UV1000-PM Programmable Universal Verbalizer Table of Contents Section Page Section 1 Introduction ............... 1-1 1.1 Safety Considerations ............1-2 1.2 Before You Begin ..............1-3 Section 2 Setup ..................2-1 2.1 Front Panel ................2-1 2.2 Rear Panel Connections ..........2-1/2-2 2.3 Power Connections ..............
Page 4
UV1000-PM Programmable Universal Verbalizer Table of Contents 4.5.10 The Set and Read buttons ....4-9 4.5.11 Application Examples of Rescaling the Engineering Unit ....4-10 4.5.11.1 Voltage input settings and rescaling .
UV1000-PM Programmable Universal Verbalizer NOTES, WARNINGS and CAUTIONS Information that is especially important to note is identified by following labels: • NOTE • WARNING or CAUTION • IMPORTANT • TIP NOTE: Provides you with information that is important to successfully setup and use the Programmable Digital Meter.
UV1000-PM Programmable Universal Verbalizer Section 1 - Introduction The UV1000-PM universal verbalizer panel meter is an innovative panel meter that can verbalize and display process signals. It can accept 0 to 10 Vdc voltage input, 0 to 20 mA or 4 to 20 mA current input, and Type J, K, T, and R thermocouple input signals.
UV1000-PM Programmable Universal Verbalizer 1.1 Safety Considerations This device is marked with the international caution symbol. It is important to read this manual before installing or commissioning this device as it contains important information relating to Safety and EMC (Electromagnetic Compatibility). Installation of this instrument should be done by qualified personnel.
UV1000-PM Programmable Universal Verbalizer 1.2 Before You Begin Inspecting Your Shipment: Remove the packing slip and verify that you have received everything listed. Inspect the container and equipment for signs of damage as soon as you receive the shipment. Note any evidence of rough handling in transit.
UV1000-PM Programmable Universal Verbalizer Section 2 – Setup 2.1 Front Panel UV1000-PM MODE DOWN TALK Figure 2.1 Front panel display Table 2.1 Front Panel Annunciators Thermocouple input indicator Voltage input indicator Current input indicator Not in use Alarm indicator MODE Change the input selection ▲...
UV1000-PM Programmable Universal Verbalizer 2.3.1 Thermocouple Input The figure below shows the wiring hookup for any thermocouple type. For example, for Type K hookup, connect the yellow wire to the "4" terminal - TC(+) and the red wire to the "3" terminal – TC(-). When configuring your Verbalizer, select Thermocouple and Thermocouple Type in the Input Type menu (see Part 3 and Part 4.5.6 TC Setup).
UV1000-PM Programmable Universal Verbalizer 2.3.3 Process Current Input The figure below shows the wiring hookup for Process Current 0 – 20 mA. 1 2 3 4 5 6 7 8 9 0 ~20 mA External Excitation – – Figure 2.7 Process Current Wiring Hookup (External Excitation) When configuring your instrument, select Current Type in the Input Type Menu.
UV1000-PM Programmable Universal Verbalizer This device has snubber circuits designed to protect the contacts of the mechanical relays when it switches to inductive loads (i.e. solenoids, relays). These snubbers are internally connected between the Common (C) and Normally Open (NO) relay con- tacts of Output 1 and Output 2.
Verbalizer - User Configuration Software Section 3 – Front Panel Button Operation 3.1 MODE button - Change the Input Selections Press the MODE button to select the input for the display and verbalize. TC input Voltage input Current input TC input Press MODE Press Press...
If the program didn’t install automatically, click Windows Start Run, click Browse… find your D: drive and select setup.exe file and then click OK button You can also visit www.omega.com or our ftp website to update latest Verbaview™ software - ftp://ftp.omega.com/public/TEMPERATUREGroup/products/UV1000-PM/ 4.2 Starting the Verbaview™ Program Connect the Universal Verbalizer UV1000 to your PC through RS232 cable.
Verbalizer - User Configuration Software 4.3.1 Select the COM port which connects to your Universal Verbalizer and the Speed (Baud Rate) is fixed at 9600bit/sec 4.3.2 Check the “Skip Logo Sound” to disable the sound effect during the Verbaview program at start up. 4.3.3 Talking Interval.
Verbalizer - User Configuration Software 4.4 Calibrate Tag This function is disabled (grayed out) and is only for factory calibration use. 4.5 Input Tag...
Verbalizer - User Configuration Software 4.5.1 Select the Input Type You can select T-Couple (Thermocouple) Input, Voltage Input or Current Input by click the pull down list. On the panel meter display, there are LED indicators to indicate the input selections. ( see 2.1 for indication references) •...
Page 21
Verbalizer - User Configuration Software • Voltage input configuration interface • Current input configuration interface...
Verbalizer - User Configuration Software 4.5.2. Select the Engineering Unit Select the Engineering Unit from the trees at Engineering Units window after you select the Input type. The Engineering Units categories are: • Acceleration • Area • Conductivity • Dissolved •...
Verbalizer - User Configuration Software 4.5.3 Select the Decimal Point You can select the Decimal Point for the verbal number. You can select no decimal point, one decimal, two decimal point and up to three decimal point. Thermocouple Input: x, x.x (Note: When you select one decimal point in TC input mode, the temperature display resolution on the LED display will be 0.5 ∞F/∞C) Voltage and Current Input: x, x.x, x.xx, x.xxx;...
Verbalizer - User Configuration Software If you set the Alarm Deadband value, the high alarm will not stop until the display value below (High Alarm value - Alarm Deadband value) and the low alarm will not stop until the display value above the (Low Alarm + Alarm Deadband) value.
Verbalizer - User Configuration Software 4.5.7 Voltage Range – (Voltage input only, will be grayed out in other analog input selection) You can select the voltage range 0-1v, 0-5v or 0-10v. Also you can type in the specified Min and Max voltage value into the text box. The maximum voltage value should not exceed 10Vdc and the minimum voltage values should not less than 0 voltage.
4.5.11 Application Examples of Rescaling the Engineering Unit 4.5.11.1 Voltage Input Settings and Rescaling Application Example 1: General Purpose Output Pressure Transducer Omega Model Number: PX303-100A5V Output: 0.5 – 5.5 Vdc Pressure Range: 0-100 PSIA The following PC user interface graphic, showing all the configuration settings and values for this application example.
Page 27
Verbalizer - User Configuration Software d. Input the voltage range value to the text boxes These text boxes are for the voltages input values: e. Input the Engineering Unit range value to the text boxes These text boxes are for Engineering Units input values: f.
Verbalizer - User Configuration Software Application Example 2: High Temperature Handheld Infrared Thermometer Omega Model Number: OS523E Analog Output: 1 mV/deg Temperature Range: 0 to 2500°F The following PC user interface graphic, showing all the configuration settings and values for this application example.
Page 29
Verbalizer - User Configuration Software b. Select the Engineering Unit – Degree F. c. Select the decimal points x – No decimal point d. Input the voltage range value to the text boxes Calculate the Voltage Range: Since the Analog Output: 1 mV/deg and the Temperature Range is 0 - 2500°F The Voltage Min = 1 mV/deg * 0 deg = 0 mV = 0 V;...
Page 30
Verbalizer - User Configuration Software f. Set the High or Low alarm Value, and Alarm Deadband enable or disable the High or Low alarm settings. g. Click the Set button to send the settings to Universal Verbalizer. h. After a few seconds, you will see ‘Configuration OK!’ message at the bottom of the User interface.
Application Example 3: Miniature Low Cost Non-Contact IR Temperature Sensor/Transmitter Omega part number: OS101-MA Transmitter with 4 to 20 mA output Current Output: 4 to 20 mA Temperature Range: 0 to 1000°F The following PC user interface graphic, showing all the configuration settings and values for this application example.
Page 32
Verbalizer - User Configuration Software b. Select the Engineering Unit – Degree F. c. Select the no decimal points – x d. Input the Current range value to the text boxes This Transmitter Current Output range is : 4 – 20 mA Select Current Range 4-20 or just type in 4 to Min text box and 20 to Max text box e.
Page 33
Verbalizer - User Configuration Software f. Set the High or Low alarm value and Alarm Deadband Enable or disable the High or Low alarm settings g. Click the Set button to send the settings to Universal Verbalizer h. After a few seconds, you will see ‘Configuration OK!’ message at the bottom of the User interface.
Verbalizer - User Configuration Software Application Example 4: Liquid Flow Transmitters Omega Model number: FPR205-PC 500, transmitter with clear cover Current Output: 4 – 20 mA Flow Measuring Range: 0.5 to 15.0 GPM The following PC user interface graphic, showing all the configuration settings and values for this application example.
Page 35
Verbalizer - User Configuration Software b. Select the Engineering Unit – GPM at Engineering Unit window c. Select the one decimal points – x.x d. Input the Current range value to the text boxes This transmitter Current Output is 4 – 20 mA Select Current Range to 4-20 or type in the Min and Max value in the text boxes.
Page 36
Verbalizer - User Configuration Software f. Set the High or Low alarm value and the Alarm Deadband Enable or disable the High or Low alarm settings g. Click the Set button to send the settings to Universal Verbalizer. h. After a few seconds, you will see ‘Configuration OK!’ message at the bottom of the User interface.
Verbalizer - User Configuration Software 4.6 Load/Save Tag At this tag, you can Load the saved previous configuration settings from your PC to the program. Or you can save the Configuration settings to your PC for future reference. 4-21...
Verbalizer - User Configuration Software 4.7 Error Messages • You may get the error message “Did not receive SOH or EOT when expected”. If this happens, please make sure the Universal Verbalizer power is turn on, check the COM port selection in Settings tag, the cable connections between PC and Universal Verbalizer and then try again •...
Verbalizer - User Configuration Software Section 5 - Specifications: 0-10 Vdc Voltage Input: Input Impedance: 500 K ohms Current Input: 0-20 mA, 4-20 mA Voltage and Current Input: Accuracy: 0.2% of full scale Thermocouple Input: Type K, J, T and R Type K: -100 to 871°C (-148 to 1600°F) Thermocouple Range: Type J: -75 to 650°C (-103 to 1202°F)
Verbalizer - User Configuration Software Inputs Input Types Range Accuracy Process Voltage 0 to 10 Vdc 0.2% of full scale 0 to 20 mA or 0.2% of full scale Process Current 4 to 20 mA CHROMEGA ® -148 to 1600°F 3.6°F ALOMEGA ®...
Page 41
Verbalizer - User Configuration Software • TC Input: Engineering Unit: Degree F TC Type: K TC Offset: 0 Decimal Point: x – No decimal points Alarms are disabled Low Alarm: -100 High Alarm: 1600 Alarm Deadband: 0 Talking interval: 3 s •...
Verbalizer - User Configuration Software Appendix 2 Engineering Units Table: Categories Engineering Units --> For the tree of PC GUI Note Acceleration Centimeter per square second Metric Meter per square second Foot per square second English Inch per square second Area Metric Square centi-meter...
Page 43
Verbalizer - User Configuration Software Categories Engineering Units --> For the tree of PC GUI Note Energy Newton meter English Inch pound force Joule Kilojoule Gram Calorie Calorie Metric Horsepower-hour Watt Hour Kilowatt-hour Electron volt Flow Gram/second Metric Kilogram/Minute Ton/day Cubicmeter per minute Milliliter per minute Ounce/second...
Page 44
Verbalizer - User Configuration Software Categories Engineering Units --> For the tree of PC GUI Note Length cont. Foot English Inch Yard Mile Power Watt Kilowatt Horsepower Calorie (IT) per hour Pressure Inch of Mercury English Inch of water Foot of water Pound per Square foot Atmosphere Metric...
Page 45
Verbalizer - User Configuration Software Categories Engineering Units --> For the tree of PC GUI Note Time Week Month Hour Minute Second Turbidity NTU - Nephelometric Turbidity Unit Vacuum Torr Velocity Meter per second Metric Knot's Foot per second English Inch per second Foot per Minute Inch/Minute...
Page 46
Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification.
Where Do I Find Everything I Need for Process Measurement and Control? OMEGA…Of Course! Shop online at omega.com TEMPERATURE Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies Wire: Thermocouple, RTD & Thermistor Calibrators & Ice Point References Recorders, Controllers & Process Monitors...