Use a quenching cloth for brazing, and place a fire extinguisher close to the work area. The info symbol indicates important information where there is no risk to property or people. CA Series Heat Pumps - 8733851021 (2025/04) US...
If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed. CA Series Heat Pumps -8733851021 (2025/04) US...
J — Disconnect Switch M — Wire to 208 V O — Outside Air Damper X — As default for non used electrical codes REFRIGERATION CIRCUIT OPTIONS: X — None Figure 1 CA Series Heat Pumps - 8733851021 (2025/04) US...
Installation, Operation, and Maintenance Manual 3 General Description CA series water-to-air heat pumps are designed for use as decentralized room terminals that are field connected to a closed-circuit piping loop within a structure. Typically these units are installed in perimeter zones and are ideal for installations where ducted systems are impractical.
Page 8
Note: Maximum and minimum operating limits may not be combined. Refer to Engineer Submittal Sheet on the product information page. (See the QR code in the Troubleshooting section of the IOM). Acronyms: LWT: Leaving Water Temperature EXT: Extended Range application option EWT: Entering Water Temperature STD: Standard application option Table 1 CA Series Heat Pumps - 8733851021 (2025/04) US...
[1] CA Model Water-to-Air Heat Pump [2] Installation and Operation Manual 5 Initial Inspection Please inspect the product carefully for any defects or discrepancies. Should you identify any issue, contact the Bosch Wholesaler / Distributor you purchased the unit from. NOTICE NOTICE...
Never stretch or twist hoses and never use hoses that show screws in the unit sub base. external wear or damage or are suspected of having damage. Never exceed the manufacturer’s maximum working pressure recommendations. 10 | CA Series Heat Pumps - 8733851021 (2025/04) US...
10.1.2 Units with Disconnect Switch Power Supply For models with disconnect switches, connect the field power to the marked terminals on the disconnect switch, and the ground to the ground lug. CA Series Heat Pumps -8733851021 (2025/04) US | 11...
When the UPM DIP switch position “2” is set to “ON” (R) refer to the UPM section for reset instructions. Y1 call relay Thermostat terminal block Optional relays Pressure relays Figure 6 Low Voltage Electrical Box. Unit Mounted Controller (UMC) Option layout CA Series Heat Pumps -8733851021 (2025/04) US | 13...
When a malfunction light is used for diagnostic purposes, the connection is made at [11] A2L Sensor (field supplied) the dry contact connection terminals of the UPM board. [12] 24VAC Power Common 14 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Page 15
If temperature drops below or remains at the freeze limit trip for 120 seconds, the controller will shut down the compressor and enter into a soft-lockout condition. The default freeze limit trip is 25°F. CA Series Heat Pumps -8733851021 (2025/04) US | 15...
270 to 300 seconds on initial power up to reduce the chance of multiple unit simultaneously starting at the same time after power up or after a power interruption, in order to avoid creating a large electrical spike. 16 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Page 17
If this alarm occurs two times (or four times if DIP switch position “1” is set to “ON”)(Refer to Figure 9)(See Table 3) within an hour, the controller will enter into a hard-lockout condition. CA Series Heat Pumps -8733851021 (2025/04) US | 17...
Maintaining proper water quality is important for insuring a long and trouble free service life for an CA series heat pump. (Refer to the Water Quality Table 6) For closed loop and boiler/tower systems water chemistry can be checked and easily maintained to ensure that corrosive elements, dissolved oxygen and pH levels are kept in check.
Record all system vitals using the “checkout sheet” and keep with equipment. Operate unit in the cooling cycle first, then the heating cycle for unit operating limits. Allow 15 minutes between cooling and heating tests for pressure to equalize. CA Series Heat Pumps -8733851021 (2025/04) US | 21...
• air temperature problems Use of the pressure and temperature charts for the unit may be required to properly determine the cause. 22 | CA Series Heat Pumps - 8733851021 (2025/04) US...
At all times the manufacturer's maintenance and for or detection of refrigerant leaks. A halide torch (or any other detector using a service guidelines must be followed. If in doubt, consult Bosch service and support naked flame) must NOT be used.
Ensure the system is leak-tested on completion of charging but prior to commissioning. A follow-up leak test must be carried out prior to leaving the site. 24 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Equipment must be labeled stating that it has been decommissioned and emptied of refrigerant. The label must be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. CA Series Heat Pumps -8733851021 (2025/04) US | 25...
Inspect the air coil for dirt/debris. Is the Fault LED blinking two (2) times? Check duct work—Are dampers closed or blocked? Low pressure fault—Low Check refrigerant pressure with a gauge set. refrigerant 26 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Page 27
Blocked return air times? on free return applications. Condensate fault— False Check that the condensate sensor is mounted on the drain pan, and the trigger terminal is not touching sheet metal. CA Series Heat Pumps -8733851021 (2025/04) US | 27...
Page 28
If not check the resistance of the compressor windings using Burned out compressor the values shown in the compressor characteristics chart. Note that the compressor must be cool (70° F) when checking the windings. 28 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Page 29
For 75 and 100 VA transformers, check Faulty control that the transformer circuit breaker has not tripped. transformer Check low voltage circuit for overload conditions or short circuits before replacing the transformer. CA Series Heat Pumps -8733851021 (2025/04) US | 29...
Page 30
High humidity Unit oversized Check unit performance against building load calculations. Short cycling Poor thermostat Make sure that the thermostat is not located near a supply air duct. location 30 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Page 31
Compressor noise Scaled or fouled water coil elevating heat pres- Clean/descale water coil. sure Check filter. Low air flow elevating head pressure Increase fan speed. Table 6 Unit Troubleshooting CA Series Heat Pumps -8733851021 (2025/04) US | 31...
Installation, Operation, and Maintenance Manual 21 Blower Performance Data CFM @ 0.0 in.w.g Model Motor Speed Factory setting Cooling Heating High CA009 High CA012 High CA015 High CA018 Table 7 32 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Installation, Operation, and Maintenance Manual 25 Wiring Diagrams Figure 11 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. CA Series Heat Pumps -8733851021 (2025/04) US | 37...
Page 38
Installation, Operation, and Maintenance Manual Figure 12 FOR REFERENCE ONLY Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 38 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Notes: All dimensions in inches unless otherwise noted. All dimensions within +-0.125". Specifications subject to change without notice. Fresh Air Opening (In Sub-base Rear) : Caution! When installing unit in cold climates, an outside air damper must be provided to prevent possible condenser freeze-up. Table 14 40 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Decommissioning — Means the final shut-down and removal from operation or usage of a product or piece of equipment containing fluorinated greenhouse gases. Discharge Pressure — Referring to the pressure leaving compressor. CA Series Heat Pumps -8733851021 (2025/04) US | 43...
Page 45
Installation, Operation, and Maintenance Manual CA Series Heat Pumps -8733851021 (2025/04) US | 45...
Page 46
Installation, Operation, and Maintenance Manual 46 | CA Series Heat Pumps - 8733851021 (2025/04) US...
Page 47
Installation, Operation, and Maintenance Manual CA Series Heat Pumps -8733851021 (2025/04) US | 47...
Page 48
8733851021/ (2025/04) US To see additional product information and documentation, please visit the product page: Bosch Thermotechnology Corp. reserves the right to www.bosch-homecomfort.com/us/ or scan the QR code below. make changes without notice due to continuing engineering and technological advances.