. Is there rated voltage between outdoor terminal block S1 and S2? Check the wiring. Press the emergency operation switch once.
Page 42
E Electromagnetic noise enters into TV sets or radios Is the unit grounded? Ground the unit. Is the distance between the antennas Extend the distance between the antennas and and the indoor unit within 9.91 ft., or is the indoor unit, and/or the antennas and the out- the distance between the antennas and door unit.
Page 43
9-7. TEST POINT DIAGRAM AND VOLTAGE Indoor power P.C. board, Indoor electronic control P.C. board, Display and receiver P.C. board, Switch buzzer P.C. board MSZ-FX06NL MSZ-FX09NL MSZ-FX12NL MSZ-FX15NL MSZ-FX18NL MSZ-FX24NL Indoor power P.C. board Indoor fan motor Connector Terminal Varistor (NR11) Resistor (R111) (CN211) Block (CN201)
DISASSEMBLY INSTRUCTIONS <Detaching method of the terminal with locking mechanism> The terminal which has the locking mechanism can be detached as shown below. There are 2 types of the terminal with locking mechanism. The terminal without locking mechanism can be detached by pulling it out. Check the shape of the terminal before detaching.
OPERATING PROCEDURE PHOTOS/FIGURES How to install the front panel (Photos 1, 2) Figure 1 (1) Attach the horizontal vanes (upper R/L) and (lower R/L) Click (2) Install the front panel to the indoor unit. Click (3) Push the locations indicated by the arrows firmly to close the front panel (Figure 1).
Page 46
OPERATING PROCEDURE PHOTOS/FIGURES 2. Removing the indoor electrical box Photo 5 (Photos 5, 6, 7, 8) (1) Remove the front panel, the horizontal vanes (uppler R/L), (lower R/L), the corner boxes (R) (L), and the pan- els (U) (R) (refer to section 1). (2) Remove the screw of the V.A.
Page 47
OPERATING PROCEDURE PHOTOS/FIGURES 3. Removing the indoor electronic control P.C. Photo 8 (Enlarged view of the indoor electronic control P.C. board) board, the indoor power P.C. board, the indoor terminal block, and the room temperature CN201 CN211 Indoor power P.C. board thermistor (1) Remove the electrical box (Refer to section 2).
Page 48
OPERATING PROCEDURE PHOTOS/FIGURES 4. Removing the display and i-see sensor assembly, Photo 9 (Details of the display and i-see sensor assembly, the refrigerant sensor assembly (option), the dis- refrigerant sensor assembly, and board in the display cover) play P.C. board, and the receiver P.C. board Photo 9-1 Front view of display and i-see (Photo 9).
Page 49
OPERATING PROCEDURE PHOTOS/FIGURES (6) Disengage the catches of the display cover, remove the Photo 9-4 refrigerant sensor assembly (option) from the display cover (Photo 9-3). (7) Disengage the catch of the refrigerant sensor cover (Photo 9-4). (8) Disconnect the connector of the refrigerant sensor (Photo 9-4).
Page 50
OPERATING PROCEDURE PHOTOS/FIGURES 5. Removing the Wi-Fi assembly (Photos 3, 11) Photo 11 Wi-Fi assembly (1) Remove the front panel, horizontal vanes (upper R/L), (lower R/L), corner boxes (R) (L), and the panels (U) (R). Catch (2)Remove the indoor/outdoor connecting wire and electri- cal cover.
Page 51
OPERATING PROCEDURE PHOTOS/FIGURES 6. Removing the horizontal vanes (R)(L) and the hor- Photo 13 izontal vane motors (R)(L) (Photos 8, 13, 14, 15) (1) Remove the front panel, horizontal vanes (upper R/L), (lower R/L), the corner boxes (R) (L), the panels (U) (R) (L), V.A.
Page 52
OPERATING PROCEDURE PHOTOS/FIGURES 7. Removing the vertical vane motor units (R) (L) Photo 16 3 screws of the horizontal and the vertical vane motors (R) (L) vane motor unit (R) (1) Remove the front panel, horizontal vanes (upper R/L) (lower R/L), the corner boxes (R) (L), the panels (U) (R) (L), V.A.
Page 53
OPERATING PROCEDURE PHOTOS/FIGURES Removing the horizontal vane motor unit (L) and the Photo 19 vane motor (L) (vertical) (Photos 18, 19) (9) Remove the 3 screws of the horizontal motor unit (L) Vertical vane motor unit (L) indicated in (Photo 18). (10) Disengage the catch of the horizontal vane motor unit (L), and remove the horizontal vane motor unit (L).
Page 54
OPERATING PROCEDURE PHOTOS/FIGURES 8. Removing the line flow fan, the indoor fan motor Photo 20 NOTE: assembly, the indoor coil thermistor, and the heat Install the fan motor and lead exchanger (Photos 20, 21, 22, 23, 24) wires in the former position (1) Remove the front panel, the horizontal vanes (upper when assembling the fan motor.
Page 55
Fixing the indoor coil thermistor *There are 2 forms of parts for fixing the indoor coil thermistor. When fixing the indoor coil thermistor to the clip-shape/holder-shape part, the Clip shape Holder shape lead wire should point down. About the same length Position and procedure for mounting the clip-shape part 1.
POSITION OF THE CENTER OF GRAVITY Wall-mounted type Unit: inch (mm) Model name MSZ-FX06NL MSZ-FX09NL MSZ-FX12NL 5-1/4 5-3/16 39-5/16 9-3/4 MSZ-FX15NL (407) (133) (132) (998) (247) (305) MSZ-FX18NL MSZ-FX24NL OBD945A...
NOISE CRITERION CURVES MSZ-FX06NL MSZ-FX09NL NOTCH SPL(dB(A)) LINE NOTCH SPL(dB(A)) LINE COOLING(SHi) COOLING(SHi) HEATING(SHi) HEATING(SHi) NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 NC-20 NC-20 1000 2000 4000 8000 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz MSZ-FX12NL MSZ-FX15NL NOTCH...
Page 58
MSZ-FX18NL MSZ-FX24NL NOTCH SPL(dB(A)) LINE NOTCH SPL(dB(A)) LINE COOLING(SHi) COOLING(SHi) HEATING(SHi) HEATING(SHi) NC-70 NC-70 NC-60 NC-60 NC-50 NC-50 NC-40 NC-40 NC-30 NC-30 NC-20 NC-20 1000 2000 4000 8000 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz WALL UNIT NOTE: The sound level is measured in an anechoic room where echoes are few,...
TEMPERATURE AND AIR FLOW DISTRIBUTIONS MSZ-FX06NL Temperature distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [°C(F)] [°C(F)] 27(81) 27(81) 25(77) 25(77) 21(70) 21(70) 19(66) 19(66) 23(73) 23(73) 25(77) 25(77) 27(81) 27(81) 2000 1000 (78.74) (39.37) Floor distance [ mm (inch) ] <Heating mode>...
Page 60
MSZ-FX06NL Airflow distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [m/s(ft/s)] [m/s(ft/s)] 0.3(1.0) 0.3(1.0) 2.1(6.9) 2.1(6.9) 1.5(4.9) 1.5(4.9) 2.7(8.9) 2.7(8.9) 0.9(3.0) 0.9(3.0) 0.3(1.0) 0.3(1.0) 0.9(3.0) 0.9(3.0) 0.3(1.0) 0.3(1.0) 2000 1000 (78.74) (39.37) Floor distance [ mm (inch) ] <Heating mode> Air volume: super high Air direction: auto (downward air flow) [m/s(ft/s)]...
Page 61
MSZ-FX09NL Temperature distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [°C(F)] [°C(F)] 25(77) 25(77) 23(73) 23(73) 21(70) 21(70) 19(66) 19(66) 25(77) 25(77) 27(81) 27(81) 3000 2000 1000 (118.11) (78.74) (39.37) Floor distance [ mm (inch) ] <Heating mode> Air volume: super high Air direction: auto (downward air flow) [°C(F)] [°C(F)]...
Page 62
MSZ-FX09NL Airflow distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [m/s(ft/s)] [m/s(ft/s)] 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.9(3.0) 0.9(3.0) 1.5(4.9) 1.5(4.9) 0.9(3.0) 0.9(3.0) 2.1(6.9) 2.1(6.9) 2.7(8.9) 2.7(8.9) 0.3(1.0) 0.3(1.0) 0.9(3.0) 0.9(3.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 3000 2000 1000 (118.11) (78.74) (39.37) Floor distance [ mm (inch) ] <Heating mode>...
Page 63
MSZ-FX12NL Temperature distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [°C(F)] [°C(F)] 25(77) 25(77) 23(73) 23(73) 21(70) 21(70) 19(66) 19(66) 25(77) 25(77) 4000 3000 2000 1000 (157.48) (118.11) (78.74) (39.37) Floor distance [ mm (inch) ] <Heating mode> Air volume: super high Air direction: auto (downward air flow) [°C(F)] [°C(F)]...
Page 64
MSZ-FX12NL Airflow distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [m/s(ft/s)] [m/s(ft/s)] 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 1.5(4.9) 1.5(4.9) 2.1(6.9) 2.1(6.9) 2.7(8.9) 2.7(8.9) 0.3(1.0) 0.3(1.0) 0.9(3.0) 0.9(3.0) 0.3(1.0) 0.3(1.0) 0.9(3.0) 0.9(3.0) 4000 3000 2000 1000 (157.48) (118.11) (78.74) (39.37) Floor distance [ mm (inch) ] <Heating mode>...
Page 65
MSZ-FX15NL Temperature distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [°C(F)] [°C(F)] 25(77) 25(77) 23(73) 23(73) 21(70) 21(70) 19(66) 19(66) 25(77) 25(77) 27(81) 27(81) 5000 4000 3000 2000 1000 (196.85) (157.48) (118.11) (78.74) (39.37) Floor distance [ mm (inch) ] <Heating mode>...
Page 66
MSZ-FX15NL Airflow distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [m/s(ft/s)] [m/s(ft/s)] 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 2.1(6.9) 2.1(6.9) 2.7(8.9) 2.7(8.9) 1.5(4.9) 1.5(4.9) 3.3(10.8) 3.3(10.8) 0.3(1.0) 0.3(1.0) 0.9(3.0) 0.9(3.0) 0.9(3.0) 0.9(3.0) 0.3(1.0) 0.3(1.0) 5000 4000 3000 2000 1000 (196.85) (157.48) (118.11) (78.74) (39.37) Floor distance [ mm (inch) ]...
Page 67
MSZ-FX18NL Temperature distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [°C(F)] [°C(F)] 25(77) 25(77) 26(79) 26(79) 24(75) 24(75) 23(73) 23(73) 21(70) 21(70) 19(66) 19(66) 25(77) 25(77) 26(79) 26(79) 27(81) 27(81) 27(81) 27(81) 6000 5000 4000 3000 2000 1000 (236.22) (196.85) (157.48) (118.11) (78.74)
Page 68
MSZ-FX18NL Airflow distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [m/s(ft/s)] [m/s(ft/s)] 0.9(3.0) 0.9(3.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 1.5(4.9) 1.5(4.9) 2.1(6.9) 2.1(6.9) 2.7(8.9) 2.7(8.9) 3.3(10.8) 3.3(10.8) 0.9(3.0) 0.9(3.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.9(3.0) 0.9(3.0) 6000 5000 4000 3000 2000 1000 (236.22) (196.85) (157.48)
Page 69
MSZ-FX24NL Temperature distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [°C(F)] [°C(F)] 25(77) 25(77) 23(73) 23(73) 21(70) 21(70) 19(66) 19(66) 24(75) 24(75) 28(83) 28(83) 25(77) 25(77) 27(81) 27(81) 26(79) 26(79) 9000 8000 7000 6000 5000 4000 3000 2000 1000 (354.33) (314.96) (275.59) (236.22)
Page 70
MSZ-FX24NL Airflow distribution <Cooling mode> Air volume: super high Air direction: auto (upward air flow) [m/s(ft/s)] [m/s(ft/s)] 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 1.5(4.9) 1.5(4.9) 2.7(8.9) 2.7(8.9) 2.1(6.9) 2.1(6.9) 3.3(10.8) 3.3(10.8) 3.9(12.1) 3.9(12.1) 0.9(3.0) 0.9(3.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 0.3(1.0) 9000 8000 7000 6000 5000 4000 3000 2000 1000 (354.33) (314.96)
Need help?
Do you have a question about the MSZ-FX06NL-U1 and is the answer not in the manual?
Questions and answers