Installation guide
Electronic superheat controller
Type EIM 316 / 336
Introduction
Superheat controller EIM series is for use where superheat must be accurately
controlled, typically in commercial air conditioning, commercial and industrial heat pumps,
commercial refrigeration and food retailing applications.
Reference: For details please see EIM data sheet.
Technical speci cations
Supply voltage
Power consumption
Input signals
For the EMC compliance, sensor cable length must be
< 3 m / 118 in. For longer sensor cable, a ferrite bead
should be used.
Valve support
Data communication
Environment
Battery backup (Only for EIM 365)
Operation
EIM 316 / 336
Power
MODbus
GND
1 2
1
3 4
3 4
ø 3 mm /
0.118 in
5 mm / 0.2 in
© Danfoss | Climate Solutions | 2024.03
Battery
Pressure
BAckup
sensor
S2
S4
2
1
1
2
1
1
2
3
4
2
2
80 mm / 3.15 in
ENGINEERING
T O M O R R O W
24 V AC / DC (+ 15%), 50 / 60 Hz, 15 VA / 8 W, Class II isolation
Idle
Max. 10 mA @ 24 V DC
Max. 150 mA @ 24 V DC
Operating
Po
0.5 - 4.5 Vdc ratiometric pressure sensor i.e AKS 32R
S2
PT1000 (measuring range -60 – 120 °C /
-76 – 248 °F)
S4
PT1000 or digital input from external contact
EIM 316 / 336: ETS 6
RS 485 – MODBUS RTU (Not terminated internally)
Storage
: -34 – 71 °C / -30 – 160 °F
Operating : -25 – 60 °C / -13 – 140 °F
Humidity : < 95% RH, non condensing
18 - 28 V DC, > 49 VmAh
Standalone or via MODBUS data communication
Note:
S2 - Temperature sensor
S4 - Temperature sensor or DI
Weight : 40 gm
EIM 336: Use metal pins to con-
nect GND.
089
More info
AN327425434124en-000303 | 1