Installation guide
Electronic superheat controller
Type EIM 316 / 336
Introduction
Superheat controller EIM series is for use where superheat must be accurately
controlled, typically in commercial air conditioning, commercial and industrial heat pumps,
commercial refrigeration and food retailing applications.
Reference: For details please see EIM data sheet.
Technical speci cations
Supply voltage
Power consumption
Input signals
For the EMC compliance, sensor cable length must be
< 3 m / 118 in. For longer sensor cable, a ferrite bead
should be used.
Valve support
Data communication
Environment
Battery backup (Only for EIM 365)
Operation
EIM 316 / 336
Power
MODbus
GND
1 2
1
3 4
3 4
ø 3 mm /
0.118 in
5 mm / 0.2 in
© Danfoss | Climate Solutions | 2024.03
Battery
Pressure
BAckup
sensor
S2
S4
2
1
1
2
1
1
2
3
4
2
2
80 mm / 3.15 in
ENGINEERING
T O M O R R O W
24 V AC / DC (+ 15%), 50 / 60 Hz, 15 VA / 8 W, Class II isolation
Idle
Max. 10 mA @ 24 V DC
Max. 150 mA @ 24 V DC
Operating
Po
0.5 - 4.5 Vdc ratiometric pressure sensor i.e AKS 32R
S2
PT1000 (measuring range -60 – 120 °C /
-76 – 248 °F)
S4
PT1000 or digital input from external contact
EIM 316 / 336: ETS 6
RS 485 – MODBUS RTU (Not terminated internally)
Storage
: -34 – 71 °C / -30 – 160 °F
Operating : -25 – 60 °C / -13 – 140 °F
Humidity : < 95% RH, non condensing
18 - 28 V DC, > 49 VmAh
Standalone or via MODBUS data communication
Note:
S2 - Temperature sensor
S4 - Temperature sensor or DI
Weight : 40 gm
EIM 336: Use metal pins to con-
nect GND.
089
More info
AN327425434124en-000303 | 1

Advertisement

loading
Need help?

Need help?

Do you have a question about the EIM 316 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Danfoss EIM 316

  • Page 1 -76 – 248 °F) should be used. PT1000 or digital input from external contact Valve support EIM 316 / 336: ETS 6 Data communication RS 485 – MODBUS RTU (Not terminated internally) Storage : -34 – 71 °C / -30 – 160 °F Environment Operating : -25 –...
  • Page 2 Danfoss does not assume any liability for damages, injuries, or adverse consequences (“damage”) resulting from the incorrect or improper use of the product and you agree to indemnify Danfoss for any such damage resulting from your incorrect or improper use of the product.
  • Page 3 Select valve setting Select Application mode o18 (ADU 36) = 1 For EIM 365, rst select Danfoss valve type (ADU 110). If valve is not preset use user de ned and set additional i.e., Manual control First select Danfoss valve type (ADU 110).
  • Page 4 8000 ü ü Max steps (384 x 10 microsteps = 480 half steps) (1000) (384) EIM 316 (Values in bracket is for EIM 316,336) and 336 default is ü ü Max steps / sec Steps per second ETS 6 )

This manual is also suitable for:

Eim 336